Specifications

22 YORK INTERNATIONAL
SYSTEM RUN – LOW PRESSURE LIMIT IN EFFECT
Displayed when the chiller is running and the evapora-
tor pressure falls to 5.55 PSIA (R11); 4.50 PSIA (R123).
Simultaneously, the prerotation vanes will be prevented
from further opening. This action maintains chiller opera-
tion to prevent low-evaporator-pressure shutdown at 5.42
PSIA (R11); 4.40 PSIA (R123). When the evaporator
pressure rises to 5.65 PSIA (R11); 4.70 PSIA (R123),
the vanes will be permitted to open. Low pressure limit
feature is not used when program jumper (JP-3) is cut
(Brine application).
SYSTEM RUN – HIGH PRESSURE LIMIT IN EFFECT
Displayed when the chiller is running and the condenser
pressure rises to 28.8 PSIA. Simultaneously, the prero-
tation vanes will be inhibited from further opening. This
action occurs to prevent system shutdown on high con-
denser pressure at 29.7 PSIA. When the condenser
pressure falls to 28.6 PSIA, the vanes will be permitted
to open.
SYSTEM RUN – PRESS STATUS
Displayed when the chiller is running. It instructs the
operator to press the STATUS key, whereupon the fol-
lowing message will be displayed. The following “Warn-
ing Messages” are displayed alternately with the fore-
ground message. The foreground message is displayed
for 2 seconds, then the warning message is displayed
for 2 seconds, etc. It is not necessary to press the STA-
TUS” key.
WARNING: COND OR EVAP TRANSDUCER ERROR
Indicates a probable condenser or evaporator transducer
problem, because the output is unreasonable. The mi-
croprocessor arrives at this conclulsion by subtracting
the evaporator transducer output from the condenser
transducer output. The result must be zero or some posi-
tive number. If the result is a negative number, it con-
cludes that there is a probable condenser or evaporator
transducer problem. This function is inhibited for the first
10 minutes of chiller run-time, and is checked every 10
minutes thereafter. Message is reset by pressing the
WARNING RESET key in the SERVICE mode.
WARNING: PURGE FLOAT SWITCH ERROR
Indicates the microprocessor is receiving conflicting digi-
tal signals from purge top float switch and purge bottom
float switch (i.e., liquid is simultaneously above TFS and
below BFS . . . an impossible condition). Message is
reset by pressing WARNING RESET key in the Ser-
vice mode.
Therefore:
(100%) (50% x 200) = 100A = Vanes stop opening
(104%) (50% x 200) = 104A = Vanes driven toward
close position
SYSTEM RUN – AUTO VANES
Displayed when the chiller is running, the MicroComputer
Control Center is in SERVICEmode, and the vanes
are operating in AUTO” mode.
SYSTEM RUN VANES OPENING
Displayed when the chiller is running and the Micro-
Computer Control Center is in SERVICE mode with:
The vanes operating in AUTO mode and opening to
maintain the leaving chilled water temperature
setpoint.
-or-
The operator has pressed the vanes OPEN key on
the keypad.
SYSTEM RUN VANES CLOSING
Displayed when the chiller is running and the Micro-
Computer Control Center is in SERVICE mode with:
The vanes operating in “AUTO mode and closing to
maintain the leaving chilled water temperature
setpoint.
-or-
The operator has pressed the vanes “CLOSE key on
the keypad.
SYSTEM RUN VANES HOLDING
Displayed when the chiller is running, the Micro-
Computer Control Center is in SERVICE” mode, and
the operator has pressed the vanes “HOLD” key.
SYS READY TO START – VANES OPENING
Displayed when the chiller is not running and the opera-
tor has pressed the vanes OPEN key on the keypad.
SYS READY TO START – VANES CLOSING
Displayed when the chiller is not running and the opera-
tor has pressed the vanes CLOSE key on the keypad.
SYS READY TO START – VANES HOLDING
Displayed when the chiller is not running and the opera-
tor has pressed the vanes HOLD key on the keypad.