505428-YTG-M-0512 ® Description TECHNICAL GUIDE R-410A SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS AND AIR HANDLERS PREDATOR® SERIES YC090-300 and YD120-240 CONDENSING UNIT MODELS PC090-180 and PD180-240 HEAT PUMP UNIT MODELS NC090-300 and ND120-240 AIR HANDLING UNIT MODELS 7.5 - 25 Ton 60 Hertz Predator® condensing units and heat pumps are completely assembled, piped and wired at the factory to provide a single-piece unit for shipment and rigging.
505428-YTG-M-0512 Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
505428-YTG-M-0512 Nomenclature Configured Split Condenser Model Number Nomenclature Y C 300 C00 A 2 A AA 2 A Product Style A = Style A Product Category Y = Split System, Condenser, AC, R-410A P = Split System, Condenser, HP, R-410A Product Generation 1 = First Generation 2 = Second Generation Product Identifier Product Options C = Standard Efficiency, 2-Pipe, R-410A D = Standard Efficiency, 4-Pipe, R-410A Nominal Cooling Capacity - MBH AA = None AB = Phase Monitor AC = Coil Guard AE = Phase Monitor
505428-YTG-M-0512 Condensing Unit Features and Benefits Benefits Features The Predator® condensing units and heat pumps can be applied on a rooftop or at ground level... due to their ample sub-cooling capacity which allows them to be located three or more stories below the evaporator coil. • Meets or exceeds ASHRAE 90.1 standards. • Scroll compressors provide both high efficiency and reliability. • Simplicity ® Controls • Dual refrigerant circuits on PD and YD models.
05428-YTG-M-0512 single packages with the blower module mounted on top of the coil module. The blower module can be repositioned in the field to meet a large number of vertical and horizontal applications. The 7.5 thru 20 Ton blower module includes the blower wheels along with factory-mounted motor and drive. The 25 Ton blower module includes the blower wheels with field mounted motor and drives. All models offer two motor horsepower options to meet both standard and high static airflow requirements.
505428-YTG-M-0512 Guide Specifications Split System Cooling Only Condensing Units Models: YC090-300, YD120-240 & Split System Heat Pump Models: PC090-240, PD180-240 General • Factory assembled, single piece, air cooled condensing unit designed for outdoor installation. • Factory wired, piped, and tested for leakage and functionality to assure trouble-free installation and startup. • Rated in accordance with AHRI Standard 340/360.
505428-YTG-M-0512 Condenser Motors • Totally enclosed, air over cooled. • Inherent overload protection. flashes a fault code that indicates which safety switch has tripped. Non-fused Disconnect Switch • Permanently lubricated bearings. • Factory-installed, internally mounted. • Must cycle to allow cooling operation down to 40°F. • Accessible from outside the unit. Refrigerant Piping • Solid core filter-drier(s) ship loose for field installation.
505428-YTG-M-0512 Each Unit Enclosure Shall Have: • Exterior panels of 18 gauge steel, finished with baked enamel to provide a long lasting quality appearance • Removable panels to provide easy access to the internal components for maintenance and service on condensing units, heat pumps and air handlers • Air handling units must have a filter rack that accepts both 2” and 4” filters. • The dimensions of each unit shall not exceed those specified in the manufacture’s literature.
505428-YTG-M-0512 Physical Data YC090 - 300 and YD120 - 240 Physical Data Component Nominal Tonnage REFRIGERANT Refrigerant type Holding charge (lb)1 (each system) System #1 Operating Charge (lb)2 System #2 DIMENSIONS (inches) Length Width Height WEIGHTS (lb) Shipping Operating COMPRESSORS Type Quantity Nominal Capacity (Tons) Capacity Stages System #1 System #2 System #1 System #2 SYSTEM DATA3 No. Refrigeration Circuits Suction Line OD (in.) Liquid Line OD (in.) OUTDOOR COIL DATA Face area (Sq. Ft.
