036-21551-001-B-0305 ® TECHNICAL GUIDE ® DESCRIPTION ASHRAE 90.1 COMPLIANT MagnaDRY™ SINGLE PACKAGE AIR CONDITIONERS AND SINGLE PACKAGE GAS/ELECTRIC UNITS DR090, 120 and 150 YORK® Predator® MagnaDry™ units are convertible single packages with a common footprint cabinet and common roof curb for all 7-1/2 through 12-1/2 ton models. All units have two compressors with independent refrigeration circuits to provide 2 stages of cooling.
036-21551-001-B-0305 TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 29 TYPICAL LOW VOLTAGE FIELD WIRING . . . . . . . . . . . 53 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 30 FIELD WIRING DISCONNECT-COOLING UNIT WITH/ WITHOUT ELECTRIC HEAT . . . . . . . . . . . . . . . . . . . . . . 54 FACTORY INSTALLED OPTIONS . . . . . . . . . . . . . . . . . . . . . 7 FIELD INSTALLED ACCESSORIES . . . . . . . .
036-21551-001-B-0305 16 ELECTRICAL DATA DR150 W/PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . 31 26 BLOWER PERFORMANCE DR150 SIDEFLOW . . . . . . . 40 17 ELECTRIC HEAT MULTIPLIERS . . . . . . . . . . . . . . . . . . . 31 27 BLOWER PERFORMANCE DR150 SIDEFLOW ECONOMIZER . . . . . . . . . . . . . . . . . . . . . . . 41 18 BLOWER PERFORMANCE DR090 SIDEFLOW . . . . . . . 32 28 BLOWER PERFORMANCE DR150 DOWNFLOW . . . . . 42 19 BLOWER PERFORMANCE DR090 SIDEFLOW ECONOMIZER . . . .
036-21551-001-B-0305 Simplicity® control board w/ screw connector for T-stat wiring and network connections Disconnect location (optional disconnect switch) Filter access (2” throw-away) Filter drier (solid core) Terminal block for hi-voltage connection Condenser section Second model nameplate inside hinged access panel Slide-out motor and blower assembly fo easy adjustment and service Dual stage cooling for maximum comfort Belt-drive blower motor Power ventor motor Compressor #2 access (higheffici
036-21551-001-B-0305 Second model nameplate inside hinged access panel Simplicity™ Control board w/screw connectors for T-stat wiring and Network Connection Disconnect location (optional disconnect switch) Filter access (2" throw-away) Filter drier (solid core) Condenser Section Dual stage cooling for maximum comfort Belt-drive blower motor Slide out motor and blower assembly for easy adjustment and service Compressor #2 access (high-efficiency compressor w/ crankcase heater) Power ventor motor 20-g
036-21551-001-B-0305 • Balanced Heating – The Predator® offers “Ultimate Heating Comfort” with a balance between 1st and 2nd stage gas heating. The first stage of a gas heat Predator® unit provides 60% of the heating capacity. Balanced heating allows the unit to better maintain desired temperatures. • Convertible Airflow Design – The side duct openings are covered when they leave the factory.
036-21551-001-B-0305 and stainless steel tubular heat exchangers carry a 10year warranty. door air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory. FACTORY INSTALLED OPTIONS YORK® offers several equipment options factory installed, for the Predator® line. • Downflow Economizer - (With barometric relief) - The economizer is provided with a single enthalpy input.
036-21551-001-B-0305 • • Technicoat Evaporator Coil - The evaporator coils are coated with a phenolic coating for protection against corrosion due to harsh environments. BAS - Building Automation System Controls Simplicity® Intelli-Comfort™ Control - The York Simplicity® Intelli-Comfort™ control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor.
036-21551-001-B-0305 connector in the unit bulkhead. You must purchase 1EH0408 barometric relief when applying to a horizontal flow application. • Manual Outdoor Air Damper - Like the motorized outdoor air damper, each manual outdoor air damper includes a slide-in damper assembly with an outdoor air hood and filters. Customers have a choice of dampers with ranges of 0% to 100% or 0% to 35% outdoor air entry.
