Specifications

Consolidated Drawing
DETAIL A
3/4" FPT
5.32
[135]
DIRECTION OF AIRFLOW
CENTER OF GRAVITY
NOTES:
1. FOR OUTDOOR USE ONLY.
2. WEIGHTS SHOWN ARE FOR COOLING ONLY UNITS.
3. MIN. CLEARANCES TO BE:
RIGHT SIDE: 12 [305]
LEFT SIDE: 36 [915]
FRONT: 36 [915]
REAR: 36 [915]
TOP: 72 [1830]
BOTTOM: 0 [0]
4. TO REMOVE THE SLIDE-OUT DRAIN PAN, A REAR CLEARANCE OF
60 in (1525 mm) IS REQUIRED. IF SPACE IS UNAVAILABLE, THE
DRAIN PAN CAN BE REMOVED THROUGH THE FRONT BY SEPARATING
THE CORNER WALL.
5. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES
CONTACT YOUR APPLICATION ENGINEERING DEPARTMENT.
6. DOWNFLOW DUCTS DESIGNED TO BE ATTACHED TO ACCESSORY
ROOF CURB ONLY. IF UNIT IS MOUNTED SIDE SUPPLY, IT
IS RECOMMENDED THAT THE DUCTS ARE SUPPORTED BY
CROSS BRACES, AS DONE ON ACCESSORY ROOF CURBS.
7. SIDE DUCT FLANGES ARE 0.75" HIGH.
BOTTOM DUCTS DO NOT HAVE FLANGES.
8. MINIMUM CONDENSATION TRAP HEIGHT SHALL BE 1.5 TIMES
THE LOWEST NEGATIVE STATIC.
9. DIMENSIONS IN [ ] ARE IN MILLIMETERS OR KILOGRAMS.
10. OPTIONAL COIL GUARDS, POWER EXHAUST, GAS HEAT,
ECONOMIZER, DISCONNECT SWITCH, CONVENIENCE OUTLET,
AND BAROMETRIC RELIEF AND FRESH AIR HOODS SHOWN.
11
TONNAGE
UNIT
OPERATING
WEIGHT (LBS)
(BASE UNIT)
CENTER OF GRAVITY
LOCATION (BASE UNIT)
4 POINT CORNER LOADS (LBS) (BASE UNIT)
X Y A B C D
8.5
1007 [458] 38 [965] 24 [610] 235 [107] 175 [79] 255 [116] 342 [155]
10
1103 [501] 38 [965] 24 [610] 257 [117] 192 [87] 279 [127] 375 [170]
8.5
1030 [467] 38 [965] 24 [610] 240 [109] 179 [81] 261 [118] 350 [159]
10
1090 [494] 38 [965] 24 [610] 254 [115] 189 [86] 276 [125] 371 [168]
6.5
1030 [467] 39 [991] 25 [635] 245 [111] 191 [87] 260 [118] 333 [151]
7.5
1050 [476] 39 [991] 25 [635] 250 [113] 195 [89] 265 [120] 340 [154]
8.5
1060 [481] 38 [965] 24 [610] 247 [112] 184 [84] 268 [122] 360 [163]
10
1070 [485] 39 [991] 24 [610] 245 [111] 191 [87] 278 [126] 357 [162]
8.5 & 10
1200 [544] 38 [965] 25.5 [648] 297 [135] 221 [100] 291 [132] 390 [177]
6.5
1080 [490] 38 [965] 25 [635] 262 [119] 195 [89] 266 [121] 357 [162]
7.5
1090 [494] 38 [965] 23 [584] 243 [110] 181 [82] 284 [129] 381 [173]
8.5
1137 [516] 38 [965] 25.5 [648] 282 [128] 210 [95] 276 [125] 370 [168]
10
1135 [515] 38 [965] 25.5 [648] 281 [127] 209 [95] 275 [125] 369 [167]
ZS
ZS
ZU
ZU
ZW
ZW
ZW
ZW
ZK
XA
XA
XA
XA
EXCEPT XA (HEAT PUMP) UNITS.
ɸ
LEFT VIEW
OUTSIDE AIR
INTAKE HOOD
(OPTIONAL)
CTL PANEL/
COMPRESSOR
ACCESS
25.72
[653]
COIL GUARD
(OPTIONAL)
RIGHT VIEW
59.00
[1499]
50.75
[1289]
58.09
[1475]
ALTERNATE CONDENSATION DRAIN
SUPPLY
R
E
T
U
R
N
REAR (PARTIAL VIEW)
(INTAKE HOOD NOT SHOWN IN THIS VIEW)
18.25
[464]
2.88
[73]
31.63
[803]
28.25
[718]
18.25
[464]
5.16
[131]
18.06
[459]
28.25
[718]
10.50
[267]
2.00 [51]
BOTTOM ENTRY:
POWER 2.50 [64]
CONTROL 3X 0.875 [22]
ɸɸ
BOTTOM GAS
SUPPLY ENTRY
R
E
T
U
R
N
S
U
P
P
L
Y
A
B
C
D
LEFT
RIGHT
FRONT
TOP VIEW
24.38
[619]
18.00
[457]
27.50
[699]
21.00
[533]
24.00
[610]
14.47
[368]
16.39
[416]
18.06
[459]
18.89
[480]
17.14
[435]
19.14
[486]
20.14
[512]
20.39
[518]
7.84
[199]
6.83
[173]
32.67
[830]
6.83
[173]
Y
X
32.06
[814]
24.24
[616]
(FROM MTB.
FLANGE)
ɸ
ɸ
ɸ
11
FRONT VIEW
(OPTIONAL FRONT COIL GUARD NOT SHOWN IN THIS VIEW)
DISCONNECT SWITCH COVER
(OPTIONAL)
POWER ENTRY 2.50 [64]
CONTROL ENTRY 0.875 [ 22]
POWER ENTRY 2.50 [64]
CONVENIENCE OUTLET COVER
(OPTIONAL)
CONVENIENCE OUTLET
POWER ENTRY 0.875 [22]
GAS INLET
BAROMETRIC RELIEF HOOD/
POWER EXHAUST (OPTIONAL)
SEE DETAIL A FOR
DRAIN LOCATION
EXHAUST
FLUE
FILTER/
COMPRESSOR
ACCESS
BLOWER ACCESS
FRESH AIR HOOD/
ECONOMIZER
(OPTIONAL)
89.00 [2261]
27.31
[694]
11.38
[289]
21.19
[538]
89.00
[2261]
ɸ
ɸ
ɸ
UnitarySalesToolv1.5.8.0 Informationissubjecttochangewithoutnotice.Checklocalcodes. Printed10/20/2014
6.5-12.5 Ton Package
Single Package R-410A Air Conditioner
Page:3
ProjectName:Jail HVAC Remediation UnitModel#:ZW-07N12AWAZZ5
Quantity:1 System:ZW-07N12AWAZZ5