User Manual
YSI 5200A
54
YSI 5200A
55
Note:
It is essential that wires be terminated cleanly. Nicks (stray wires, not -
cleanly terminated) can result in unreliable network communication.
CAUTION: Run high and low voltage wires/cables through separate bulk-
head and conduit.
Do not connect or disconnect IDC ribbon cable
when 5200A is powered. Serious damage can occur
.
Figure 3.25
Terminate wires as described using category 5 cable: (color scheme may 5.
be dierent than described below.)
Pair #1 wires: solid blue and white with blue stripe -
Pair #2 wires: solid orange and white with orange stripe -
1 wire green -
Secure unused wires to avoid potential for shorting -
Wire the master as follows:
Wire Color Terminal
solid orange T (-)
white with orange stripe T (+)
solid blue R (-)
white with blue stripe R (+)
green Communications Common (C)
Installation and Wiring
Wire all slaves as follows:
Wire Color Terminal
solid blue T (-)
white with blue stripe T (+)
solid orange R (-)
white with orange stripe R (+)
green Communications Common (C)
Figure 3.26 is a wiring diagram for the most common 5200A network congura-
tion where a master 5200A is the rst physical device in the network. Additional
network diagrams are provided aer step 8.
Figure 3.26
Wire all network terminal strips prior to network testing, but only con-6.
nect a network terminal strip to the rst and last devices on the network
(*see note below). Congure network menu and follow testing procedure
as described - see page 93. Slave devices are tested one by one as they are
added to the network. Network testing cannot be done if stubs exist (**
see note below).
Notes:
*If the master is not the rst physical device on the network, place network -
terminal strip on the master and on the rst and last physical devices on
the network. (In this case two slaves will need to be tested at the same
time.) - gure 3.27.
**A stub is created when the last wired network terminal strip is not con- -
nected to a network slave - gure 3.24.
Installation and Wiring