Technical Guide
505428-YTG-R-1114        
4 Johnson Controls Unitary Products
Condensing Unit Features and Benefits
Features
• Meets or exceeds ASHRAE 90.1 standards.
• Scroll compressors provide both high efficiency and 
reliability.
• Simplicity
®
 SE Controls
• Dual refrigerant circuits on PD and YD models.
• Condensing unit coils are constructed of reliable and 
durable Micro-Channel aluminum tube and fins for long 
lasting, efficient operation. Mirco-Channel technology 
provides exceptional durability along with reduced 
product weight and less refrigerant charge. Heat pumps 
units are equipped with aluminum fin, copper tube coils 
providing durability, reliability and value.
• Multiple condensing unit and air handler match-ups 
provide a wide range of application choices from 
oversized indoor motors to dual indoor units matched-
up with single outdoor units.
• Crankcase heaters that de-energize when compressors 
are operating.
• Both high and low pressure controls. Since these 
controls are self-contained, there are no capillary lines 
to be damaged.
• Internal compressor motor protection.
• Class 2, 24-volt thermostat control circuit protected by a 
re-settable breaker.
• Standard factory installed service valves.
• Filter-driers are shipped in the unit's control box for field 
installation in the liquid line leaving the outdoor unit.
• Copper stub-outs are factory mounted on the suction 
and liquid lines to simplify the field piping connections. 
• Simplicity® SE Controls provide stable cooling 
operation at ambient temperatures down to 40°F with 
low ambient kits available for operation to 0°F.
• Capacity staging for more economical operation and 
stable temperature levels within the conditioned space.
• Simplicity® SE Controls control board uses a three 
times, you're out philosophy. The high, low-pressure 
switch, anti-freeze protection, low voltage or heating 
high limit must trip three times within two hours before 
the unit control board will lock out the associated 
compressor. An alarm message will be displayed on the 
LCD screen 
• Simplicity® SE Controls monitor each safety 
independently (High pressure, low pressure, low 
voltage) allowing ease of troubleshooting if any 
problems arise.
• Inherently protected condenser fan motors.
• Technicoat or E-coat coated outdoor coils for sea coast 
or corrosive environment applications.
• Factory installed disconnect to allow power to be 
removed from the unit when performing periodic 
maintenance or for service.
• Factory installed powered or non-powered 115 volt GFI 
outlet.
• Factory installed phase monitor to protect the unit from 
phase loss or phase reversal.
Benefits
The Predator® condensing units and heat pumps can be 
applied on a rooftop or at ground level... due to their ample 
sub-cooling capacity which allows them to be located three or 
more stories below the evaporator coil.
After assembly, the unit is pressurized with a combination of 
Refrigerant R-410A and nitrogen for pressure testing and 
additional leak testing. During this pressure test, the 
operation of the high pressure control is checked. As the unit 
is being evacuated and dehydrated, the operation of the low 
pressure control is also checked.
Every compressor, condenser fan motor, crankcase heater, 
and electrical control circuit is checked to assure a trouble-
free start-up and years of reliable operation. The condenser 
fan guards are vinyl-coated to provide additional rust 
protection and to enhance the appearance of the unit. 
Compressors are mounted on rubber isolators to reduce the 
transmission of vibration. Vertical discharge condenser fans 
direct sound upward and away from any surrounding 
structures.
All sheet metal parts are constructed of commercial grade 
galvanized steel. After fabrication, each part is thoroughly 
cleaned to remove any grease or dirt from its surfaces. The 
external parts are coated with a powder paint to assure a 
quality finish for many years. This UL approved coating 
system has passed the 1000 hour, 20% salt spray test per 
ASTM Standard B117. 
All condensing unit and heat pump models include a 5-year 
limited warranty on the compressor(s) and 1-year limited 
warranty on all other parts. The matching line of air handling 
units carries a 1-year limited parts warranty.
Outdoor Unit Accessories
Coil Guards: Wire-form coil guards for added protection of 
outdoor coils. Designed to mount on each side of the product 
if required to provide protection from minor impacts or large 
debris.
Hail Guards:
 Hood type hail guards designed to protect the 
outdoor coils from hail. Can be installed on a single side or 
both to provide protection from storms that may produce hail.
Low Ambient Kits:
 Kits designed to allow the cooling only 
units to operate between 0°F and 40°F in the cooling mode. 
Standard cooling is allowed to 40°F. (Not designed for 
operation on heat pump units).
Air Handling Unit Features and Benefits
Features 
These air handlers can be arranged for a variety of air 
discharge patterns in either the horizontal or vertical position. 