Specifications
567040-YIM-B-1210
Johnson Controls Unitary Products 47
Compressor Protection
In addition to the external pressure switches, the compressors 
also have inherent (internal) protection. If there is an abnormal 
temperature rise in a compressor, the protector will open to shut 
down the compressor. The UCB incorporates features to 
minimize compressor wear and damage. An Anti-Short Cycle 
Delay (ASCD) is utilized to prevent operation of a compressor 
too soon after its previous run. Additionally, a minimum run time 
is imposed any time a compressor is energized.
The ASCD is initiated on unit start-up and on any compressor 
reset or lock-out.
Flash Codes
The UCB will initiate a flash code associated with errors within 
the system. Refer to UNIT CONTROL BOARD FLASH CODES 
Table 30.
Reset
Remove the call for cooling, by raising thermostat setting higher 
than the conditioned space temperature. This resets any 
pressure or freezestat flash codes.
Reheat Mode Sequence Of Operation
The reheat control board allows the user to select two different 
modes of operation via a jumper connection on the board. (See 
Figure 31.) Each mode is described below.
“Normal” Mode
When the reheat control board (RCB) detects a need for 
dehumidification (24VAC) at "HUM" via the field supplied 
dehumidistat connected to RHTB-1 and RHTB-2 and there is 
not a call for cooling, it energizes the hot gas relay (HGR), 
which energizes the 3-way valve (SOL 3), the condenser coil 
valve (SOL 2), and de-energizes the reheat coil bleed valve 
(SOL 1). (In the ZR150, SOL 4 is only energized when the 
discharge pressure in circuit #1 rises above 400 psig and de-
energizes SOL 4 after the discharge pressure falls below 320 
psig. Both outdoor fans of circuit #1 in the ZR150 also 
disengage to conserve energy.) The Y1 signal is passed to the 
unit control board (UCB), which engages circuit # 1, resulting in 
circuit #1 reheat mode operation.
When the room thermostat calls for first stage cooling, with or 
without a call for dehumidification, the RCB senses a signal 
through "Y1", de-energizing the HGR, which de-energizes SOL 
3 and SOL 2 and energizes SOL 1, engaging circuit #1, 
resulting in circuit #1 cooling mode operation.
When the room thermostat calls for second stage cooling, the 
RCB senses a signal through "Y1" & "Y2" and engages circuit 
#1 and circuit #2 in cooling mode.
Indoor blower operation is initiated upon a call for first stage 
cooling, second stage cooling or dehumidification.
Anytime there is a call for 2 stages of cooling, the unit will not 
operate in the reheat mode, even if there is a call for 
dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call 
for heating.
On units with economizers, the unit will not operate in the 
reheat mode if there is a call for cooling and the economizer is 
operating as first stage of cooling.
All safety devices function as previously described.
"Alternate” Mode
When the RCB detects a need for dehumidification (24VAC) at 
"HUM" via the field supplied dehumidistat connected to RHTB-1 
and RHTB-2, and there is not a call for cooling, it energizes the 
HGR, which energizes the SOL 3, SOL 2, and de-energizes 
SOL 1. (In the ZR150, SOL 4 is only energized when the 
discharge pressure in circuit #1 rises above 400 psig and de-
energizes SOL 4 after the discharge pressure falls below 320 
psig. Both outdoor fans of circuit #1 in the ZR150 also 
disengage to conserve energy.) The unit then operates with 
circuit #1 in reheat mode and circuit #2 in cooling mode.
When the room thermostat calls for first stage cooling while 
there is still a call for dehumidification, no operational change is 
made. The call for cooling is ignored and the unit continues to 
operate with circuit #1 in reheat mode and circuit #2 in cooling 
mode.
When the room thermostat calls for second stage cooling, the 
RCB senses a signal through "Y1" and "Y2" and de-energizes 
the HGR, which de-energizes SOL 3 and SOL 2, and energizes 
SOL 1. Both circuits operate in the cooling mode.
Indoor blower operation is initiated upon a call for first stage 
cooling, second stage cooling or dehumidification.
Anytime there is a call for 2 stages of cooling, the unit will not 
operate in the reheat mode, even if there is still a call for 
dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call 
for heating.
All safety devices function as previously described.