036-21551-001-B-0305 When the room thermostat calls for second stage cooling, the RCB senses a signal through "Y1" & "Y2" and engages circuit #1 and circuit #2 in cooling mode. Indoor blower operation is initiated upon a call for first stage cooling, second stage cooling or dehumidification. Anytime there is a call for 2 stages of cooling, the unit will not operate in the reheat mode, even if there is a call for dehumidification at "HUM".
036-21551-001-B-0305 FIGURE 4 - DR090 & 120 REHEAT CONTROLS Unitary Products Group 11
036-21551-001-B-0305 FIGURE 5 - DR150 REHEAT CONTROLS 12 Unitary Products Group
036-21551-001-B-0305 TABLE 1: ACCESSORIES Part Number 1RC0470 1RC0471 1RC0472 1BD0408 2TP04520925 2TP04521825 2TP04522425 2TP04523625 2TP04525425 2TP04520946 2TP04521846 2TP04522446 2TP04523646 2TP04525446 2TP04520958 2TP04521858 2TP04522458 2TP04523658 2TP04525458 1FA0411 1FA0412 2MD04702724 2MD04703324 2EE04705024 2EE04705124 2EE04705224 2PE04703225 2PE04703246 2PE04703258 2EC04700924 1EH0407 1RD0411 1EH0408 1EH0409 2AQ04700424 2AQ04700324 2SD04700424 2MK04700624 1CG0419 1CG0420 1CG0424 1CG0425 1HG0411
036-21551-001-B-0305 NOMENCLATURE Predator MagnaDRY™ Model Number Nomenclature D R 090 N10 A 2 A AA 3 Product Generation Product Category 3 = Third Generation 4 = Fourth Generation D = Air Cond., Single Package Product Identifier R = R-22 Reheat Voltage 2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60 Nominal Cooling Capacity - MBH 090 = 7-1/2 Ton 120 = 10 Ton 150 = 12-1/2 Ton Heat Type & Nominal Heat Capacity C00 = Cooling Only.
036-21551-001-B-0305 NOMENCLATURE ADDITIONAL OPTIONS: AA AB AC AD AE AF AG AH AJ AK AL AM AN CA CB CC CD CE CF CG CH CJ CK CL CM CN CP CQ CR CS CT CU CV CW CX JA JB JC JD JE JF JG JH JJ JK JL JM JN JP JQ JR JS JT JU JV JW JX HA None Phase Monitor Coil Guard Dirty Filter Switch Phase Monitor & Coil Guard Phase Monitor & Dirty Filter Switch Coil Guard & Dirty Filter Switch Phase Monitor, Coil Guard, & Dirty Filter Switch SS Drain Pan SS Drain Pan & Phase Monitor SS Drain Pan & Coil Guard SS Drain Pan & Dirt
036-21551-001-B-0305 HB HC HD HE HF HG HH HJ HK HL HM HN HP HQ HR HS HT HU HV HW HX WA WB WC WD WE WF WG WH WJ WK WL WM WN WP WQ WR WS WT WU WV WW WX NA NB NC ND NE NF NG NH NJ NK NL NM NN NP NQ NR 16 Honeywell Excel 10 Controller, DFS, APS & Phase Monitor Honeywell Excel 10 Controller, DFS, APS & Coil Guard Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond.
