User Manual

YSI 5200A
50
YSI 5200A
51
󱂈
󱂈
󱂈
󱂈
󱂉
󱂊
󱂋
󱂌
󱂍
󱂎
󱂏
󱂐
󱂑
󱂒
󱂓
Do not connect or disconnect IDC ribbon cable
when 5200A is powered. Serious damage can occur
.
Figure 3.21
Complete other wiring to 5200A.5.
Close front panel - 6. page 40.
Test aux systems.7.
Test Auxiliary Input Devices
Apply power to 5200A. See Aux Setup - beginning on page 133 for conguration
information. Verify display, control, and/or alarm functionality based on user-
dened conguration.
Installation and Wiring
Wire Aux Digital Input
Install aux digital device according to manufacturer’s instructions.1.
Connect switch wires to Aux Input 1 or 2. Connect one wire at (G) at 2. K. Connect
second wire to (1) or (2) at K.
CAUTION: Do not input external voltage.
Figure 3.22
Wire Aux Analog Input
Install analog instrument according to manufacturer’s instructions.1.
Connect analog instrument wires to Aux Input 1 or 2. Connect negative wire to 2.
ground (G) at K. Connect positive wire to (1) or (2) at K.
Instrument with analog
voltage or 4-20 mA output
Auxiliary Input
Connector
+ -
CAUTION: Observe correct polarity on analog input.
Figure 3.23
Installation and Wiring