Air Flow Data
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM
040A10 060B12 080B12 Jumper Settings
High Low High Low High Low COOL Tap ADJ Tap
1073 704 1320 858 1320 858 A B
957 622 1100 715 1100 715 B B
975 640 1200 780 1200 780 A A
870 565 1000 650 1000 650 B A
878 576 1080 702 1080 702 A C
770 501 880 572 880 572 C B
783 509 900 585 900 585 B C
649 440 660 440 660 440 D B
700 455 800 520 800 520 C A
590 400 600 400 600 400 D A
630 410 720 468 720 468 C C
531 400 540 400 540 400 D C
080C16 100C16 100C20 Jumper Settings
High Low High Low High Low COOL Tap ADJ Tap
1760 1144 1760 1144 2200 1430 A B
1540 1001 1540 1001 1760 1144 B B
1600 1040 1600 1040 2000 1300 A A
1400 910 1400 910 1600 1040 B A
1440 936 1440 936 1800 1170 A C
1320 858 1320 858 1540 1001 C B
1260 819 1260 819 1440 936 B C
1100 715 1100 715 1320 858 D B
1200 780 1200 780 1400 910 C A
1000 650 1000 650 1200 780 D A
1080 702 1080 702 1260 819 C C
900 585 900 585 1080 702 D C
120D20 Jumper Settings
High Low COOL Tap ADJ Tap
2200 1430 A B
1760 1144 B B
2000 1300 A A
1600 1040 B A
1800 1170 A C
1540 1001 C B
1440 936 B C
1320 858 D B
1400 910 C A
1200 780 D A
1260 819 C C
1080 702 D C
HIGH/LOW HEAT CFM
040A10 060B12 080B12 Jumper Settings
High Low High Low High Low HEAT Tap ADJ Tap
890 770 1200 870 1366 1156 A Any
790 660 1070 770 1293 1022 B Any
711 578 970 693 1185 924 C Any
646 514 890 630 1094 840 D Any
080C16 100C16 100C20 Jumper Settings
High Low High Low High Low HEAT Tap ADJ Tap
1580 1156 1975 1444 1975 1284 A Any
1422 1027 1778 1284 1778 1156 B Any
1293 924 1616 1156 1616 1050 C Any
1185 840 1481 1050 1481 963 D Any
120D20 Jumper Settings
High Low HEAT Tap ADJ Tap
2250 1539 A Any
2133 1385 B Any
1939 1259 C Any
1778 1154 D Any
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6”
w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external
static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower that what is required to operate an airflow switch on certain models of electronic air
cleaners. Consult the instructions for the electronic air cleaner for further details.
* The ADJ “D” tap should not be used.