Technical Guide

5126749-YTG-A-0715
Johnson Controls Unitary Products 21
BOTTOM DUCT DIMENSIONS (Inches)
REAR DUCT DIMENSIONS (Inches)
Additional Static Resistance
Size (Tons) CFM Wet Indoor Coil Economizer
1
1. The pressure drop through the economizer is greater for 100% outdoor air
than for 100% return air. If the resistance of the return air duct is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter pressure drop based on standard filter media tested at velocities not to
exceed 300 ft/min.
Filter/Frame Kit
24 (2.0)
500 0.01 0.00 0.01
600 0.01 0.00 0.02
700 0.01 0.00 0.04
800 0.02 0.01 0.06
900 0.03 0.01 0.08
1000 0.04 0.01 0.10
1100 0.05 0.01 0.13
1200 0.06 0.02 0.16
30 (2.5)
700 0.01 0.00 0.04
800 0.02 0.01 0.06
900 0.03 0.01 0.08
1000 0.04 0.01 0.10
1100 0.05 0.01 0.13
1200 0.06 0.02 0.16
1300 0.07 0.03 0.17
36 (3.0)
700 0.01 0.00 0.04
800 0.02 0.01 0.06
900 0.03 0.01 0.08
1000 0.04 0.01 0.10
1100 0.05 0.01 0.13
1200 0.06 0.02 0.16
1300 0.07 0.03 0.17
1400 0.08 0.04 0.18
42 (3.5)
1100 0.02 0.02 0.04
1200 0.03 0.02 0.04
1300 0.04 0.02 0.05
1400 0.05 0.03 0.05
1500 0.06 0.04 0.06
1600 0.07 0.04 0.07
1700 0.07 0.04 0.08
1800 0.08 0.04 0.09
1900 0.09 0.05 0.10
2000 0.09 0.05 0.11
48 (4.0)
1100 0.02 0.02 0.04
1200 0.03 0.02 0.04
1300 0.04 0.02 0.05
1400 0.05 0.03 0.05
1500 0.06 0.04 0.06
1600 0.07 0.04 0.07
1700 0.07 0.04 0.08
1800 0.08 0.04 0.09
1900 0.09 0.05 0.10
2000 0.09 0.05 0.11
60 (5.0)
1100 0.02 0.02 0.04
1200 0.03 0.02 0.04
1300 0.04 0.02 0.05
1400 0.05 0.03 0.05
1500 0.06 0.04 0.06
1600 0.07 0.04 0.07
1700 0.07 0.04 0.08
1800 0.08 0.04 0.09
1900 0.09 0.05 0.10
2000 0.09 0.05 0.11
Model ABCDEF
24, 30, 36, 42 10 21.5 5 4.5 47.5 32
48, 60 14 13.5 5 3.5 47.5 42
Model A B
24, 30, 36, 42 9.6 22
48, 60 13.6 14
'

&
$
%
$
$
6833/<
$,5'8&7
5(7851
$,5'8&7
(
)
15.6
A
B
A
4.3
A0344-001
6
SUPPLY
AIR DUCT
RETURN
AIR DUCT