Specifications

53
FORM 160.80-NOM1
YORK INTERNATIONAL
LD00476
FIG. 31 MOTOR STATOR TEMPERATURE AND INSULATION RESISTANCES
4
Minimum Insulation Resistance vs. Temperature (per IEEE Std 43)
YT CodePak Open Motors
1. Megohm readings should be taken after Megohm voltage has been applied one minute.
2. If insulation resistance lies to the right of the applicable curve, the motor is acceptable for use.
3. If insulation resistance lies to the left of the applicable curve, the motor should not be run. The motor
should be heated to 250ºF in an effort to remove moisture and obtain an acceptable reading at
room ambient. This can be done either by baking in a forced hot air oven or, if proper voltage is
available, apply 5 - 10% of rated voltage to motor windings.
4. Any gradual or abrupt decrease in Megohm readings over an extended period of time is an
indication of deterioration of insulation and/or moisture absorption or oil/dirt contamination.
5. Megohm readings of individual phase coils of 200 - 600V motors should be made with coils not
under test being grounded.