Specifications
YORK INTERNATIONAL 17
FORM 160.48-O1
To Enter REMOTE/RESET TEMP RANGE Setpoint:
FIG. 13 - KEYPAD - PROGRAMMING “REMOTE
RESET TEMP RANGE” SETPOINT
FIG. 14 - KEYPAD - PROGRAMMING “EXCESS
PURGE THRESHOLD” SETPOINT
(Refer to Fig. 13)
1. Press and release “REMOTE/RESET TEMP
RANGE” setpoint key. The following program prompt
message is displayed:
REMOTE/RESET TEMP RANGE = XX °F
2. Use “Entry” keys to enter desired value (10 or 20).
3. Press and release “ENTER” key. The following mes-
sage is displayed.
PROGRAM MODE, SELECT SETPOINT
To Enter DATA LOGGER Setpoint:
Refer to Form 160.48-NO1.2 for operation of this key.
To Enter EXCESS PURGE THRESHOLD Setpoint:
(Refer to Fig. 14)
1. Press and release “DISPLAY DATA” key. The fol-
lowing program prompt message is displayed:
MAXIMUM PURGES PER HOUR = XX
2. Use “ENTRY” keys to enter desired values.
3. Press and release “ENTER” key. The following mes-
sage is displayed:
PROGRAM MODE, SELECT SETPOINT