Physical Data
COMPONENT
MODELS
PHG4A24 PHG4A30 PHG4B36 PHG4B42 PHG4B48 PHG4B60
NOMINAL TONNAGE 2.0 2.5 3.0 3.5 4.0 5.0
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH) 23.5 29.4 36.0 41.1 47.0 58.1
AHRI net capacity (MBH) 23.1 29.0 35.5 40.7 45.5 57.5
EER 11.0 11.0 11.0 11.0 11.0 11.0
SEER 14.0 14.0 14.0 14.0 14.0 14.0
Nominal CFM 800 1000 1200 1400 1600 2000
System power (KW) 1.8 2.1 2.8 3.2 3.6 4.7
Refrigerant type R410A R410A R410A R410A R410A R410A
Refrigerant charge (lb-oz) 8-8 9-8 11-13 13-0 12-13 16-10
AHRI Heat Pump Heating Performance
47 Capacity Rating (MBH) 21.9 27.0 33.5 38.1 44.1 55.9
System Power (kW/COP) 1.8 2.1 2.6 2.9 3.5 4.3
17 F Capacity Rating (MBH) 11.3 14.5 19.0 22.0 25.4 31.7
HSPF (BTU/Watts-hr.) 8.0 8.0 8.0 8.0 8.0 8.0
AHRI Gas Heat Performance
Heating model 50 75 50 75 65 100 65 100 65 100 125 65 100 125
Heat input (K Btu) 50.0 75.0 50.0 75.0 65.0 100.0 65.0 100.0 65.0 100.0 125.0 65.0 100.0 125.0
Heat output (K Btu) 40 60 40 60 52 80 52 80 52 80 100 52 80 100
AFUE % 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0
No. burners 2 3 2 3 2 3 2 3 2 3 4 2 3 4
No. stages 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Temperature Rise Range (°F) 40-70 40-70 40-70 40-70 40-70 40-70
Max. Static Pressure w.c. 0.5 0.5 0.5 0.5 0.5 0.5
Max. Outlet Air Temp. (°F) 180 180 180 180 180 180
Gas piping connection (in.) 1/2 1/2 1/2 1/2 1/2 1/2
Dimensions (inches)
Length 51-1/4 51-1/4 51-1/4 51-1/4 51-1/4 51-1/4
Width 35-3/4 35-3/4 45-3/4 45-3/4 45-3/4 45-3/4
Height 47 49 49 49 53 55
Operating WT. (lbs.) 394 404 449 453 498 505 532 534 551 559 564 577 581 588
Compressors
Type Scroll Scroll Scroll Scroll Scroll Scroll
Outdoor Coil Data
Face area (Sq. Ft.) 15.3 17.2 19.8 19.8 24.1 26.3
Rows 2 2 2 2 2 2
Fins per inch 22 22 22 22 22 22
Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8
Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced
Refrigerant Control TXV TXV TXV TXV TXV TXV
Indoor Coil Data
Face area (Sq. Ft.) 3.4 3.4 3.4 4.4 4.4 4.4
Rows 3 3 3 3 3 4
Fins per inch 16 16 16 16 16 16
Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8
Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced
Refrigerant control TXV TXV TXV TXV TXV TXV
Outdoor Fan Data
Fan diameter (Inch) 24 24 26 26 26 26
Type Prop Prop Prop Prop Prop Prop
Drive type Direct Direct Direct Direct Direct Direct
No. speeds 1 1 1 1 1 1
Motor HP each 1/10 1/8 1/3 1/3 1/3 1/3
RPM 850 850 850 850 850 850
Nominal total CFM 2400 2400 3200 3200 3200 3200
Direct Drive Indoor Fan Data
Fan Size (Inch) 11 x 8 11 x 8 11 x 10 11 x 10 11 x 10 11 x 10
Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal
Motor HP each 1/3 1/2 1/3 1/2 1/2 3/4 3/4 3/4 1
RPM 1200 Max 1200 Max 1200 Max 1200 Max 1200 Max 1200 Max
Frame size 48 48 48 48 48 48
Filters
Quantity - Size
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable
filters. For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for
replacement filter sizes. Filter sizes: A=20x20, B=20x30.