Technical Guide
505428-YTG-R-1114
14 Johnson Controls Unitary Products
Air Handling Unit Limitations
Model Power Supply Voltage
Voltage Variation Supply Air Range CFM
Entering Air Temperature Degrees °F
Cooling
DB/WB
Heating DB
1
1
Heating Min/Max temperatures apply to steam and hot water coils. NOTE: Do not apply steam to hot water coils.
Min. Max. Min. Max. Min. Max. Min. Max.
NC090
208/230-3-60 187 253 2,250 3,750 65/57 90/77 40 80
460-3-60 414 506 2,250 3,750 65/57 90/77 40 80
575-3-60 540 630 2,250 3,750 65/57 90/77 40 80
NC120
208/230-3-60 187 253 3,000 5,000 65/57 90/77 40 80
460-3-60 414 506 3,000 5,000 65/57 90/77 40 80
575-3-60 540 630 3,000 5,000 65/57 90/77 40 80
ND120
208/230-3-60 187 253 3,000 5,000 65/57 90/77 40 80
460-3-60 414 506 3,000 5,000 65/57 90/77 40 80
575-3-60 540 630 3,000 5,000 65/57 90/77 40 80
NC180
208/230-3-60 187 253 4,500 7,500 65/57 90/77 40 80
460-3-60 414 506 4,500 7,500 65/57 90/77 40 80
575-3-60 540 630 4,500 7,500 65/57 90/77 40 80
ND180
208/230-3-60 187 253 4,500 7,500 65/57 90/77 40 80
460-3-60 414 506 4,500 7,500 65/57 90/77 40 80
575-3-60 540 630 4,500 7,500 65/57 90/77 40 80
NC240
208/230-3-60 187 253 6,000 10,000 65/57 90/77 40 80
460-3-60 414 506 6,000 10,000 65/57 90/77 40 80
575-3-60 540 630 6,000 10,000 65/57 90/77 40 80
ND240
208/230-3-60 187 253 6,000 10,000 65/57 90/77 40 80
460-3-60 414 506 6,000 10,000 65/57 90/77 40 80
575-3-60 540 630 6,000 10,000 65/57 90/77 40 80
NC300
208/230-3-60 187 253 8,000 12,000 65/57 90/77 40 80
460-3-60 414 506 8,000 12,000 65/57 90/77 40 80
575-3-60 540 630 8,000 12,000 65/57 90/77 40 80