036-21551-001-B-0305 NS NT NU NV NW NX LA LB LC LD LE LF LG LH LJ LK LL LM LN LP LQ LR LS LT LU LV LW LX TA TB TC TD TE TF TG TH TJ TK TL TM TN TP TQ TR TS TT TU TV TW TX TY TZ T1 T3 T4 T6 T7 T9 Novar ETC-3 Controller, DFS, APS, SS Drain Pan Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat
036-21551-001-B-0305 TABLE 2: PHYSICAL DATA Component Evaporator Blower Evaporator Coil Reheat Coil Condenser Fan Condenser Coil Refrigerant Charge Compressors Air Filters 18 Blower, Centrifugal (Dia. X Wd. In.) Motor, Standard (HP) Motor, Optional (HP) Rows Fins per Inch Height (in.) Face Area (ft.2) Rows Fins per Inch Height (in.) Face Area (ft.2) Quantity Propeller Dia. (in., each) Motor (HP, each) CFM, Nominal (each) Number of Coils Rows (each) Fins per Inch Height (in., each) Face Area (ft.
036-21551-001-B-0305 TABLE 3: DR CAPACITY RATINGS Cooling Capacity ARI Ratings1 Size Nominal Electric Heat Capacity3 (kW) Input (MBH) Output (MBH) Seasonal Efficiency (%) Temp.
036-21551-001-B-0305 TABLE 5: COOLING CAPACITY DR090 UNIT Air On Evap. Coil Temperature of Air on Condenser Coil 85°F Temperature of Air on Condenser Coil 95°F CFM WB (°F) 86 Sensible Capacity (MBH) Return Dry Bulb (°F) 83 80 77 74 71 68 Total Cap.* (MBH) 105 6.7 60 54 47 41 35 28 22 96 7.3 2250 72 67 62 57 94 6.5 73 67 61 54 48 41 35 87 85 82 6.3 6.3 85 82 79 82 72 75 66 69 60 62 53 56 47 50 109 6.8 67 59 51 44 36 29 2625 72 67 62 57 97 6.
036-21551-001-B-0305 TABLE 6: COOLING CAPACITY DR090 UNIT (ALTERNATE REHEAT MODE) Air On Evap. Coil Temperature of Air on Condenser Coil 85°F Tot. Temperature of Air on Condenser Coil 95°F Sensible Capacity (MBH) Return Dry Bulb (°F) 83 80 77 74 71 Tot. Sensible Capacity (MBH) Return Dry Bulb (°F) 83 80 77 74 71 Total Cap.* (MBH) Input† (kW) 86 44 6.6 10 3 - - - - 2250 72 67 62 57 39 6.3 17 11 4 - - 35 37 6.0 5.7 24 28 18 21 11 15 5 8 2 72 67 62 57 45 6.
036-21551-001-B-0305 TABLE 7: COOLING CAPACITY DR120 UNIT Temperature of Air on Condenser Coil 85°F Air On Evap. Coil Temperature of Air on Condenser Coil 95°F CFM WB (°F) Cap.1 (MBH) Input2 (kW) 86 Sensible Capacity (MBH) Return Dry Bulb (°F) 83 80 77 74 71 68 Total Cap.1 (MBH) 134 8.6 80 72 63 54 46 37 29 126 9.4 3000 72 67 62 57 121 8.4 96 88 79 71 62 53 45 113 110 108 8.3 8.2 110 108 105 108 97 99 88 91 79 82 71 74 62 65 103 100 139 8.
036-21551-001-B-0305 TABLE 8: COOLING CAPACITY DR120 UNIT (ALTERNATE REHEAT MODE) Air On Evap. Coil CFM 3000 3500 4000 4500 5000 Temperature of Air on Condenser Coil 85°F Temperature of Air on Condenser Coil 95°F Total Tot. Cap. (MBH) 1 Input (kW) 86 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 56 8.8 9 1 - - - - 50 8.4 21 13 4 - - 43 44 8.0 7.8 32 37 24 28 15 20 6 11 2 56 8.8 8 - - - - - - 49 9.1 10 - - - - - - 50 8.
036-21551-001-B-0305 TABLE 9: COOLING CAPACITY DR150 UNIT Air On Evap. Coil CFM 3750 4375 5000 5625 6250 Temperature of Air on Condenser Coil 85°F Total Cap.1 (MBH) Tot. Input2 (kW) 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 174 10.9 160 Temperature of Air on Condenser Coil 95°F 68 Total Cap.1 (MBH) Tot. Input2 (kW) 86 Sensible Capacity (MBH) Return Dry Bulb (°F) 83 80 77 74 71 34 168 11.9 97 86 75 65 54 43 32 72 62 153 11.
