Cut a square hole and clear any roofing material so frame with proper minimum opening can be installed (See Table 9).
When cutting the opening, allowance must be made for the thickness of the frame.
NOTICE
In the event that roof joists must be cut - follow the building codes having jurisdiction for reframing the opening.
For roof curb installations (recommended): Refer to minimum opening in Table 9 for framing size for masonry pour
and Table 8 for roof jack dimensions. Roof curbs may also be purchased at your local building supply store.
INSTALLING ON A FRAMED OPENING
Implementing "best practice" and / or "preferred" methods. Drill sufficient holes in the roof jack plate.
Place the Roof Jack Support System (conical side up) by centering it over and lowering it down onto the frame and transfer
the position of the drilled holes from the plate onto the frame. Temporarily remove the Roof Jack for adhesive application.
Apply the appropriate weather resistant adhesive to the frame observing the hole markings.
Install the Roof Jack Support System (conical side up) by centering it over the framed opening and lowering it onto the
frame and secure it using screws equipped with neoprene washers.
Using the appropriate roofing methods reapply the roofing material over the plate to maintain the roofing integrity.
Install the flashing over the roof jack by implementing the standard contractor roofing methods.
INSTALLING ON A CURB
Implementing "best practice" and / or "preferred" methods. Drill sufficient holes in the roof jack plate.
Place the Roof Jack Support System (conical side up) by centering it over and lowering it down onto the curb and transfer
the location of the drilled holes from the plate onto the curb. Temporarily remove the Roof Jack. Select the appropriate
masonry drill bit size for the concrete screws being used and drill the marked holes in the curb to the prescribed depth.
Apply the appropriate weather resistant adhesive to the curb observing the hole markings.
Install the Roof Jack Support System (conical side up) by centering it over and lowering it down onto the curb again. This
time fasten the plate to the curb with concrete screws equipped with neoprene washers.
Seal where the plate meets the curb with the appropriate weather resistant sealant.
INSTALLING VENT PIPE THROUGH ROOF JACK SUPPORT SYSTEM
Where double wall pipe with ZV-Clamp is to be used with a roof jack assembly, do not install the ZV-Clamp inside the roof jack.
Instead install mating flanges in slotted sections located in Pipe Joint Range of Roof Jack Coupling assembly (See Illustration 4)
supplied with the Roof Jack Support System. Connect the two prescribed lengths of pipe (above and below roof) and couple them
together with Roof Jack Coupling Assembly. Position the pipe joint in the notched area of the coupling assembly (See Illustration 5).
Tighten the lock-nuts onto the bolts that clamp the assembly onto the pipe to a torque specification of 70 in/lbs. / 6 ft-lbs / 8
Nm.
Large
End
UP
Outside
Pipe
Joint
Range
Illustration 4
Inside
Roof Jack Pipe Assembly
DOWN
Small
End
Illustration 5
Page 20 of 28
Lower the pipe assembly maintaining the proper pipe orientation (gasket end up) into the previously installed Roof Jack
Support until the coupling assembly is fully seated. (See Illustration 6)
Illustration 6
Pipe
Joint
Roof Jack Coupling Assembly
Install mating
flanges of double
wall ZV-Clamp pipes
in slotted sections