Installation manual
● A short circuit or earth fault on the inverter output side may damage the
inverter modules.
– Fully check the insulation resistance of the circuit prior to inverter oper-
ation since repeated short circuits caused by peripheral circuit inade-
quacy or an earth fault caused by wiring inadequacy or reduced motor
insulation resistance may damage the inverter modules.
– Fully check the to-earth insulation and inter-phase insulation of the
inverter output side before power-on.
Especially for an old motor or use in hostile atmosphere, securely check
the motor insulation resistance etc.
● Do not use the inverter input side magnetic contactor to start/stop the
inverter. Always use the start signal (ON/OFF of STF and STR signals) to
start/stop the inverter.
● Across + and PR terminals, connect only an external regenerative brake dis-
charge resistor. Do not connect a mechanical brake.
The brake resistor can not be connected to the FR-D720S-008 and 014.
Leave terminals + and PR open.
Also, never short between + and PR.
● Do not apply a voltage higher than the permissible voltage to the inverter
I/O signal circuits.
Application of a voltage higher than the permissible voltage to the inverter
I/O signal circuits or opposite polarity may damage the I/O devices. Espe-
cially check the wiring to prevent the speed setting potentiometer from
being connected incorrectly to short terminals 10-5.
● Provide electrical
and mechanical
interlocks for MC1
and MC2 which are
used for bypass
operation.
When the wiring is
incorrect or if there
is a bypass circuit
as shown on the right, the inverter will be damaged by leakage current
from the power supply due to arcs generated at the time of switch-over or
chattering caused by a sequence error.
● If the machine must not be restarted when power is restored after a power
failure, provide a magnetic contactor in the inverter's input side and also
make up a sequence which will not switch on the start signal. If the start sig-
nal (start switch) remains on after a power failure, the inverter will automat-
ically restart as soon as the power is restored.
● Instructions for overload operation
When performing operation of frequent start/stop of the inverter,
increase/decrease in the temperature of the transistor element of the
inverter may repeat due to a continuous flow of large current, shortening
the life from thermal fatigue. Since thermal fatigue is related to the amount
of current, the life can be increased by reducing bound current, starting
current, etc. Decreasing current may increase the life. However, decreasing
current will result in insufficient torque and the inverter may not start.
Therefore, increase the inverter capacity to have enough allowance for cur-
rent.
● Make sure that the specifications and rating match the system require-
ments.
● When the motor speed is unstable, due to change in the frequency setting
signal caused by electromagnetic noises from the inverter, take the follow-
ing measures when applying the motor speed by the analog signal.
– Do not run the signal cables and power cables (inverter I/O cables) in
parallel with each other and do not bundle them.
– Run signal cables as far away as possible from power cables (inverter I/
O cables).
– Use shield cables as signal cables.
– Install a ferrite core on the signal cable (Example: ZCAT3035-1330 TDK).
6 Specifications
Category of Safe Torque of Function:
The FR-D700 adjustable frequency AC drive family is suitable for emergency
stop according to EN 60204-1, stop category 0 within safety related applica-
tions according to EN 954-1 up to safety category 3.
Environment
Before installation, check that the environment meets following specifications.
햲
Temperature applicable for a short time, e.g. in transit.
Single-phase 200 V power supply
햲
The applied motor capacity indicated is the maximum capacity applicable for use
of the Mitsubishi 4-pole standard motor.
햳
The rated output capacity indicated assumes that the output voltage is 230 V.
햴
The % value of the overload current rating indicated is the ratio of the overload
current to the inverter’s rated output current. For repeated duty, allow time for
the inverter and motor to return to or below the temperatures under 100 % load.
햵
The maximum output voltage does not exceed the power supply voltage. The
maximum output voltage can be changed within the setting range. However, the
pulse voltage value of the inverter output side voltage remains unchanged at
about that of the power supply.
햶
The power supply capacity varies with the value of the power supply side inverter
impedance (including those of the input reactor and cables).
Three-phase 400V power supply
햲
The applied motor capacity indicated is the maximum capacity applicable for use
of the Mitsubishi 4-pole standard motor.
햳
The rated output capacity indicated assumes that the output voltage is 440 V.
햴
When operating the inverter with an ambient temperature of 40 °C, the rated out-
put current is the value in parenthesis.
햵
The % value of the overload current rating indicated is the ratio of the overload
current to the inverter’s rated output current (ambient temperature of 50 °C). For
repeated duty, allow time for the inverter and motor to return to or below the
temperatures under 100 % load.
햶
The maximum output voltage does not exceed the power supply voltage. The
maximum output voltage can be changed within the setting range. However, the
pulse voltage value of the inverter output side voltage remains unchanged at
about that of the power supply.
햷
The power supply capacity varies with the value of the power supply side inverter
impedance (including those of the input reactor and cables).
6.1 Cables and wiring length
The following tables indicates a selection example for the wiring length of
20 m.
Single-phase 200 V class (when input power supply is 220 V)
Three-phase 400 V class (when input power supply is 440 V)
햲
The recommended cable size is that of the HIV cable (600 V class 2 vinyl-insulated
cable) with continuous maximum permissible temperature of 75 °C. Assumes that
the ambient temperature is 50 °C or less and the wiring distance is 20 m or less.
햳
The recommended cable size is that of the THHW cable with continuous maxi-
mum permissible temperature of 75 °C. Assumes that the ambient temperature is
40 °C or less and the wiring distance is 20 m or less.