036-21551-001-B-0305 TABLE 10: COOLING CAPACITY DR150 UNIT (ALTERNATE REHEAT MODE) Air On Evap. Coil CFM 3750 4375 5000 5625 6250 Temperature of Air on Condenser Coil 85°F Temperature of Air on Condenser Coil 95°F Total Cap.1 (MBH) Tot. 2 Input (kW) 86 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 70 10.7 14 4 - - - - 63 10.2 28 17 6 - - 57 52 9.7 9.8 42 43 31 33 21 22 10 11 74 10.5 11 - - 66 10.0 38 25 13 60 55 9.5 9.
036-21551-001-B-0305 Moisture Removal Rate (lbs Water/Hour) DR090 Moisture Removal @ 3000 cfm Alternate Mode @ various indoor (dry bulb / wet bulb) conditions 70 60 50 40 30 20 10 0 65 75 85 95 105 Outdoor Temperature (°F) 75db/71wb 85db/71wb 80db/71wb 80db/67wb 75db/67wb 85db/67wb FIGURE 6 - DR090 MOISTURE REMOVAL - ALTERNATE MODE DR090 Moisture Removal @ 3000 cfm Normal Mode @ various indoor (dry bulb / wet bulb) conditions Moisture Removal Rate (lbs Water/Hour) 30 25 20 15 10 5 65 75 85
036-21551-001-B-0305 DR120 Moisture Removal @ 4000 cfm Alternate Mode @ various indoor (dry bulb / wet bulb) conditions 90 Moisture Removal Rate (lbs Water/Hour) 80 70 60 50 40 30 20 10 0 65 75 85 95 105 Outdoor Temperature (°F) 75db/71wb 85db/71wb 80db/71wb 80db/67wb 75db/67wb 85db/67wb FIGURE 8 - DR120 MOISTURE REMOVAL - ALTERNATE MODE DR120 Moisture Removal @ 4000 cfm Normal Mode @ various indoor (dry bulb / wet bulb) conditions Moisture Removal Rate (lbs Water/Hour) 40 35 30 25 20 15 10 5
036-21551-001-B-0305 Moisture Removal Rate (lbs Water / Hour) DR150 Moisture Removal @ 5000cfm Alternate Mode @ various indoor (dry bulb / wet bulb) conditions 100 90 80 70 60 50 40 30 20 10 0 65 75 85 95 105 Outdoor Temperature 75db/71wb 80db/71wb 75db/67wb 85db/71wb 80db/67wb 85db/67wb FIGURE 10 - DR150 MOISTURE REMOVAL - ALTERNATE MODE DR150 Moisture Removal @ 5000cfm Normal Mode @ various indoor (dry bulb / wet bulb) conditions Moisture Removal Rate (lbs Water / Hour) 50 40 30 20 10 0 65
036-21551-001-B-0305 TABLE 11: ELECTRICAL DATA DR090 W/O PWRD CONVENIENCE OUTLET Compressors Voltage 208 230 460 575 * OD Fan Motors Supply Blower Motor FLA RLA LRA FLA 1.5 2 ea. ea. ea. HP HP 13.1 13.1 6.7 5.1 110.0 110.0 54.0 44.0 1.5 1.5 0.8 0.6 6.2 6.2 3.1 2.4 8.2 8.2 4.1 3.6 Pwr Exh Motor Pwr Conv Outlet FLA FLA 5.5 5.5 2.2 1.8 0.0 0.0 0.0 0.0 Electric Heater Model No. Actual KW Heater Amps Min.