505428-YTG-M-0512 PC090 - 240 and PD180 - 240 Physical Data PC090 7.5 PC120 10 Models PC180 15 PD180 15 PD240 20 R-410A 1.0 23.9 --- R-410A 1.0 27.5 --- R-410A 1.0 54.0 --- R-410A 1.0 27.0 27.0 R-410A 1.0 34.0 34.0 59.1 31.9 44.5 59.1 31.9 50.0 59.1 64.1 44.5 59.1 64.1 44.5 59.1 64.1 50.0 421 430 543 574 947 968 921 942 1090 1126 Single Scroll 1 Tandem Scroll 1 Tandem Scroll 1 Single Scroll 2 Single Scroll 2 System #1 System #2 System #1 System #2 7.
505428-YTG-M-0512 NC090 - 240 and ND120 - 240 Indoor Unit Physical Data NC090 7 1/2 NC120 10 ND120 10 Models NC180 15 ND180 15 NC240 20 ND240 20 Length 56.0 56.0 56.0 74.5 74.5 98.5 98.5 Width 30.0 30.0 30.0 33.0 33.0 30.0 30.0 Height 65.0 65.0 65.0 75.0 75.0 65.0 65.0 526 573 575 796 796 938 938 Standard Motor and Drive 498 539 541 764 764 873 873 High Static Motor and Drive INDOOR BLOWER (Forward Curve) Diameter x Width Quantity INDOOR COIL Face area (Sq. Ft.
505428-YTG-M-0512 NC300 Indoor Unit Physical Data Component Nominal Tonnage DIMENSIONS (inches) Models NC300 25 Length 100.1 Width 38.1 74.6 Height WEIGHTS1 (lb) Unit Shipping 1067 Unit Operating With 5 hp Motor and Drive 1130 7.5 hp Motor and Drive INDOOR BLOWER (Forward Curve) Diameter x Width Quantity INDOOR COIL Face area (Sq. Ft.) Rows Fins per inch Tube diameter Circuitry Type Refrigerant Control SYSTEM DATA No. Refrigeration Circuits Suction Line OD (in.) Liquid Line OD (in.
505428-YTG-M-0512 Unit Limitations Condenser Unit limitations Size (Tons) Model 090 (7.5) PC 090 (7.5) YC 120 (10) PC 120 (10) YC/YD 150 (12.
505428-YTG-M-0512 Air Handling Unit Limitations Entering Air Temperature Degrees °F Model NC090 NC120 ND120 NC180 ND180 NC240 ND240 NC300 1 14 Power Supply Voltage Voltage Variation Supply Air Range CFM Cooling DB/WB Heating DB1 Min. Max. Min. Max. Min. Max. Min. Max.
505428-YTG-M-0512 Cooling and Heating Ratings Cooling And Heating Rating System Cooling Capacity1 Condensing Unit Only Outdoor Unit Indoor Unit Heating Capacity1 High Outdoor Rated Airflow (CFM) KW PC0904 N/A N/A N/A NC090 92 11.0 11.4 --- 82 3.3 49 2.3 3000 PC1204 N/A N/A N/A NC120 124 11.0 11.4 11.8 109 3.3 63 2.1 4000 PC1804 N/A N/A N/A NC180 180 10.6 11.5 12.4 168 3.3 104 2.3 6000 PD1804 N/A N/A N/A ND180 180 10.6 11.5 12.0 168 3.4 103 2.
505428-YTG-M-0512 Capacity Performance Condenser and Air Handling Cooling Capacities YC090/NC090 Air on Evaporator Coil CFM 2250 2625 3000 3375 3750 2250 2625 3000 3375 3750 16 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 110.8 103.3 95.9 88.0 77.7 114.0 106.3 98.7 90.6 79.9 117.2 109.3 101.4 93.1 82.2 109.2 101.3 93.0 82.1 109.1 101.2 92.9 82.0 6.0 5.7 5.5 5.4 5.2 6.0 5.7 5.4 5.4 5.2 5.9 5.7 5.4 5.4 5.2 5.8 5.5 5.5 5.
