TABLE 2 - OPERATING ANALYSIS CHART
RESULTS POSSIBLE CAUSE REMEDY
1. SYMPTOM: ABNORMALLY HIGH DISCHARGE PRESSURE
Temperature difference between liquid Air in condenser. Purge unit operates automatically to take
refrigerant out and water off condenser care of this condition. Test for air leaks if
higher than normal. display
reads:
High discharge pressure. Condenser tubes dirty or scaled. Clean condenser tubes.
Check water conditioning.
High condenser water temperature. Reduce condenser water inlet temperature.
(Check cooling tower and water circulation.)
Temperature difference between condenser Insufficient condensing water flow. Increase the quantity of water through the
water on and water off higher than normal, condenser to proper value.
with normal cooler pressure.
2. SYMPTOM: ABNOrMALLY LOW SUCTION PRESSURE
Temperature difference between leaving Insufficient charge of refrigerant. Check for leaks and charge refrigerant into
chilled water and refrigerant in cooler system.
greater than normal with high discharge
temperature. Flow orifice blocked. Remove obstruction.
Temperature difference between leaving Cooler tubes dirty or restricted. Clean cooler tubes.
chilled water and refrigerant in the cooler
greater than normal with normal discharge
temperature.
Temperature of chilled water too low with Insufficient load for system capacity. Check prerotation vane motor operation
low motor amperes. and setting of low water temperature cutout.
3. SYMPTOM: HIGH COOLER PRESSURE
High chilled water temperature. Prerotation vanes fail to open. Check the prerotation vane motor
positioning circuit.
System overloaded. Be sure the vanes are wide open
(without overloading the motor) until the
load decreases.
4. SYMPTOM: NO OIL PRESSURE WHEN SYSTEM START BUTTON PUSHED
Low oil pressure displayed on control Oil pump running in wrong direction. Check rotation of oil pump.
center; compressor will not start. (Electrical Connections)
Oil pump not running. Check electrical connecrtions to oil pump
and press manual reset on oil pump starter
(on condenser shell in front of purge unit).
5. SYMPTOM: COMPRESSOR STARTS, NORMAL OIL PRESSURE DEVELOPS, FLUCTUATES FOR SHORT WHILE, THEN
COMPRESSOR STOPS ON OIL PRESSURE CUTOUT
Oil pressure normal, fluctuates, then com- Unusual starting conditions exist, i.e., oil Drain the oil from the compressor and
pressor stops on Oil Pressure Cutout. foaming in reservoir and piping due to charge new oil into the compressor. (See
Display reading: lowered system pressure. “Oil Charging Procedure”, page 44.)
Burned out oil heater. Replace oil heater.
LOW OIL PRESSURE
WARNING – EXCESS PURGE