Technical Guide

5127524-YTG-A-0815
Johnson Controls Unitary Products 19
1. Airflow tested with dry coil conditions, without air filters, at 230 volts
2. Applications above 0.8" w.c. external static pressure are not recommended.
3. Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
4. Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
5. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
36065
Low (1) 1231 1186 1146 1103
1069 1030 977 912
Low/Medium (2) 1270 1225 1189 1140
1098 1046 1008 960
Medium (3) 1317 1286 1245 1198
1151 1110 1064 1024
Medium/High (4) 1358 1317 1275 1238
1197 1148 1105 1057
High (5) 1517 1475 1447 1400
1357 1318 1275 1232
36100
Low (1) 1340 1299 1264 1224
1182 1182 1097 1049
Low/Medium (2) 1409 1368 1334 1291
1253 1201 1173 1128
Medium (3) 1527 1492 1470 1419
1385 1343 1299 1250
Medium/High (4) 1663 1585 1594 1601
1521 1480 1440 1400
High (5) 1711 1677 1643 1600
1560 1503 1466 1425
42065
Low (1) 1332 1295 1263 1222
1185 1148 1110 1063
Low/Medium (2) 1457 1419 1376 1340
1299 1253 1215 1160
Medium (3) 1451 1412 1371 1339
1296 1257 1211 1165
Medium/High (4) 1568 1524 1491 1464
1425 1383 1345 1296
High (5) 1711 1677 1643 1600
1560 1503 1466 1425
42100
Low (1) 1455 1414 1379 1335
1294 1254 1212 1160
Low/Medium (2) 1566 1532 1492 1455
1416 1372 1333 1280
Medium (3) 1565 1530 1491 1458
1419 1381 1336 1290
Medium/High (4) 1675 1641 1606 1578
1535 1495 1455 1412
High (5) 1711 1677 1643 1600
1560 1503 1466 1425
48065
Low (1) 1032 999 970 938
910 879 843 808
Low/Medium (2) 1272 1236 1204 1165
1129 1081 1037 968
Medium (3) 1611 1574 1518 1494
1439 1405 1357 1266
Medium/High (4) 1892 1777 1771 1701
1639 1617 1565 1489
High (5) 2131 2058 1998 1949
1892 1840 1788 1728
48100
Low (1) 1598 1548 1502 1454
1410 1362 1307 1251
Low/Medium (2) 1663 1612 1568 1522
1476 1422 1370 1297
Medium (3) 1789 1733 1670 1650
1596 1578 1535 1483
Medium/High (4) 1931 1814 1808 1736
1673 1650 1597 1519
High (5) 2131 2058 1998 1949
1892 1840 1788 1728
48125
Low (1) 1598 1548 1502 1454
1410 1362 1307 1251
Low/Medium (2) 1766 1703 1656 1611
1566 1518 1469 1419
Medium (3) 1912 1875 1805 1787
1750 1713 1672 1636
Medium/High (4) 2105 2014 2006 1931
1898 1845 1793 1739
High (5) 2131 2058 1998 1949
1892 1840 1788 1728
60065
Low (1) 1026 999 989 950
907 907 886 862
Low/Medium (2) 1263 1230 1192 1165
1167 1101 1099 1071
Medium (3) 1987 1933 1861 1817
1820 1715 1725 1651
Medium/High (4) 2114 2050 2047 1974
1899 1889 1920 1866
High (5) 2369 2308 2249 2183
2126 2088 2034 1990
60100
Low (1) 1655 1612 1596 1531
1461 1462 1429 1391
Low/Medium (2) 1766 1720 1667 1629
1632 1539 1537 1498
Medium (3) 1987 1933 1861 1817
1820 1715 1725 1651
Medium/High (4) 2114 2050 2047 1974
1899 1889 1920 1866
High (5) 2369 2308 2249 2183
2126 2088 2034 1990
60125
Low (1) 1973 1924 1905 1826
1743 1744 1703 1660
Low/Medium (2) 2024 1983 1937 1889
1886 1843 1799 1759
Medium (3) 2123 2075 2019 1970
1978 1862 1849 1804
Medium/High (4) 2191 2154 2117 2075
2002 1995 2028 1974
High (5) 2369 2308 2249 2183
2126 2088 2034 1990
Airflow - Bottom Duct Application (Continued)
Model Motor Speed
External Static Pressure (Inches WC)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
SCFM SCFM SCFM SCFM
SCFM SCFM SCFM SCFM