505428-YTG-M-0512 YC090/NC090 (Continued) Air on Evaporator Coil CFM 2250 2625 3000 3375 3750 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 94.7 87.8 80.9 74.3 75.0 97.0 89.9 82.8 76.1 76.8 99.2 92.0 84.8 77.8 78.6 92.2 84.9 78.0 78.7 92.3 85.1 78.1 78.9 9.0 9.1 9.1 8.8 8.9 9.1 9.1 9.2 8.8 9.0 9.1 9.2 9.2 8.9 9.0 9.2 9.2 8.9 9.0 9.1 9.2 8.9 9.
505428-YTG-M-0512 YC090/NC120 Air on Evaporator Coil CFM 2250 2625 3000 3375 3750 2250 2625 3000 3375 3750 18 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 105.1 100.1 95.1 87.9 83.1 109.8 104.5 99.3 91.8 86.7 114.5 109.0 103.5 95.7 90.4 110.2 104.6 96.7 91.4 111.4 105.8 97.8 92.4 6.0 5.8 5.7 5.6 5.5 6.0 5.9 5.7 5.6 5.6 6.1 5.9 5.8 5.7 5.6 6.0 5.8 5.7 5.6 6.0 5.9 5.7 5.7 49.2 63.3 77.3 87.9 83.1 53.6 68.6 83.5 91.
505428-YTG-M-0512 YC090/NC120 (Continued) Air on Evaporator Coil CFM 2250 2625 3000 3375 3750 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 103.1 95.4 87.6 80.6 79.5 106.1 98.2 90.3 83.0 81.8 109.2 101.0 92.9 85.4 84.2 103.1 94.7 87.1 85.9 105.1 96.6 88.8 87.6 9.1 9.0 8.9 8.7 8.6 9.2 9.1 9.0 8.8 8.7 9.3 9.2 9.1 8.9 8.8 9.2 9.1 9.0 8.8 9.2 9.1 9.0 8.
505428-YTG-M-0512 YC120/NC120 Air on Evaporator Coil CFM 3000 3500 4000 4500 5000 3000 3500 4000 4500 5000 20 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 142.3 133.9 125.5 115.0 111.2 151.4 142.4 133.4 122.3 118.3 160.5 150.9 141.4 129.6 125.4 154.4 144.7 132.6 128.3 157.9 148.0 135.6 131.2 7.5 7.4 7.3 7.3 7.2 7.5 7.4 7.3 7.3 7.2 7.5 7.4 7.3 7.3 7.2 7.5 7.4 7.3 7.3 7.5 7.4 7.3 7.3 64.7 84.4 104.0 115.0 111.2 72.
505428-YTG-M-0512 YC120/NC120 (Continued) Air on Evaporator Coil CFM 3000 3500 4000 4500 5000 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 117.5 109.1 100.8 94.0 94.0 124.2 115.4 106.6 99.4 99.4 131.0 121.7 112.3 104.8 104.8 124.7 115.2 107.4 107.4 127.8 118.0 110.1 110.1 12.0 11.9 11.9 11.8 11.8 12.0 11.9 11.9 11.8 11.8 12.0 11.9 11.9 11.8 11.8 11.9 11.9 11.8 11.8 12.0 11.9 11.8 11.9 63.4 81.0 98.6 94.0 94.0 74.
505428-YTG-M-0512 YD120/ND120 Air on Evaporator Coil CFM 3000 3500 4000 4500 5000 3000 3500 4000 4500 5000 22 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 138.1 130.1 122.0 112.3 108.2 147.1 138.4 129.8 119.5 115.1 156.0 146.8 137.7 126.8 122.1 152.4 142.9 131.5 126.7 157.9 148.1 136.3 131.3 7.5 7.4 7.2 7.2 7.1 7.5 7.4 7.3 7.2 7.2 7.6 7.4 7.3 7.2 7.2 7.5 7.3 7.2 7.2 7.5 7.4 7.3 7.3 63.6 82.9 102.2 112.3 108.2 70.
