User Manual

YSI 5200A
156
YSI 5200A
157
Calibrate Feed Smart Timer
Install and wire feed timer device - 1. page 46.
Enable Feed Timer. 2.
Menus → Timers→Feed Smart Timer →Feed Timer →Enabled
Assign feed timer relay.3.
Menus → Timers→Feed Smart Timer →Relay
Calibrate feeder.4.
Menus → Timers→Feed Smart Timer →Calibrate
At numeric keypad, enter test run time the feeder relay will energize.5.
Press 6. for feed timer relay to energize for congured run test time.
Countdown of relay “on” time is displayed.
When run time expires, the relay de-energizes. Enter the amount of food 7.
dispensed at the Measured Weight screen.
Press
8. to save settings and return to Run Screen.
Notes:
Since feeders and food size vary, run several calibrations and enter the -
average weight at the last calibration. If feeder or feed type is changed,
recalibrate the feeder.
If no test/calibration has been performed or if the results have not been -
saved, the 5200A will be unable to perform any feeding(s) because there
Conguring the 5200A
will be no reference to determine the rate at which feeding(s) will oc-
cur.
- Stored calibration data is available from the AquaManager program.
If feed timer units change, the feeder must be recalibrated. -
If an incorrect value is entered and saved, another calibration must be -
performed.
Disable the feed timer system when performing the feed timer calibration, -
de-energizing any active feed timer relay.
Aer calibration is complete, press
- to Run Screen. e feed timer
system resets based on the new calibration conguration.
- Feed Timer calibration cannot be done using AquaManager.
AquaManager and the Timer Menu
Most Timer menus can be congured using AquaManager. Aer polling the 5200A
node, use “Systems Management” to view and upload 5200A congurations. Select
the Timers/Feeder tabs to view and change conguration.
Conguring the 5200A