036-21551-001-B-0305 TABLE 13: ELECTRICAL DATA DR120 W/O PWRD CONVENIENCE OUTLET Compressors Voltage 208 230 460 575 * OD Fan Motors Supply Blower Motor FLA RLA LRA FLA 2 3 ea. ea. ea. HP HP 16.0 16.0 8.3 6.4 137.0 137.0 69.0 58.0 3.5 3.5 1.6 1.3 8.2 8.2 4.1 3.6 10.9 10.9 5.3 4.1 Pwr Exh Motor Pwr Conv Outlet FLA FLA 5.5 5.5 2.2 1.8 0.0 0.0 0.0 0.0 Electric Heater Model No. Actual KW Heater Amps Min.
036-21551-001-B-0305 TABLE 15: ELECTRICAL DATA DR150 W/O PWRD CONVENIENCE OUTLET Compressors Voltage 208 LRA FLA 3 5 ea. ea. ea. HP HP 20.0 460 8.4 575 7.1 * Supply Blower Motor FLA RLA 20.0 230 OD Fan Motors 146.0 146.0 73.0 60.0 1.5 1.5 0.8 0.6 10.9 10.9 5.3 4.1 16.1 16.1 8.1 6.0 Pwr Exh Motor Pwr Conv Outlet FLA FLA 5.5 5.5 2.2 1.8 0.0 0.0 0.0 0.0 Electric Heater Model No. Actual KW Heater Amps Min.
036-21551-001-B-0305 TABLE 18: BLOWER PERFORMANCE DR090 SIDEFLOW DR090 Standard Drive Assembly (Side Flow) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 ---- ------- ------- ------- ---3885 848 1585 1.70 3647 849 1517 1.63 3439 850 1444 1.55 3235 852 1363 1.46 3012 853 1276 1.37 2748 856 1182 1.27 2417 859 1081 1.
036-21551-001-B-0305 TABLE 19: BLOWER PERFORMANCE DR090 SIDEFLOW ECONOMIZER DR090 Standard Drive Assembly (Side Flow) (100% Return Economizer) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 3886 3709 3517 3310 3088 2853 2605 2343 846 1588 847 1530 848 1468 849 1401 851 1329 853 1250 855 1164 858 1070 0 Turns Open 1.70 1.64 1.57 1.50 1.43 1.34 1.25 1.
036-21551-001-B-0305 TABLE 20: BLOWER PERFORMANCE DR090 DOWNFLOW DR090 Standard Drive Assembly (Down Flow) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 ---3619 3385 3182 2985 2764 2494 2147 ------- ---853 1468 1.57 854 1402 1.50 855 1334 1.43 857 1261 1.35 859 1181 1.27 861 1092 1.17 864 990 1.
036-21551-001-B-0305 TABLE 21: BLOWER PERFORMANCE DR090 DOWNFLOW ECONOMIZER DR090 Optional Drive Assembly (Down Flow) (100% Return Economizer) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.2 0.3 0.4 0.5 0.6 0.7 0.8 ---3355 3154 2945 2720 2486 2284 ------854 1393 855 1324 857 1247 859 1166 861 1089 863 1029 0 Turns Open ---1.49 1.42 1.34 1.25 1.17 1.
036-21551-001-B-0305 TABLE 22: BLOWER PERFORMANCE DR120 SIDEFLOW DR120 Standard Drive Assembly (Side Flow) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 ---------4480 4291 4104 3910 3705 3482 3233 ---------937 938 940 941 943 945 948 ---------2201 2115 2023 1926 1824 1717 1607 ---- ------- 4507 ---- 4298 2.36 4102 2.27 3914 2.17 3726 2.07 3533 1.96 3327 1.84 3104 1.
036-21551-001-B-0305 TABLE 23: BLOWER PERFORMANCE DR120 SIDEFLOW ECONOMIZER DR120 Standard Drive Assembly (Side Flow) (100% Return Economizer) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 ------4309 4134 3961 3784 3594 3381 3137 ------939 940 941 942 944 946 948 ------2099 2024 1944 1859 1769 1670 1564 ---- ------- 4214 2.25 4026 2.17 3851 2.09 3678 1.99 3501 1.90 3311 1.79 3098 1.
