Specifications

45JOHNSON CONTROLS
FORM 160.80-EG1 (511)
1-PASS & 3-PASS COOLERS
2-PASS COOLERS
* Applies to compressor end if connections are on motor end.
** Applies to motor end if connections are on motor end.
MOTOR END
COMPR. END
COMPR. ENDMOTOR END
COOLER NOZZLE ARRANGEMENTS – MARINE WATER BOXES
R-134a UNITS
EVAP. NOZZLE SIZES
EVAPO-
RATOR
Code
Nozzle Size (In.)
No. of Passes
1 2 3
B 8 6 4
C 10 6 6
D 12 8 6
E 12 8 6
F 12 10 8
WEIGHTS (To be added to Metric Unit Weights on pages 48-49)
Cooler
Code
Shipping Weight
Increase – Kg
Operating Weight
Increase – Kg
1-Pass 2-Pass 3-Pass 1-Pass 2-Pass 3-Pass
B 252 134 255 358 178 343
C 368 190 304 549 269 434
D 396 200 349 598 273 495
E 473 276 453 761 420 698
F 582 398 514 864 466 764