505428-YTG-M-0512 YD120/ND120 (Continued) Air on Evaporator Coil CFM 3000 3500 4000 4500 5000 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 116.8 106.7 96.6 89.7 93.0 122.7 112.1 101.4 94.2 97.7 128.6 117.4 106.3 98.8 102.3 122.9 111.2 103.3 107.1 128.3 116.1 107.9 111.8 12.1 11.9 11.8 11.7 11.7 12.1 11.9 11.8 11.7 11.7 12.1 11.9 11.8 11.7 11.7 12.0 11.8 11.7 11.7 12.0 11.9 11.7 11.8 58.7 75.9 93.2 89.7 93.0 71.
505428-YTG-M-0512 YC150/NC180 Air on Evaporator Coil CFM 3750 4375 5000 5625 6250 3750 4375 5000 5625 6250 24 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 178.5 168.2 157.9 144.8 149.7 184.7 174.0 163.4 149.9 154.9 190.9 179.9 168.8 154.9 160.1 182.3 171.1 157.0 162.2 184.7 173.4 159.0 164.4 10.2 9.9 9.6 9.4 9.5 10.2 9.9 9.6 9.4 9.5 10.3 9.9 9.6 9.4 9.6 10.1 9.8 9.6 9.7 10.2 9.9 9.7 9.8 87.6 111.9 136.1 144.8 149.
505428-YTG-M-0512 YC150/NC180 (Continued) Air on Evaporator Coil CFM 3750 4375 5000 5625 6250 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 153.8 142.2 130.5 128.2 131.2 155.5 143.8 132.0 129.7 132.7 157.3 145.4 133.5 131.1 134.2 149.5 137.3 134.8 138.0 153.6 141.0 138.5 141.8 15.8 15.5 15.1 15.1 15.2 15.7 15.3 15.0 15.0 15.1 15.5 15.2 14.9 14.9 15.0 15.4 15.1 15.1 15.2 15.6 15.3 15.3 15.4 77.6 101.0 124.4 128.
505428-YTG-M-0512 YD150/ND180 Air on Evaporator Coil CFM 3750 4375 5000 5625 6250 3750 4375 5000 5625 6250 26 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 170.2 164.1 157.9 142.4 141.3 182.4 175.5 168.7 152.3 151.2 194.5 187.0 179.5 162.2 161.1 187.6 180.3 162.8 161.6 188.2 181.0 163.3 162.1 10.0 9.7 9.5 9.3 9.3 10.0 9.7 9.5 9.4 9.3 10.0 9.8 9.5 9.4 9.4 9.8 9.6 9.5 9.4 9.9 9.7 9.5 9.5 80.1 106.1 132.0 142.4 141.
505428-YTG-M-0512 YD150/ND180 (Continued) Air on Evaporator Coil CFM 3750 4375 5000 5625 6250 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 148.6 138.6 128.6 119.7 123.4 155.4 145.0 134.5 125.3 129.1 162.3 151.3 140.4 130.8 134.8 154.3 143.2 133.4 137.4 157.3 146.0 136.0 140.1 15.3 15.1 14.8 14.5 14.7 15.4 15.1 14.8 14.5 14.7 15.4 15.1 14.8 14.5 14.7 15.2 14.9 14.6 14.8 15.3 15.0 14.7 14.9 73.8 97.6 121.5 119.
505428-YTG-M-0512 YC180/NC180 Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 28 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 223.5 207.2 191.0 176.0 175.0 229.4 212.8 196.1 180.7 179.7 235.4 218.3 201.2 185.4 184.4 221.3 204.0 187.9 186.8 224.2 206.7 190.4 189.3 11.8 11.5 11.1 10.8 10.8 11.9 11.6 11.2 11.0 10.9 12.0 11.7 11.3 11.1 11.0 11.3 11.0 10.7 10.6 10.9 10.6 10.3 10.3 104.
