Specifications
567040-YIM-B-1210
Johnson Controls Unitary Products 15
designed for HCFC and CFC refrigerants. Take all necessary 
precautions to avoid exposure of the oil to the atmosphere.
POE (polyolester) compressor lubricants are known to cause 
long term damage to some synthetic roofing materials.
Procedures which risk oil leakage include, but are not limited to, 
compressor replacement, repairing refrigerant leaks, replacing 
refrigerant components such as filter drier, pressure switch, 
metering device or coil.
Units are shipped with compressor mountings which are 
factory-adjusted and ready for operation.
Filters
Two-inch filters are supplied with each unit. One-inch filters may 
be used with no modification to the filter racks. Filters must 
always be installed ahead of evaporator coil and must be kept 
clean or replaced with same size and type. Dirty filters reduce 
the capacity of the unit and result in frosted coils or safety 
shutdown. Refer to physical data tables, for the number and 
size of filters needed for the unit. The unit should not be 
operated without filters properly installed.
Power And Control Wiring
Field wiring to the unit, fuses, and disconnects must conform to 
provisions of National Electrical Code (NEC), ANSI/NFPA No. 
70 – Latest Edition (in U.S.A.), current Canadian Electrical 
Code C221, and/or local ordinances. The unit must be 
electrically grounded in accordance with NEC and CEC as 
specified above and/or local codes.
Voltage tolerances which must be maintained at the 
compressor terminals during starting and running conditions are 
indicated on the unit Rating Plate and Table 1.
The internal wiring harnesses furnished with this unit are an 
integral part of the design certified unit. Field alteration to 
comply with electrical codes should not be required. If any of 
the wire supplied with the unit must be replaced, replacement 
wire must be of the type shown on the wiring diagram and the 
same minimum gauge as the replaced wire.
A disconnect must be utilized for these units. Factory installed 
disconnects are available. If installing a disconnect (field 
supplied or York International
®
 supplied accessory), refer to 
Figure 4 for the recommended mounting location.
NOTE:  Since not all local codes allow the mounting of a 
disconnect on the unit, please confirm compliance with 
local code before mounting a disconnect on the unit.
Electrical line must be sized properly to carry the load. USE 
COPPER CONDUCTORS ONLY. Each unit must be wired with 
a separate branch circuit fed directly from the meter panel and 
properly fused.
Refer to Figures 21, 22 and 23 for typical field wiring and to the 
appropriate unit wiring diagram mounted inside control doors 
for control circuit and power wiring information.
Do not leave the system open to the atmosphere. Unit 
damage could occur due to moisture being absorbed by 
the POE oil in the system. This type of oil is highly 
susceptible to moisture absorption
Exposure, even if immediately cleaned up, may cause 
embrittlement (leading to cracking) to occur in one year 
or more. When performing any service that may risk 
exposure of compressor oil to the roof, take precautions 
to protect roofing.
Do not loosen compressor mounting bolts.
Make sure that panel latches are properly positioned on 
the unit to maintain an airtight seal.
208/230-3-60 and 380/415-3-50 units control 
transformers are factory wired for 230v and 415v power 
supply respectively. Change tap on transformer for 208-
3-60 or 380-3-50 operation. See unit wiring diagram.
Avoid damage to internal components if drilling holes for 
disconnect mounting.
When connecting electrical power and control wiring to 
the unit, water-proof connectors must be used so that 
water or moisture cannot be drawn into the unit during 
normal operation. The above water-proofing conditions 
will also apply when installing a field supplied disconnect 
switch.