Specifications

11JOHNSON CONTROLS
FORM 160.80-EG1 (511)
the Slot Numbers button or the Master Slot Numbers
List found in the Operating Manual. The interval at which
all the parameters are sampled is selected under the
Collection Interval button. The data point minimum and
maximum values may be adjusted closer to increase
viewing resolution.
Programmable:
Chart Type (select continuous or one screen)
Collection Interval
Select
Data Point Slot Number (1 - 6)
Data Point Min (1 - 6)
Data Point Max (1 - 6)
The TREND COMMON SLOTS screen displays the
Master Slot Numbers List of the monitored parameters.
Display Only:
Slot Numbers
Programmable:
Page Up
Page Down
Print
DISPLAY MESSAGES
The Control Center continuously monitors the operating
system, displaying and recording the cause of any shut-
downs (Safety, Cycling or Normal). The condition of the
chiller is displayed at the System Status line that contains
a message describing the operating state of the chiller;
whether it is stopped, running, starting or shutting down.
A System Details Line displays Warning, Cycling, Safety,
Start Inhibit and other messages that provide further
details of the Status Bar messages. Messages are color-
coded: Green Normal Operations; Yellow Warnings;
Orange Cycling Shutdowns; and Red Safety Shut-
downs to aid in identifying problems quickly.
Status messages include:
System Ready To Start
Cycling Shutdown – Auto Restart
Safety Shutdown – Manual Restart
Start Sequence Initiated
System Run (with countdown timers)
Start Inhibit
Slide Valve Closing Before Shutdown
System Lockout Delay
Run Messages include:
Leaving Chilled Liquid Control
Motor Pulldown Limit
Motor – High Current Limit
Start Inhibit Messages include:
Anti-Recycle XX min/sec.
Slide Valve – Position >30%
Motor Current >15% FLA
LCSSS – High-Temperature Phase X - Stopped
Warning Messages include:
Real Time Clock Failure
Setpoint Override
Condenser – High Pressure Limit
Evaporator – Low Pressure Limit
Freeze Threat From Operating Chiller
Freeze Threat, Condenser Flow Switch Open
Low Discharge Superheat Limit
Low Discharge Superheat Detected
Maximum Load – Load Limit
Minimum Load – Load Limit
Oil – Dirty Filter
Oil – High Temperature
Slide Valve Uncalibrated
Routine Shutdown Messages Include:
Remote Stop
Local Stop
Place Compressor Switch In Run Position
Cycling Shutdown Messages Include:
Multiunit Cycling – Contacts Open
System Cycling – Contacts Open
Control Panel – Power Failure
Leaving Chilled Liquid – Low Temperature
Leaving Chilled Liquid – Flow Switch Open
Condenser – Flow Switch Open
Motor Controller – Contacts Open
Motor Controller – Loss of Current
Power Fault
Control Panel – Schedule