Specifications

14 YORK INTERNATIONAL
To enter CHILLED LIQUID TEMP Setpoint:
(Refer to Fig. 7)
1. Press and release CHILLED LIQUID TEMP setpoint
key. The following program prompt message will be
displayed:
LEAVING SETPOINT = XX.X °F (BASE)
(BASE) refers to the base or lowest setpoint avail-
able to an Energy Management System. If any En-
ergy Management System is applied, this value must
be entered into the Energy Management System.
Refer to previous explanation or REMOTE/RESET
TEMP RANGE, page 10.
2. Use “ENTRY keys to enter desired value.
3. Press and release ENTER key. This message is
displayed:
PROGRAM MODE, SELECT SETPOINT
To Enter % CURRENT LIMIT Setpoint:
(Electro-Mechanical Starter or VSD)
FIG. 7 - KEYPAD - PROGRAMMING “LEAVING
CHILLED WATER TEMP” SETPOINT
FIG. 8 - KEYPAD - PROGRAMMING “% CURRENT
LIMIT” SETPOINT
(Refer to Fig. 8)
1. Press and release % CURRENT LIMIT setpoint key.
The following program prompt message is displayed:
CURRENT LIMIT = XXX % FLA
2. Use “ENTRY keys to enter desired value.
3. Press and release ENTER key. This message is
displayed:
PROGRAM MODE, SELECT SETPOINT
(Solid State Starter)
(Refer to Fig. 8)
1. Press and release % CURRENT LIMIT setpoint key.
The following message is displayed:
CURRENT LIMIT = XXX % FLA MTR CUR = _ _ _ FLA
2. Use “ENTRY keys to enter desired current limit value.
NOTE: Motor Current FLA value is entered by YORK
factory and checked at system start-up. It can-
not be changed without special access code.
(Note to service technician: refer to Program-
ming Instructions in Service Instruction Form
160.48-M2.)
3. Press and release ENTER” key. The following mes-
sage is displayed:
PROGRAM MODE, SELECT SETPOINT
LD0457
LD0457