505428-YTG-M-0512 YC180/NC180 (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 185.3 170.5 155.8 145.5 147.3 189.1 174.1 159.0 148.5 150.4 192.9 177.6 162.2 151.5 153.4 179.0 163.5 152.7 154.7 180.4 164.8 153.9 155.9 17.5 17.3 17.1 16.9 16.8 17.6 17.4 17.2 17.0 16.9 17.7 17.5 17.3 17.0 17.0 17.5 17.3 17.0 17.0 17.5 17.3 17.0 17.0 92.7 119.4 146.1 145.
505428-YTG-M-0512 YC180/NC240 Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 30 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 214.3 201.7 189.0 181.2 177.1 220.7 207.6 194.6 186.5 182.3 227.1 213.6 200.2 191.9 187.6 218.3 204.5 196.0 191.6 223.0 208.9 200.2 195.7 12.1 11.8 11.6 11.3 11.3 12.2 11.9 11.7 11.4 11.4 12.3 12.0 11.8 11.5 11.5 12.1 11.9 11.6 11.6 12.2 11.9 11.7 11.6 111.
505428-YTG-M-0512 YC180/NC240 (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 203.2 187.4 171.6 153.7 157.8 208.6 192.4 176.2 157.8 162.0 214.1 197.4 180.8 162.0 166.3 200.5 183.6 164.5 168.8 203.6 186.4 167.0 171.4 18.8 18.3 17.7 17.2 17.1 19.0 18.4 17.8 17.3 17.2 19.1 18.5 17.9 17.4 17.3 18.5 17.9 17.4 17.3 18.5 17.9 17.4 17.3 106.1 131.7 157.3 153.
505428-YTG-M-0512 YD180 / Two NC090 Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 32 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 216.0 200.4 184.8 173.1 165.6 222.3 206.2 190.2 178.1 170.4 228.6 212.1 195.6 183.2 175.2 216.4 199.6 186.9 178.8 220.7 203.5 190.6 182.4 12.0 11.7 11.4 11.2 11.1 12.1 11.8 11.5 11.2 11.2 12.1 11.9 11.6 11.3 11.3 11.9 11.6 11.4 11.3 12.0 11.7 11.4 11.
505428-YTG-M-0512 YD180 / Two NC090 (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 193.0 179.5 166.0 154.6 151.8 198.9 185.0 171.0 159.2 156.4 204.7 190.4 176.1 163.9 161.0 192.4 177.9 165.6 162.6 194.3 179.7 167.3 164.3 17.7 17.4 17.1 16.8 16.8 17.8 17.5 17.2 16.9 16.9 17.9 17.6 17.2 17.0 17.0 17.6 17.3 17.1 17.0 17.7 17.4 17.1 17.1 96.7 121.8 146.
505428-YTG-M-0512 YD180 / Two NC120 Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 6000 7000 8000 9000 10000 34 Temperature of Air on Condenser Coil Sensible Capacity (MBh)1 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 241.0 222.0 203.0 191.6 189.3 247.3 227.8 208.3 196.6 194.3 253.6 233.6 213.6 201.6 199.3 238.5 218.1 205.8 203.4 243.3 222.5 210.0 207.6 12.0 11.7 11.4 11.2 11.2 12.1 11.8 11.5 11.2 11.3 12.
505428-YTG-M-0512 YD180 / Two NC120 (Continued) Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 1 2 Temperature of Air on Condenser Coil Sensible Capacity (MBh)1 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 226.4 210.6 194.9 185.6 185.6 228.3 212.4 196.5 187.1 187.1 230.2 214.2 198.2 188.7 188.7 216.2 200.1 190.5 190.5 218.3 202.0 192.3 192.3 15.9 15.6 15.3 15.0 15.0 17.1 16.8 16.5 16.2 16.2 18.3 18.0 17.7 17.
