Specifications

41JOHNSON CONTROLS
FORM 160.80-EG1 (511)
Refer to Tables 6 and 7 on pages 26 & 27 for valid compressor/shell/motor combinations.
S4 - S5 COMPRESSOR
R-134a UNITS
(50 and 60 Hz)
1. All dimensions are approximate. Certied dimensions are available on request.
2. Determine overall unit length by adding water box depth from table below to tube sheet length:
3. Unit height includes steel mounting plates under tube sheets. To determine overall installed height,
add 22mm for neoprene isolators (25.4 for optional spring isolators).
NOTES:
DIMENSIONS (mm)
S4 COMPRESSOR S4 and S5 COMPRESSOR
SHELL CODES (Evaporator – Condenser)
D-C D-D E-E E-F F-E F-F
A – TUBE SHEET WIDTH 1,880 1,880 1,880 1,943 1,994 2,057
A
1
– WITH SOLID STATE STARTER 2,080 2,080 2,080 2,143 2,226 2,200
A
2
– OVERALL WIDTH (Less S.S.S) 1,915 1,915
B – OVERALL HEIGHT3 2,365 2,365 2,365 2,496 2,496 2,496
C – EVAPORATOR C/L 502 502 502 502 559 559
D – CONDENSER C/L 438 438 438 470 438 470
REFRIGERANT RELIEF VALVE CONNECTIONS
VESSEL SIZE
EVAPORATOR 1” FPT SINGLE
CONDENSER 1” FPT DUAL
TYPE COMPACT WATER BOX
COOLER CODE CONDENSER CODE
D E F D E F
RETURN BOX 140 140 197 133 133 194
WITH VICTAULIC CONNECTION 352 352 384 352 352 384
WITH FLANGED CONNECTION 365 365 397 365 365 397