036-21551-001-B-0305 TABLE 24: BLOWER PERFORMANCE DR120 DOWNFLOW DR120 Standard Drive Assembly (Down Flow) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 4755 4455 4213 4006 3811 3603 3359 3056 914 2162 2.32 915 2034 2.18 917 1935 2.08 918 1851 1.99 920 1767 1.90 922 1669 1.79 924 1543 1.66 926 1375 1.
036-21551-001-B-0305 TABLE 25: BLOWER PERFORMANCE DR120 DOWNFLOW ECONOMIZER DR120 Standard Drive Assembly (Down Flow) (100% Return Economizer) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.2 0.3 0.4 0.5 0.6 0.7 4461 915 2037 2.19 4216 917 1936 2.08 3982 919 1840 1.97 3730 921 1730 1.86 3404 924 1567 1.68 2902 928 1288 1.38 0 Turns Open 4050 3820 3593 3337 2988 ---- 878 1801 879 1707 881 1613 883 1496 886 1317 ------1 Turn Open 1.93 1.83 1.
036-21551-001-B-0305 TABLE 26: BLOWER PERFORMANCE DR150 SIDEFLOW DR150 Standard Drive Assembly (Side Flow) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 ---------------5029 4862 4697 4535 4379 4230 4090 ---------------1087 1089 1092 1094 1096 1098 1099 ---------------3317 3191 3066 2947 2835 2734 2646 ---------------3.56 3.42 3.29 3.16 3.04 2.93 2.
036-21551-001-B-0305 TABLE 27: BLOWER PERFORMANCE DR150 SIDEFLOW ECONOMIZER DR150 Standard Drive Assembly (Side Flow) (100% Return Economizer) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 ------------4876 4741 4612 4486 4363 4240 4116 3990 3859 ------------1086 1088 1090 1092 1094 1096 1098 1101 1103 ------------3219 3126 3037 2952 2868 2784 2700 2613 2522 ------------3.45 3.35 3.26 3.17 3.
036-21551-001-B-0305 TABLE 28: BLOWER PERFORMANCE DR150 DOWNFLOW DR150 Standard Drive Assembly (Down Flow) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 ---- ------- ------- ------- ------- ------- ---4919 1091 3182 3.41 4721 1092 3073 3.30 4530 1094 2958 3.17 4347 1096 2839 3.05 4172 1099 2717 2.91 4007 1101 2595 2.78 3853 1104 2475 2.
036-21551-001-B-0305 TABLE 29: BLOWER PERFORMANCE DR150 DOWNFLOW ECONOMIZER DR150 Standard Drive Assembly (Down Flow) (100% Return Economizer) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 ------4893 4726 4567 4414 4264 4116 3968 ------1091 1092 1094 1095 1097 1099 1102 ------3168 3076 2981 2883 2782 2676 2566 ------3.40 3.30 3.20 3.09 2.98 2.87 2.
036-21551-001-B-0305 TABLE 30: ADDITIONAL STATIC RESISTANCE CFM Gas Heat Electric Heat KW 9 18 24 36 54 2300 0.08 0.07 0.08 0.09 0.10 0.13 2500 0.09 0.08 0.09 0.10 0.11 0.14 2700 0.11 0.09 0.10 0.12 0.13 0.16 2900 0.12 0.10 0.11 0.13 0.14 0.18 3100 0.14 0.12 0.13 0.15 0.16 0.20 3300 0.16 0.13 0.14 0.17 0.18 0.22 3500 0.18 0.15 0.16 0.19 0.20 0.24 3700 0.20 0.17 0.18 0.21 0.22 0.26 3900 0.23 0.19 0.20 0.23 0.24 0.28 4100 0.25 0.21 0.
