Specifications
Addr (Hex) Addr (Dec) Bit Init/
Default
Min Value Max Value Description
A9H 169H - 0 255
Buildingpressurevalue(0.001”WC,Highbyte,0=-0.250”
WC,max=0.250”WC)
A9L 169L - 0 255
Buildingpressurevalue(0.001”WC,Lowbyte,0=-0.250”
WC,max=0.250”WC)
AAH 170H - 0 255
DuctPressurevalue(0.01”WC,Highbyte,0=0.00”WC,
max=5.00”WC)
AAL 170L - 0 255
DuctPressurevalue(0.01”WC,Lowbyte,0=0.00”WC,
max=5.00”WC)
ABH 171H 0 0 200
RemoteControlinputvalue(0.05VDCcounts)(coolingSAT
setpointorEconomizer)
ABL 171L 40 0 200
DemandVentilationsetpoint(25PPMincrements,maximum
5000PPM)
ACH 172H 80 0 200
OutdoorAirQualitysensorrange(25PPM
increments,maximum5000PPM)
ACL 172L 80 0 200
AirQuality(DV)sensorrange(25PPMincrements,maximum
5000PPM)
ADL 173L 60 0 240 Unoccupiedoverridetimeperiod(minutes)
AEH 174H 45 0 100
OutdoorAirTemperaturecoolinglockouttemperature
(degreesF,0=disabled)
AEL 174L 75 0 100
OutdoorAirTemperatureheatinglockout
temperature(degreesF,0=disabled)
AFH 175H 50 40 65 SATCoolingLimitsetpoint(degreesF)
AFL 175L 135 100 180 SATHeatingLimitsetpoint(degreesF)
B0H 176H 120 80 179 Hydronicheatingstage#1supplyairsetpoint(degreesF)
B0L 176L 150 81 180 Hydronicheatingstage#2supplyairsetpoint(degreesF)
B1H 177H 80 60 85 Comfortventilationuppersetpoint(degreesF)
B1L 177L 70 60 85 Comfortventilationlowersetpoint(degreesF)
B2H 178H 60 41 70
VAVcoolingSupplyAirTemperature:uppersetpoint(degrees
F)
B2L 178L 55 40 69
VAVcoolingSupplyAirTemperature:lowersetpoint(degrees
F)
B3H 179H 72 40 85
VAVcoolingSupplyAirTemperature:ResetSetpointdegrees
F)
B3L 179L Unused
B4H 180H 70 50 85
MorningWarm-UpandVAVheating:ReturnAirTemperature
setpoint(degreesF)
B4L 180L 40 40 60 SATTemperingwithHydronicHeatSetpoint
B5H 181H 60 0 200
Ductpressuresetpoint(0.025”WCincrements,default=
1.500”WC↔60)
B5L 181L 180 0 200
Ductpressureshutdownsetpoint(0.025”WCincrements,
default=4.500”WC↔180)
B6H 182H 70 0 100
Buildingpressuresetpoint(0.005”WCincrements,0=
-0.250”WC,default=0.100”WC↔70)
B8H 184H 20 0 100 Economizerminimumposition(percent)
B8L 184L 25 0 100 Economizerminimumposition(percent)forLowSpeedFan
UnitarySalesToolv1.5.8.0 Informationissubjecttochangewithoutnotice.Checklocalcodes. Printed10/20/2014
SIMPLICITY® Intelli-Comfort II
Page:21