Specifications

54 YORK INTERNATIONAL
VIBRATION ANALYSIS
Vibration analysis performed at yearly intervals is a useful
diagnostic that can detect internal damage to rotating
machinery and component parts. This service should be
performed by a skilled technician trained in the use and
operation of the equipment. Fig. 32 is provided to prop-
erly locate the transducer measurement points. Locat-
SPECTRAL ALARM BANDS FOR 4/6 LOBE TWIN SCREW CHILLERS
MALE
INLET
MALE
OUTLET
FEMALE
INLET
FEMALE
OUTLET
COMPRESSOR
(BOTTOM)
MOTOR
MOTOR
DRIVE
END
MOTOR
OUTBOARD
END
HORIZONTAL
VERTICAL
AXIS
LD04382
LD04381
FIG. 32 TRANSDUCER MEASUREMENT POINTS
ing the transducers at these locations will enable the
data to be analyzed against a large database of sound
and vibration data.
Note the natural or pumping frequency of the YORK
YS compressor is 238 HZ (14,280 CPM) at 60 HZ and
198 HZ (11,880 CPM) at 50 HZ operation.
Maintenance