Specifications

40 JOHNSON CONTROLS
FORM 160.80-EG1 (511)
S0 - S3 COMPRESSOR
R-134a UNITS
(50 and 60 Hz)
NOTES:
1. All dimensions are approximate. Certied dimensions are available on request.
2. Determine overall unit length by adding water box dimension to tube sheet length:
132mm for compact return box
356mm for compact water box with ANSI/AWWA C-606 couplings water nozzles
Add 12.6mm to each compact water box with optional anged water nozzles
3. Unit height includes steel mounting plates under tube sheets. To determine overall installed height, add 22mm for neoprene isolators (25 mm
for optional spring isolators).
Dimensions - Metric
Refer to Tables 6 and 7 on pages 26 & 27 for valid compressor/shell/motor combinations.
DIMENSIONS (mm)
S0 and S1 COMPRESSOR S2 COMPRESSOR S2 and S3 COMPRESSOR
SHELL CODES (Cooler – Condenser)
B-B B-C C-B C-C B-B B-C C-B C-C C-D D-C D-D
A – TUBE SHEET WIDTH 1292 1292 1292 1292 1588 1588 1588 1588 1588 1588 1588
A
1
– OVERALL WIDTH 1349 1349 1349 1349 1591 1591 1591 1591 1591 1591 1591
B – OVERALL HEIGHT
3
1816 1895 1857 1899 1848 1946 1946 1946 2054 2102 2102
C – COOLER C/L 351 351 351 351 432 432 432 432 432 432 432
D – CONDENSER C/L 295 291 295 295 362 362 362 362 362 362 362
REFRIGERANT RELIEF VALVE CONNECTIONS
SHELL CODE EVAP. SIZE CONDENSER SIZE
B, C 3/4” FPT SINGLE 3/4” FPT DUAL
D 1” FPT SINGLE 3/4” FPT DUAL