ON RISE ON FALL
MON. 10:00 AM Low Water Autostart Low Water (LWT) Chilled water 4°F below chilled
Temperature setpoint water setpoint
MON. 10:00 AM Low Water Autostart Low Water (LWT) Chilled water 4°F below chilled
Temperature VSD setpoint water setpoint
MON. 10:00 AM Flow Switch Autostart Flow Switch
MON. 10:00 AM System Cycling Autostart A remote command
(computer relay contact or
manual switch)
MON. 10:00 AM Multi-Unit Cycling Autostart (Optional)
Lead-Lag Sequence Control
MON. 10:00 AM Internal Clock Autostart Internal Clock
MON. 10:00 AM AC Undervoltage Autostart <15% FLA for 25
continuous seconds
MON. 10:00 AM Power Fault Autostart CM-2 Current Module or
Solid State Starter
Remote Stop Energy Management System
MON. Anti-Recycle, Anti-Recycle
20 Min. Left Timer
MON. 10:00 AM Low Evap. Pressure Low Evap. Pressure 5.43 PSIA 5.42 PSIA
Transducer (LEP)
MON. 10:00 AM Low Evap. Pressure LEP external control Set to Job Spec. Set to Job Spec.
Brine (Brine units only)
MON. 10:00 AM Low Oil Low Oil Press. Transducer (OP) 20 PSID 15 PSID
Pressure High Oil Press. Transducer (OP)
MON. 10:00 AM High Pressure High Pressure 15 PSIG 9 PSIG
Safety Control (HP)
MON. 10:00 AM Evap. Transducer Evap. Pressure Transducer
or Probe Error or Leaving Chilled Water
Thermistor (RS1)
MON. 10:00 AM Motor Controller - CM-2 or Solid State Starter or
Ext. Reset Variable Speed Drive
MON. 10:00 AM High Discharge Discharge Temperature 220°F 219°F
Temperature Thermistor (RT2)
MON. 10:00 AM High Oil Oil Temperature 180°F 179°F
Temperature Thermistor (RT3)
MON. 10:00 AM Power Autostart Micro Board undervoltage 8.29 VDC 7.84 VDC
Failure circuit on 5V unregulated
supply
MON. 10:00 AM Power Micro Board undervoltage 8.29 VDC 7.84 VDC
Failure circuit on 5V unregulated
supply
SHUTDOWN CAUSE