Technical Guide
505428-YTG-O-0413 
70 Johnson Controls Unitary Products
Additional Static Resistance (Continued)
CFM Static Pressure and Power-Altitude and 
Temperature Corrections
The information below should be used to assist in application 
of product when being applied at altitudes at or exceeding 
1000 feet above sea level.
The air flow rates listed in the standard blower performance 
tables are based on standard air at sea level. As the altitude 
or temperature increases, the density of air decreases. In 
order to use the indoor blower tables for high altitude 
applications, certain corrections are necessary.
A centrifugal fan is a "constant volume" device. This means 
that, if the rpm remains constant, the CFM delivered is the 
same regardless of the density of the air. However, since the 
air at high altitude is less dense, less static pressure will be 
generated and less power will be required than a similar 
application at sea level. Air density correction factors are 
shown in Altitude Factors Table and Temperature Correction 
Figure.
 Model   CFM  Hot Water Coil Steam Coil
NC300
8000 0.06 0.11
9000 0.07 0.14
10000 0.08 0.17
11000 0.09 0.20
12000 0.10 0.23