036-21551-001-B-0305 TABLE 32: INDOOR BLOWER SPECIFICATIONS MODEL DR090 DR120 DR150 HP RPM 1-1/2 2 2 3 3 5 1725 1725 1725 1725 1725 1725 MOTOR Eff. SF 80% 80% 80% 80% 80% 87% Frame 1.15 1.15 1.15 1.15 1.15 1.15 56 56 56 56 56 184T MOTOR SHEAVE Datum Dia. (in.) Bore (in.) 3.4 - 4.4 3.4 - 4.4 3.4 - 4.4 3.4 - 4.4 3.4 - 4.4 4.3 - 5.3 7/8 7/8 7/8 7/8 7/8 1 1/8 Model BLOWER SHEAVE Datum Dia. (in.) Bore (in.) 1VM50 1VM50 1VM50 1VM50 1VM50 1VP56 9.0 7.5 8.5 7.0 7.0 6.
036-21551-001-B-0305 FRONT LEFT B FRONT C C LEFT A B A D D FIGURE 14 - DR090, 120 UNITS 4 POINT LOAD FIGURE 17 - DR150 UNIT 4 POINT LOAD FRONT LEFT FRONT D C D LEFT B A C A E B F F FIGURE 15 - DR090, 120 UNITS 6 POINT LOAD TABLE 34: 4 POINT LOAD WEIGHT Model A Location (lbs.) B C D 250 215 309 374 DR120 276 237 341 408 DR150 293 370 479 393 LEFT Model FR O N T Locations (lbs.
036-21551-001-B-0305 TABLE 36: UNIT WEIGHT Shipping Weight (lbs.) Model Operating Weight (lbs.) DR090 1163 1148 DR120 1277 1262 1545 DR150 1560 W/ECON. 85 84 W/PE 150 148 W/ELECT. HEAT1 W/GAS HEAT2 1. 54 KW Heater 2.
036-21551-001-B-0305 119-7/16 For Gas Pipe Entry see DETAIL A Convenience Outlet Power Entry 2-1/2 30-11/32 4-1/4 Convenience Outlet Power Entry 7/8 Control Entry 7/8 50-3/4 11-1/2 FRONT For Baserail Dimensions see DETAIL B 30-3/16 17-3/16 24-3/16 6-3/16 59 89 27 LEFT For Drain Dimensions see DETAIL C FIGURE 21 - DR150 UNIT DIMENSIONS G a s P ip e In le t DETAIL A 2-3/8 DETAIL B 5 -1 /4 B a s e P a n 1 7 -1 3 /1 6 V ie w o f W a ll A c r o s s fr o m 3-3/4 C o il TABLE 37: UNIT CL
036-21551-001-B-0305 R IG H T 8 0 -5 /8 IN S U L A T E D D E C K U N D E R C O N D E N S E R S E C T IO N 2 0 2 0 S U P P L Y 6 R E T U R N 2 T Y P .
036-21551-001-B-0305 32-11/16 6-13/16 Supply Air 6-13/16 6-13/16 Return Air 24 LEFT 27-1/2 21 18 21-3/16 19-3/16 17-3/16 12-5/16 7-1/8 14-23/32 FRONT 16-3/8 18-1/16 19-5/8 Bottom Condensate Drain Bottom Power, Control and Convenience Outlet Wiring Entries Bottom Gas Supply Entry 63-1/2 FIGURE 24 - BOTTOM DUCT OPENINGS (FROM ABOVE) 18-1/4 Dot Plugs Supply Air Return Air A 18-1/4 B 5-5/32 2-31/32 C 31-11/16 FIGURE 25 - DR090, 120 REAR DUCT DIMENSIONS 50 Unitary Products Group
036-21551-001-B-0305 Dot Plugs 18-1/4 Return Air 28-1/4 Supply Air 18-1/4 18-1/16 2-31/32 28-1/4 31-11/16 5-5/32 FIGURE 26 - DR150 REAR DUCT DIMENSIONS RU FIGURE 27 - DOWNFLOW ECONOMIZER HOOD DETAIL Unitary Products Group 51
036-21551-001-B-0305 ! " # $ % FIGURE 28 - DOWNFLOW ECONOMIZER HOOD DETAIL 52 Unitary Products Group
036-21551-001-B-0305 THERMOSTAT TERMINALS 1 ( RCB ) REHEAT CONTROL BOARD RC RH R Y1 Y1 Y2 Y2 W1 W1 W2 W2 G G C C OCC X1 X3 TERMINAL BLOCK RH 2 X4 A1 HUM 1 A2 HUM 2 T DEHUMIDISTAT 3 3 T 4 TO REMOTE SENSOR 2ET04701324 IF USED 1 Electronic programmable Thermostat 2ET0770010024 ( includes subbase). 2 Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set-back position. 3 Dehumidistat closes on rise in humidity.
