DOUBLE WALL: 
1.  Align pipes and push them together until the snap-lock 
engages. (Illustration #1A, Images 4, 5 & 6). 
Proper pipe orientation is essential to achieve effective 
condensate flow. In most cases the use of an appliance 
specific flue collar adaptor is required to connect directly to 
the appliance. This adaptor will configure the vent orientation 
with the gasket end of pipe and fittings towards termination. 
Also: 
Some flue collars may require the use of high temperature 
silicone sealant to make a positive pressure gas tight seal. In some cases a clamping mechanism may be necessary to 
secure the adaptor to the appliance. 
IMAGES BELOW SHOW DOUBLE WALL PIPE CONNECTION 
Image 4  Image 5 
Image 6 
SYSTEM  SYSTEM OPERATING 
TEMPERATURE  
CLEARANCE 
ENCLOSED VERTICAL 
CLEARANCE 
UNENCLOSED 
   HORIZONTAL VERTICAL 
SINGLE WALL 
550°F (288°C) 
480 F (249 C) 
300 F (149 C) 
6” (150 mm) 
4” (100 MM) 
4” (100 MM) 
Pipe 3” (76 mm) 
Thimble-6”(25 mm) 
1” (25 MM) 
1” (25 MM) 
3” (152 mm) 
1” (25 MM) 
1” (25 MM) 
DOUBLE WALL 
550°F (288°C) 
480 F (249 C) 
300 F (149 C) 
6” (150 mm) 
4” (100 MM) 
4” (100 MM) 
Pipe-2” (51 mm) 
Thimble-3” (76 MM) 
1” (25 MM) 
1” (25 MM) 
2” (51 mm) 
1” (25 MM) 
1” (25 MM) 
Table 2 
NOTICE 
Illustration 1A 