Specifications

20 YORK INTERNATIONAL
and it says that there have been 7 purges in the
“Last Hour”, that means that there have been 7
exhausts since 8:11 AM. If you do this at 2:57
PM, it means that there have been 7 exhausts
since 1:57 PM, etc.
The purge count is reset to zero by:
A. Clearing the excess purge message.
B. Moving the Micro Board program jumper
J-57 (CLK ON/OFF) from “CLK OFF” to
CLOCK ON” position.
C. Starting the chiller.
The purge count is frozen by the following:
A. When the chiller is not running.
B. An excess purge message is being dis-
played and at least 1 full hour of purge
exhausts have accumulated.
HISTORY PRINT - This key is used to initiate a history
print to the optional printer. Refer to Form 160.48-NO1.2
for operation of this key.
OPERATING MODES
The MicroComputer Control Center can be operated in
four different operating modes as follows:
SERVICE - Enables all the Service keys except “DIS-
PLAY DATA”, “MANUAL OIL PUMP”, and HISTORY
PRINT”, which are enabled in all modes. See “Service
Keys”, page 18.
LOCAL - This is the normal operating mode. The com-
pressor can be started and stopped from the Control
Center. Also, the Display and Setpoints parameters can
be displayed.
PROGRAM - Allows the operator to program the
Setpoints parameters, and change operating modes.
REMOTE - In this mode, the Control Center will accept
control signals form a remote device (i.e., Energy Man-
agement System) or cycling inputs. The control signal
inputs are:
1. Remote Start
2. Remote Stop
3. Remote LCWT Setpoint
4. Remote Current Limit Setpoint
NOTE: The compressor can be stopped by the “COM-
PRESSOR switch, regardless of the operating
mode. The switch must be in “RUN position to
enable “REMOTE” mode. The operator cannot
locally start the compressor using the COM-
PRESSORswitch when in the REMOTE
mode.
To determine which operating mode the Control Center
is presently in, simply press the MODE” key.
If the Control Center is in “LOCAL” mode, this is
displayed:
LOCAL OPERATING MODE IN EFFECT
If the Control Center is in REMOTE” mode, this is
displayed:
REMOTE OPERATING MODE IN EFFECT
If the Control Center is in SERVICE mode, this is
displayed:
SERVICE OPERATING MODE IN EFFECT
To change operating mode, proceed as follows:
1. Press “ACCESS CODE” key.
2. This message appears:
ENTER VALID ACCESS CODE __ __ __ __
3. Using “Entry keys, enter 9 6 7 5.
4. As each digit is entered, the characters Y O R K are
displayed.
NOTE: If digits other than 9 6 7 5 are entered,
Y O R K is still displayed.
5. Press “ENTER” key.
NOTE: If digits other than 9 6 7 5 were entered in step
No. 4,
INVALID ACCESS CODE
is displayed when the ENTER key is pressed.
If this occurs, enter the correct access code
(9 6 7 5) and proceed.
6. This message is displayed:
ACCESS TO PROGRAM KEY AUTHORIZED
NOTE: Unless terminated by pressing the ACCESS
CODE key again, the operator will have ac-
cess to the PROGRAM” key for 10 minutes.