Specifications
567040-YIM-B-1210
Johnson Controls Unitary Products 43
Supply Air Drive Adjustment
At unit start-up, the measured CFM may be higher or lower than 
the required CFM. To achieve the required CFM, the speed of 
the drive may have adjusted by changing the datum diameter 
(DD) of the variable pitch motor sheave as described below:
Use the following tables and the DD calculated per the above 
equation to adjust the motor variable pitch sheave.
EXAMPLE
A 12.5 ton unit was selected to deliver 4,000 CFM with a 3 HP 
motor, but the unit is delivering 3,800 CFM. The variable pitch 
motor sheave is set at 2 turns open.
Use the equation to determine the required DD for the new 
motor sheave,
Use Table 21 to locate the DD nearest to 4.21 in. Close the 
sheave to 1 turn open.
New BHP
= (Speed increase)
3
 • BHP at 3,800 CFM
= (Speed increase)
3
 • Original BHP
= New BHP
New motor Amps
= (Speed increase)
3
 • Amps at 3,800 CFM
= (Speed increase)
3
 • Original Amps
= New Amps
Before making any blower speed changes review the 
installation for any installation errors, leaks or undesirable 
systems effects that can result in loss of airflow.
Even small changes in blower speed can result in 
substantial changes in static pressure and BHP. BHP 
and AMP draw of the blower motor will increase by the 
cube of the blower speed. Static pressure will increase 
by the square of the blower speed. Only qualified 
personnel should make blower speed changes, strictly 
adhering to the fan laws.
Belt drive blower systems MUST be adjusted to the 
specific static and CFM requirements for the application. 
The Belt drive blowers are NOT set at the factory for any 
specific static or CFM. Adjustments of the blower speed 
and belt tension are REQUIRED
. Tighten blower pulley 
and motor sheave set screws after these adjustments. 
Re-checking set screws after 10-12 hrs. run time is 
recommended.
Table 21: Motor Sheave Datum Diameters
1VM50x7/8
(1-1/2, 2 & 3 HP Motor)
1VP56x1-1/8
(5 HP Motor)
Turns Open Datum Diameter Turns Open Datum Diameter
04.415.3
1/2 4.3 1-1/2 5.2
14.225.1
1-1/2 4.1 2-1/2 5.0
24.034.9
2-1/2 3.9 3-1/2 4.8
33.844.7
3-1/2 3.7 4-1/2 4.6
43.654.5
4-1/2 3.5 5-1/2 4.4
53.464.3