User Manual

YSI 5200A
162
YSI 5200A
163
Conguring the 5200A
Notes:
Data logging must be enabled in the System Menu. - See Data Logging -
page 102 for additional information.
Svr Hold Menu
When servicing sensors or doing tank maintenance, it may be necessary to shut
o all systems (including relays) because sensor values will not be accurate. Press
at Run Screen to enter Service Hold menu. When in Service hold, all relays
are de-energized until the Service Hold time expires. e Service Hold time is user
selectable. Enable and congure service hold time at Menus System→Service
Hold. Aer service hold time expires or is cancelled, sensor and aux systems are
reset causing relays to energize/de-energize based on the system value/condition.
Timer systems are not reset. To reset timer systems, turn power o and then on
at the 5200A.
Press
to exit Service Hold. Go to Menus → System → Service Hold
to enable and congure service hold time - page 124.
e Run Screen displays a clock count down of the Service Hold remaining time.
Notes:
If a timer is active (relay energized) at service hold, the relay will not reen- -
ergize aer service hold expires regardless if timer time has not expired.
ere is only one “on” time for all timer systems.
Entering Downloader mode places 5200A into Service Hold. -
- AquaManager polling, autopoller (including mapping), and email alarm-
ing continue to function during a 5200A Service Hold. Stop or pause
the AquaManager Autopoller during a Service Hold to avoid seeing
erroneous data in AquaManager and to avoid receiving alarm emails
during sensor service.
5200A alarm emails are not sent during service hold. -
Conguring the 5200A