Technical Guide

546039-YTG-C-0211
38 Unitary Products Group
Electric Heat Minimum Supply Air
Size
(Tons)
Model Voltage
Minimum Supply Air (CFM)
Heater kW
5.0 6.5 10 15
024
(2.0)
NM 208/230-1-60 800 800 800 775
030
(2.5)
NM 208/230-1-60 800 800 800 775
036
(3.0)
NM 208/230-1-60 800 800 800 775
042
(3.5)
NM 208/230-1-60 800 800 800 775
048
(4.0)
NM 208/230-1-60 1300 1300 1270 1160
060
(5.0)
NM 208/230-1-60 1300 1300 1270 1160
024
(2.0)
UQ 208/230-1-60 800 800 800 750
030
(2.5)
UQ 208/230-1-60 800 800 800 750
036
(3.0)
UQ 208/230-1-60 800 800 800 750
042
(3.5)
UQ 208/230-1-60 1300 1300 1270 1270
048
(4.0)
UQ 208/230-1-60 1300 1300 1270 1270
060
(5.0)
UQ 208/230-1-60 1300 1300 1270 1270
Indoor Blower Specifications
Size
(Tons)
Model
Motor
HP RPM Eff. SF Frame
024
(2.0)
UM 1/2 1075 0.8 1.0 48
030
(2.5)
UM 1/2 1075 0.8 1.0 48
036
(3.0)
UM 1/2 1075 0.8 1.0 48
042
(3.5)
UM 1/2 1100 0.8 1.0 48
048
(4.0)
UM 1 1100 0.8 1.0 48
060
(5.0)
UM 1 1100 0.8 1.0 48
024
(2.0)
UQ 1/2 1100 0.8 1.0 48
030
(2.5)
UQ 1/2 1100 0.8 1.0 48
036
(3.0)
UQ 1/2 1100 0.8 1.0 48
042
(3.5)
UQ 1 1100 0.8 1.0 48
048
(4.0)
UQ 1 1100 0.8 1.0 48
060
(5.0)
UQ 1 1100 0.8 1.0 48
Electric Heat Multipliers
Voltage
kW Capacity Multipliers
1
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Nominal Applied
240
208 0.75
230 0.92