Specifications
567040-YIM-B-1210
54 Johnson Controls Unitary Products
NOTE:  To find the Btu input, multiply the number of cubic feet 
of gas consumed per hour by the Btu content of the gas 
in your particular locality (contact your gas company for 
this information as it varies widely from area to area).
EXAMPLE
By actual measurement, it takes 19 seconds for the hand on a 1 
cubic foot dial to make a revolution with a 192,000 Btuh furnace 
running. To determine rotations per minute, divide 60 by 19 = 
3.16. To calculate rotations per hour, multiply 3.16  60 = 189.6. 
Multiply 189.6  1 (0.5 if using a 1/2 cubic foot dial) = 189.6. 
Multiply 189.6  (the Btu rating of the gas). For this example, 
assume the gas has a Btu rating of 1050 Btu/ft.
3
. The result of 
199,000 Btuh is within 5% of the 192,000 Btuh rating of the 
furnace.
Manifold Gas Pressure Adjustment
This gas furnace has two heat stages. Therefore, the gas valve 
has two adjustment screws located under a plastic protective 
cover. The second stage (100% input) adjustment screw is 
adjacent to the “HI” marking on the valve and the first stage 
(60% input) adjustment screw is located adjacent to the “LO” 
marking on the valve (See Figure 34).
Manifold pressure adjustment procedure.
Adjust second stage (100% input) pressure first, then adjust 
first stage (60% input) pressure.
1. Turn off all power to the unit.
2. Using the outlet pressure port on the gas valve, connect a 
manometer to monitor the manifold pressure.
3. Remove plastic cap covering HI and LO pressure 
adjustment screws.
4. Turn on power to the unit.
5. Set thermostat to call for second stage heat and start 
furnace.
6. If necessary, using a screwdriver, turn the
second stage 
adjustment screw (adjacent to the “HI” marking on the 
valve) clockwise to increase manifold pressure or 
counterclockwise to decrease manifold pressure. Be sure 
not to over-fire the unit on second stage.
7. After the high manifold pressure has been checked, adjust 
the thermostat to call for first stage heat.
8. If necessary, using a screwdriver, turn the first stage 
adjustment screw (adjacent to the “LO” marking on the 
valve) clockwise to increase manifold pressure or 
counterclockwise to decrease manifold pressure. Be sure 
not to under-fire the unit on first stage.
9. Once pressure has been checked, replace the plastic cap 
covering the HI and LO pressure adjustment screws.
NOTE:  When using natural gas, the manifold pressure for 
second stage (100% input) should be 3.5 IWG ± 0.3. 
The manifold pressure for first stage (60% input) when 
using natural gas should be 1.5 IWG ± 0.3.
Adjustment Of Temperature Rise
The temperature rise (the difference of temperature between the 
return air and the heated air from the furnace) must lie within the 
range shown on the CSA rating plate and the data in Table 11.
After the temperature rise has been determined, the CFM can 
be calculated as follows:
After about 20 minutes of operation, determine the furnace 
temperature rise. Take readings of both the return air and the 
heated air in the ducts (about 6 feet from the furnace) where 
they will not be affected by radiant heat. Increase the blower 
CFM to decrease the temperature rise; decrease the blower 
CFM to increase the rise (See SUPPLY AIR DRIVE 
ADJUSTMENT).
NOTE:  Each gas heat exchanger size has a minimum 
allowable CFM. Below this CFM, the limit will open.
Table 28: Gas Rate Cubic Feet Per Hour
Seconds for
One Rev.
Size of Test Dial
1/2 cu. ft. 1 cu. ft.
10 180 360
12 150 300
14 129 257
16 113 225
18 100 200
20 90 180
22 82 164
24 75 150
26 69 138
28 64 129
30 60 120
32 56 113
34 53 106
36 50 100
38 47 95
40 45 90
42 43 86
44 41 82
46 39 78
48 37 75
50 36 72
52 35 69
54 34 67
56 32 64
58 31 62
60 30 60
Table 29: Gas Heat Stages
# of Burner Tubes
2nd Stage Input
(100% Btuh)
1st Stage Input
(60% Btuh)
4 120,000 72,000
6 180,000 108,000
8 240,000 144,000