(Selection example for use mainly in the Unite States.)
햴
The recommended cable size is that of the PVC cable with continuous maximum
permissible temperature of 70 °C. Assumes that the ambient temperature is 40 °C
or less and the wiring distance is 20 m or less.
(Selection example for use mainly in Europe.)
햵
The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, PR,
+, , P1 and a screw for earthing.
(For single-phase power input, the terminal screw size indicates the size of termi-
nal screw for L1, N, U, V, W, and a screw for earthing (grounding).)
Inverter
Undesirable Current
M
3~
Interlock
Power
supply
Ambient
temperature
10 °C to +50 °C (non-freezing)
Ambient
humidity
90 % RH or less (non-condensing)
Storage
temperature
20 °C to +65 °C
햲
Atmosphere
Free from corrosive and explosive gases, free from dust
and dirt
Maximum
altitude
Maximum 1000 m above sea level for standard operation.
After that derate by 3 % for every extra 500 m up to
2500 m (91 %).
Vibration 5.9 m/s² or less at 10 to 55Hz (directions of X, Y, Z axes)
FR-D720S-첸첸첸-EC 008 014 025 042 070 100
Rated motor capacity
[kW]
햲
0.1 0.2 0.4 0.75 1.5 2.2
Output
Output capacity
[kVA]
햳
0.3 0.6 1.0 1.7 2.8 4.0
Rated
current [A]
0.8 1.4 2.5 4.2 7.0 10.0
Overload current
rating
햴
200 % of rated motor capacity for 0.5 s;
150 % for 60 s
Voltage
햵
3-phase AC, 0 V to power supply voltage
Power supply
Power supply
voltage
1-phase, 200–240 V AC
Voltage range 170–264 V AC at 50/60 Hz
Power supply
frequency
50/60 Hz ± 5 %
Rated input
capacity [kVA]
햶
0.5 0.9 1.5 2.3 4.0 5.2
Protective structure IP20
Cooling system Self cooling
Forced air
cooling
Weight [kg] 0.5 0.5 0.9 1.1 1.5 2.0
2
FR-D740-첸첸첸-EC 012 022 036 050 080 120 160
Rated motor capacity
[kW]
햲
0.4 0.75 1.5 2.2 3.7 5.5 7.5
Output
Output capacity
[kVA]
햳
0.9 1.7 2.7 3.8 6.1 9.1 12.2
Rated
current [A]
햴
1.2
(1.4)
2.2
(2.6)
3.6
(4.3)
5.0
(6.0)
8.0
(9.6)
12.0
(14.4)
16.0
(19.2)
Overload current
rating
햵
200 % of rated motor capacity for 0.5 s;
150 % for 60 s
Voltage
햶
3-phase AC, 0V to power supply voltage
Power supply
Power supply
voltage
3-phase, 380–480 V AC
Voltage range 325–528 V AC at 50/60 Hz
Power supply
frequency
50/60 Hz ± 5 %
Rated input
capacity [kVA]
햷
1.5 2.5 4.5 5.5 9.5 12 17
Protective structure IP20
Cooling system Self cooling Forced air cooling
Weight [kg] 1.3 1.3 1.4 1.5 1.5 3.3 3.3
Applicable
Inverter Type
Terminal
Screw Size
햵
Tightening
Torque [Nm]
Crimping Terminal
L1, N U, V, W
FR-D720S-008
to 042
M3.5 1.2 2-3.5 2-3.5
FR-D720S-070 M4 1.5 2-4 2-4
FR-D720S-100 M4 1.5 5.5-4 2-4
Applicable
Inverter Type
Cable Sizes
HIV [mm
²
]
햲
AWG
햳
PVC [mm
²
]
햴
L1, N U, V, W
Earth
Cable
Gauge
L1, N U, V, W L1, N
U, V, W
Earth
Cable
Gauge
FR-D720S-008
to 042
22 214142.52.52.5
FR-D720S-070 2 2 2 14 14 2.5 2.5 2.5
FR-D720S-100 3.5 2 3.5 12 14 4 2.5 4
2
Applicable
Inverter Type
Terminal
Screw Size
햵
Tightening
Torque [Nm]
Crimping Terminal
R/L1, S/L2,
T/L3
U, V, W
FR-D740-012
to 080
M4 1.5 2-4 2-4
FR-D740-120 M4 1.5 2-4 2-4
FR-D740-160 M4 1.5 5.5-4 5.5-4
Applicable
Inverter Type
Cable Sizes
HIV [mm
²
]
햲
AWG
햳
PVC [mm
²
]
햴
R/L1,
S/L2,
T/L3
U, V, W
Earth
Cable
Gauge
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W
Earth
Cable
Gauge
FR-D740-012
to 080
22214142.52.52.5
FR-D740-120 3.5 2 3.5 12 14 4 2.5 4
FR-D740-160 3.5 3.5 3.5 12 12 4 4 4
NOTES
● Tighten the terminal screw to the specified torque. A screw that has been
tightened too loosely can cause a short circuit or malfunction. A screw that
has been tightened too tightly can cause a short circuit or malfunction due
to the unit breakage.
● Use crimping terminals with insulation sleeve to wire the power supply and
motor.
Mitsubishi Electric Europe B.V. /// FA - European Business Group ///
Germany /// Tel.: +49(0)2102-4860 /// Fax: +49(0)2102-486112 0///
www.mitsubishi-automation.com