3.1.3 Requirements of the measurement location
The measurement location must meet the environmental conditions
specified in section 9.1.
3.1.4 Drawing up the power rating
General information The System IQ S
ENSORNET supplies all components with low voltage
as well as digital communication via a shielded 2-wire line.
Because of this characteristic the energy consumption of all
components must be taken into account (power rating) when planning
an IQ S
ENSORNET system. The energy consumption determines
whether an additional power module is necessary.
Power rating - why? All components in the system require a specific level of electrical power
for operation. Thus, it is necessary to draw up a power rating after
selecting the desired components. At the same time a determination is
made of whether the entire power requirement of all components
(consumers) is covered by the existing power supply in the DIQ/S 182-
XT-4-PR. If this is not the case, the power available in the system must
be increased by an additional MIQ power supply module.
Power requirement of
IQ S
ENSORNET
components
Component Power requirement [W]
IQ sensors
SensoLyt
®
700 IQ (SW) 0.2
TriOxmatic
®
700 IQ (SW) 0.2
TriOxmatic
®
701 IQ 0.2
TriOxmatic
®
702 IQ 0.2
FDO
®
700 IQ (SW) 0.7
TetraCon
®
700 IQ (SW) 0.2
VisoTurb
®
700 IQ 1.5
ViSolid
®
700 IQ 1.5
AmmoLyt
® Plus
700 IQ 0.2
NitraLyt
® Plus
700 IQ 0.2
VARiON
® Plus
700 IQ 0.2
NitraVis
®
70x IQ (TS) 7.0
CarboVis
®
70x IQ (TS) 7.0
NiCaVis
®
70x IQ 7.0
MIQ modules