If pumps discharge through the unit, the strainer may be
located upstream from the pumps to protect both pump
and unit. (Piping between the strainer, pump and unit
must be very carefully cleaned before start-up.) If
pumps are remotely installed from the unit, strainers
should be located directly upstream.
Condenser Water Circuit
For proper operation of the unit, condenser refrigerant
pressure must be maintained above cooler pressure. If
operating conditions will fulfill this requirement, no at-
tempt should be made to control condenser water tem-
perature by means of automatic valves, cycling of the
cooling tower fan or other means. Refer to Fig. 9 for a
typical water piping schematic. YS units are designed
to function satisfactorily and efficiently, when condenser
water is allowed to seek its own temperature level at
reduced loads and off-peak seasons of the year. How-
ever, if entering condenser water temperature can go
below the required minimum, condenser water tempera-
ture must be maintained equal to or slightly higher than
the required minimum. Refer to page 37, Condensing
Water Temperature, and the formula to calculate the
minimum Entering Condensing Water Temperature.
FIG. 10 TYPICAL REFRIGERANT VENT PIPING FROM RELIEF VALVES
LD04896
Stop Valves
Stop valves may be provided (by others) in the cooler
and condenser water piping, adjacent to the unit to ease
maintenance. Pressure taps should be provided (by oth-
ers) in the piping as close to the unit as possible, to aid in
obtaining operating checks.
Flow Switches (Field Installed)
A flow switch or pressure differential control in the
chilled water line(s), adjacent to the unit, is an acces-
sory which can be provided by YORK for connection
to the control center. If a flow switch is used, it must
be directly in series with the unit and sensing only wa-
ter flow through the unit. The differential switch must
sense pressure drop across the unit.
Drain and Vent Valves
Drain and vent valves (by others) should be installed in
the connections provided in the cooler and condenser
liquid heads. These connections may be piped to drain if
desired.