505428-YTG-M-0512 YD180/ND180 Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 36 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 208.6 198.3 188.0 170.5 177.8 217.2 206.4 195.7 177.6 185.1 225.8 214.6 203.4 184.6 192.4 214.6 203.4 184.6 192.4 214.6 203.5 184.6 192.5 11.7 11.4 11.0 10.9 11.0 11.7 11.4 11.1 10.9 11.0 11.8 11.4 11.1 11.0 11.1 11.5 11.2 11.1 11.1 11.6 11.3 11.1 11.2 106.
505428-YTG-M-0512 YD180/ND180 (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 175.1 163.9 152.8 144.6 146.8 181.4 169.9 158.3 149.8 152.1 187.8 175.8 163.9 155.1 157.5 174.6 162.8 154.0 156.4 173.5 161.7 153.0 155.4 17.7 17.4 17.2 17.1 17.0 17.7 17.5 17.2 17.1 17.0 17.8 17.5 17.3 17.2 17.1 17.6 17.3 17.2 17.1 17.6 17.3 17.2 17.1 89.8 117.8 145.9 144.6 146.
505428-YTG-M-0512 YD180/ND240 Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 38 Temperature of Air on Condenser Coil Sensible Capacity (MBh)1 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 213.8 201.0 188.1 171.4 175.2 220.6 207.3 194.1 176.8 180.7 227.3 213.6 200.0 182.2 186.3 217.5 203.6 185.5 189.6 221.4 207.3 188.8 193.0 12.1 11.8 11.5 11.3 11.3 12.2 11.9 11.6 11.4 11.4 12.3 12.
505428-YTG-M-0512 YD180/ND240 (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 1 2 Temperature of Air on Condenser Coil Sensible Capacity (MBh)1 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 200.6 186.0 171.4 153.0 156.4 207.4 192.3 177.2 158.2 161.8 214.3 198.7 183.1 163.5 167.1 200.5 184.7 164.9 168.6 202.3 186.4 166.4 170.1 18.3 17.8 17.4 16.9 16.9 18.4 18.0 17.5 17.0 17.0 18.6 18.1 17.6 17.1 17.
505428-YTG-M-0512 YC240/NC240 Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 6000 7000 8000 9000 10000 40 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 286.3 267.4 248.5 228.9 227.5 296.6 277.0 257.5 237.1 235.7 306.9 286.6 266.4 245.4 243.8 296.2 275.2 253.5 251.9 305.7 284.0 261.7 260.0 15.3 14.8 14.4 14.1 14.0 15.4 14.9 14.5 14.2 14.1 15.5 15.0 14.6 14.3 14.2 15.1 14.7 14.4 14.3 15.2 14.8 14.5 14.4 136.
505428-YTG-M-0512 YC240/NC240 (Continued) Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 244.4 226.2 208.0 192.2 194.4 250.0 231.4 212.8 196.7 198.9 255.7 236.6 217.6 201.1 203.3 241.9 222.4 205.6 207.9 247.2 227.3 210.0 212.4 23.4 22.8 22.1 21.6 21.8 23.5 22.8 22.1 21.7 21.8 23.5 22.8 22.2 21.7 21.8 23.0 22.3 21.9 22.0 23.2 22.5 22.0 22.2 120.7 156.5 192.4 192.
505428-YTG-M-0512 YD240 / Two NC120 Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 6000 7000 8000 9000 10000 42 Temperature of Air on Condenser Coil Sensible Capacity (MBh)1 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 268.6 253.5 238.3 214.5 213.5 280.9 265.0 249.1 224.2 223.1 293.1 276.4 259.8 234.0 232.8 278.2 261.5 235.5 234.3 280.0 263.2 236.9 235.7 15.0 14.6 14.2 13.9 13.9 15.1 14.7 14.3 14.0 14.0 15.
505428-YTG-M-0512 YD240 / Two NC120 (Continued) Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 1 2 Temperature of Air on Condenser Coil Sensible Capacity (MBh)1 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 193.7 205.5 217.3 200.0 183.4 208.6 221.4 234.1 215.5 197.5 223.6 237.2 250.9 230.9 211.7 246.6 260.8 240.1 220.1 256.0 270.8 249.2 228.5 16.1 19.1 22.1 21.7 21.4 16.3 19.3 22.3 22.0 21.7 16.5 19.6 22.6 22.
