Manual

YSI 5X00
137
YSI 5X00
136
AquaManager and the System Menu
AquaManager users can congure most 5X00 system menus from a PC. Aer polling
the 5X00, use “Systems Management” from the node window to view and upload
5X00 conguration. System menus are congured at the Setup tab selections.
Notes:
- Always manually poll the 5X00 aer uploading conguration changes and
verify uploaded information is retained. When conguration changes are
uploaded using AquaManager at the same time conguration changes are
being made by a user in the menus on a 5X00 instrument, the AquaManager
uploads may not be saved depending on the timing of keystrokes at the 5X00.
- e Run Screen must be displayed during normal operation. If the 5X00
is not at the run screen during AquaManager uploading, pressing
at
the 5X00 will only save certain conguration changes.
-
See Chapter 5 AquaManager - page 175 and AquaManager online help for ad-
ditional information.
Sensor Setup
Menus → Sensor Setup → Aux 1-6
→ DO 1-4
Aux, DO, and temperature system set points, control (set point or PID/PWM),
alarm, and sensor system relays are congured in the Sensor Setup menus. Eight
onboard relays can be congured for control and alarm output devices. Enabled
relays energize when a control or alarm system is active. Alarm notications can be
sent via email or cell phone (SMS messaging) - page 91.
Notes:
- For normal operation, the 5X00 must be at the Run Screen. Alarm func-
tionality (email alarms, activation of assigned alarm relays, alarm icons,
and buzzer) is suspended when 5X00 is not at Run Screen.
- Sensor system must be enabled in order to display values at Run Screen.
Control and/or alarm relays will not energize regardless of value if the
sensor system is disabled.
- ere is a 30 second delay at power up before control, timer, and alarm systems
become active.
- ere is a 30 second sensor system hold o when sensor conguration is
changed. See 30 Second Sensor System Hold O - page 146.
- Calibrate sensor prior to use. See Calibration - page 83.
- Over” and “Under” readings are displayed when DO sensor is measuring
outside it’s operating range - see DO range specification - page 14 DO
control and alarm functions including relays are suspended when a sensor is
reading “Over” or “Under.
- Over” and “Under” are not displayed for aux temperature systems when tem-
perature values are outside the temperature operating range - see Temperature
Range Specication - page 15. Temperature system controls and alarms will not
operate correctly when values are outside the temperature operating range.
- DO “Over” and “Under” readings most likely indicate that the sensor needs
to be serviced or replaced, or a bad probe or cable connection exists.
Conguring the 5X00
Conguring the 5X00