036-21551-001-B-0305 TERMINAL BLOCK TB1 FACTORY OR FIELD SUPPLIED DISCONNECT GROUND LUG THREE PHASE POWER SUPPLY FIGURE 30 - FIELD WIRING DISCONNECT-COOLING UNIT WITH/WITHOUT ELECTRIC HEAT CONTACTOR 1M GROUND LUG T1 T2 T3 L1 L2 L3 FACTORY OR FIELD SUPPLIED DISCONNECT THREE PHASE POWER SUPPLY FIGURE 31 - FIELD WIRING DISCONNECT-COOLING UNIT WITH GAS HEAT 54 Unitary Products Group
036-21551-001-B-0305 FIGURE 32 - DR090, 120 COOLING UNIT WITH GAS HEAT WIRING 230 VOLT DIAGRAM Unitary Products Group 55
036-21551-001-B-0305 FIGURE 33 - DR150 COOLING UNIT WITH GAS HEAT WIRING 230 VOLT DIAGRAM 56 Unitary Products Group
036-21551-001-B-0305 FIGURE 34 - DR090, 120 COOLING UNIT WITH/WITHOUT ELECTRIC HEAT WIRING DIAGRAM Unitary Products Group 57
036-21551-001-B-0305 FIGURE 35 - DR150 COOLING UNIT WITH/WITHOUT ELECTRIC HEAT WIRING DIAGRAM 58 Unitary Products Group
036-21551-001-B-0305 FIGURE 36 - DR090, 120 COOLING UNIT WITH GAS HEAT WIRING 460, 575 VOLT 50 HZ DIAGRAM Unitary Products Group 59
036-21551-001-B-0305 FIGURE 37 - DR150 COOLING UNIT WITH GAS HEAT WIRING 460, 575 & 50 HZ DIAGRAM 60 Unitary Products Group
036-21551-001-B-0305 FIGURE 38 - DR090 AND 120 REHEAT WIRING DIAGRAM Unitary Products Group 61
036-21551-001-B-0305 FIGURE 39 - DR150 REHEAT WIRING DIAGRAM 62 Unitary Products Group
036-21551-001-B-0305 GUIDE SPECIFICATIONS PREDATOR® MagnaDRY™ DR 090, 120 & 150 GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK® Predator® MagnaDRY™ units are convertible single packages with a common footprint cabinet and common roof curb for all 7-1/2 through 12-1/2 ton models. All units have two compressors with independent refrigeration circuits to provide 2 stages of cooling.
036-21551-001-B-0305 Refrigerant Circuit and Refrigerant Safety Components shall include: air entering temperature of 40 ºF. Burners shall be of the inshot type, constructed of aluminum-coated steel. All gas piping shall enter the unit cabinet at a single location, through either the side or bottom, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition.
036-21551-001-B-0305 2. outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55 ºF. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible.
036-21551-001-B-0305 66 Unitary Products Group
036-21551-001-B-0305 Unitary Products Group 67
Subject to change without notice. Printed in U.S.A. Copyright © 2005 by Unitary Products Group . All rights reserved.