User manual
Technical data System 182-XT-4
9 - 4
ba76027e02 12/2014
Relay
(3 x)
Terminals
Cable glands
PROFIBUS connection 9-pin SUB-D socket on the top of the enclosure, compatible with
Phoenix connector (IP 67).
Output Galvanically separated
Max. switching voltage Front terminal strip: 240 VAC or 24 VDC
Rear terminal strip: 250 VAC or 24 VDC
Max. switching current Front terminal strip: 2 A (AC and DC)
Rear terminal strip: 5 A (AC and DC)
Fuse rating on the
operator side
Front terminal strip: max. 2 A
Rear terminal strip: Maximum 5 A
Relay functions Programmable as:
– Opener or closer
– Limit monitor
– Monitoring of the warning and error
signals of the DIQ/S 182-XT-4-PR
– Proportional frequency output
– Proportional pulse width output
Terminal type Screw-type terminal strip, accessible by
opening the lid
Terminal ranges Solid wires:
Flexible wires:
0.2 ... 4.0 mm
2
AWG 24 ... 12
0.2 ... 2.5 mm
2
Suitable for cable
diameter
4.5 ... 10 mm or 7 ... 13 mm