Specifications
length.Theunitcontrollerwillleavethefactorywith
theserialnumberoftheequipmentitisin,storedin
non-volatilememory.
18. Theunitcontrollershallnotpowerthecontactors
throughthethermostatwiring.Droppingvoltageover
thethermostatwiringcauseschatteringcontactors
whenthecontactorsarepoweredinthismanner.
19. Theunitcontrollershalloperateandmonitorupto2
stagesofheatindependently.
20. TheunitcontrollershallmonitortheGasHeat
operationintheheatingmode.Itshallmonitorthegas
valvewhenthereisacallforheating.Theunit
controllershallalarmwhenthereisacallforheatand
nogasvalvevoltageafter5minutes.
COMFORT CONTROL FEATURES
1. Theunitcontrollershallbeinstalledandtestedatthe
factorywheretheequipmentisassembled.
2. TheunitcontrollershalluseaWallSensorthathasa
meansofoverridingtheunoccupiedmodefora
programmableamountoftime.
3. TheUnoccupiedOverridetimeshallbeprogrammed
inminutesupto4hours.
4. TheunitcontrollershalluseaWallSensorthathasa
warmer/coolerdialsotheoccupantscanoffsetthe
programmedsetpointbyaprogrammedamount
between1and5degreesfahrenheit.
5. TheunitcontrollershallhaveaSupplyAirSensoras
standard.
6. TheunitcontrollershallhaveaReturnAirSensoras
standard.
7. TheunitcontrollershallhaveanOutsideAirSensor
asstandard.
8. TheunitcontrollershallusetheReturnAirSensorin
placeoftheSpaceSensoriftheSpaceSensorfails
foranyreason.
9. Theunitcontrollershallhavea365dayRealTime
Clock.
10. RealTimeClockshallbeabletodoautomatic
DaylightSavingsTimeadjustment.
11. TheunitcontrollershallhaveanOccupancySchedule
thatallowstwodifferentOccupiedschedulesperday
foreachofthesevendaysoftheweekindividually.
12. Theunitcontrollershallhave20HolidaySchedules,
eachcapableof99days.
13. Theunitcontroller'sHolidaySchedulesshallhavea
starttimeassociatedwitheachschedule.
14. TheunitcontrollershallcontroltheEconomizer
directly.
15. Theunitcontrollershallbecapableofoperatingthe
EconomizerusingDryBulb,OutsideEnthalpy,or
DifferentialEnthalpy.
16. WhentheunitcontrollerisusingEnthalpytocontrol
theEconomizer,itshallalsohaveanOutsideAir
TemperatureenableSetpoint.
17. TheunitcontrollershallusetwosetpointsforSupply
AirTemperaturefortheEconomizeroperation.One
willbeforasmallspacecoolingdemandandonefor
alargespacecoolingdemand.
18. Theunitcontrollershallhavetheabilitytoperform
DemandVentilationusingoneCO2sensor.
19. Theunitcontrollershallhaveaprogrammable
maximumOutsideAirDamperPositionforIAQ
operation.
20. Theunitcontrollershallhavetheabilitytotemperthe
ventilationairduringtimeswhenheatingorcoolingis
notrequired.
21. Theunitcontrollershallhavetheabilitytooffsetthe
operatingsetpointbasedonhighHumidityinthe
Space.
22. Theunitcontrollershallhaveprogrammablelimits
whenoffsettingtheOperatingSetpointtocontrol
Humidity.
23. TheunitcontrollershallbeabletolockoutCooling
belowaprogrammableOutsideAirTemperature
Setpoint.
24. TheunitcontrollershallbeabletolockoutHeating
aboveaprogrammableOutsideAirTemperature
Setpoint.
25. TheunitcontrollershallhaveaSpaceTemperature
Alarm.
26. TheunitcontrollershallhaveaSupplyAir
TemperatureAlarmforHeatingandCooling.The
Alarmtemperaturewillbeprogrammable.
27. TheUnitcontrollershallbeabletoperformaPre-
OccupancyPurgeataProgrammableTime.
28. TheunitcontrollershallhaveahardwareSmoke-
Purgeinput.
29. Theunitcontrollershallhavetheabilitytoreadadirty
filterswitch.
30. Theunitcontrollershallhavethecapabilityofreading
afanprovingswitch.
31. Theunitcontrollershallhaveanintelligentrecovery
functionthatwillbringthespacetotheOccupied
Setpointjustbeforeoratthebeginningofthefirst
Occupiedscheduleeachday.Theunitcontrollerwill
learnandapplytheminimumruntimerequiredto
heatorcoolthespacetosetpointforthefirst
Occupiedperiodofaday.
32. TheunitcontrollershallhaveSoftwarecontrollable
ModeSwitches(Heat,Cool,andFan).
33. TheunitcontrollershallmeterandtrackUnoccupied
OverrideTimeforbillingpurposes.
UnitarySalesToolv1.5.8.0 Informationissubjecttochangewithoutnotice.Checklocalcodes. Printed10/20/2014
SIMPLICITY® Intelli-Comfort II