Install Instructions
Page 15 of 18 
TYPICAL ECCENTRIC INCREASER / SINGLE WALL TO DOUBLE WALL APPLICATION 
¾  Eccentric Increaser (see illustration #3) 
shall be used when increasing the 
appliance vent diameter or system 
diameter from one size to a larger size 
in a “horizontal application”. (Refer to 
appliance installation & operating 
manual and /or engineered approved 
design) 
¾ The Z-Vent Eccentric Increaser 
provides a level wall allowing the 
condensate to flow unimpeded back to 
drain.(see Vent Pipe Slope pg. 7) 
¾ A Z-Vent Single Wall to Double Wall 
fitting is necessary when transitioning 
from a single wall vent system to a 
double wall vent system. 
TYPICAL CONCENTRIC INCREASER APPLICATION 
¾  Concentric Increasers shall be used when increasing the 
vent diameter or system diameter from one size to a 
larger size in a “vertical application”. (Refer to 
appliance installation & operating manual and /or 
engineered approved design) 
¾ The Z-Vent Concentric Increaser provides a conical 
wall allowing the condensate to flow vertically unimpeded 
back to drain.(see Vent Pipe Slope pg. 7) 