505428-YTG-M-0512 YD240/ND240 Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 6000 7000 8000 9000 10000 44 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 292.8 272.9 253.0 231.8 224.6 302.2 281.7 261.1 239.3 231.8 311.7 290.5 269.3 246.8 239.1 299.4 277.5 254.3 246.4 308.2 285.7 261.9 253.7 14.7 14.4 14.0 13.8 13.7 14.8 14.5 14.2 13.9 13.9 14.9 14.6 14.3 14.0 14.0 14.9 14.6 14.3 14.2 15.2 14.8 14.6 14.5 136.
505428-YTG-M-0512 YD240/ND240 (Continued) Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 249.8 229.9 210.1 198.2 196.0 255.8 235.5 215.2 203.0 200.8 261.9 241.1 220.3 207.8 205.5 246.6 225.3 212.6 210.3 252.2 230.4 217.4 215.0 22.6 22.3 22.0 21.9 21.9 22.7 22.4 22.1 22.0 22.0 22.8 22.5 22.2 22.1 22.1 22.7 22.4 22.3 22.3 23.0 22.7 22.5 22.5 126.1 160.6 195.1 198.
505428-YTG-M-0512 YC300/NC300 Air on Evaporator Coil CFM 7500 8750 10000 11250 12500 7500 8750 10000 11250 12500 46 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 390.0 360.6 331.2 305.3 308.5 399.4 369.3 339.2 312.8 316.1 408.8 378.0 347.2 320.3 323.7 390.1 358.3 330.5 334.0 402.1 369.4 340.7 344.3 20.3 19.9 19.5 18.6 18.5 20.7 20.4 20.0 19.0 18.9 21.2 20.8 20.4 19.4 19.3 20.5 20.2 19.2 19.1 20.3 19.9 18.9 18.
505428-YTG-M-0512 YC300/NC300 (Continued) Air on Evaporator Coil CFM 7500 8750 10000 11250 12500 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 317.1 288.5 259.8 246.4 258.8 318.9 290.1 261.3 247.8 260.2 320.7 291.7 262.7 249.2 261.7 302.2 272.2 258.2 271.1 312.8 281.7 267.2 280.6 31.5 30.8 30.2 29.7 29.6 31.6 31.0 30.4 29.9 29.7 31.8 31.2 30.5 30.0 29.9 31.2 30.5 30.0 29.9 31.2 30.6 30.0 29.9 143.2 194.6 246.1 246.
505428-YTG-M-0512 Condenser Only Cooling Capacities Condenser Only Ratings Suction Press. Temperature of Air on Condenser Coil °F and Model 65 75 85 95 105 115 Corresponding Temp.
505428-YTG-M-0512 Heat Pump and Air Handling Cooling Capacities PC090/NC090 Cooling Capacities Air on Evaporator Coil CFM 2250 2625 3000 3375 3750 2250 2625 3000 3375 3750 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 112.8 104.8 96.7 89.0 88.9 117.0 108.6 100.3 92.3 92.2 121.1 112.5 103.8 95.6 95.4 114.6 105.7 97.4 97.2 116.6 107.7 99.1 99.0 5.9 5.8 5.7 5.5 5.6 5.9 5.8 5.7 5.6 5.6 5.9 5.8 5.7 5.6 5.6 5.8 5.7 5.6 5.
5428-YTG-M-0512 PC090/NC090 Cooling Capacities (Continued) Air on Evaporator Coil CFM 2250 2625 3000 3375 3750 1 2 50 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 99.8 86.5 73.1 69.9 69.5 103.0 89.2 75.5 72.1 71.7 106.2 92.0 77.8 74.4 73.9 94.8 80.2 76.7 76.2 97.7 82.6 79.0 78.5 8.8 8.7 8.7 8.5 8.5 8.8 8.8 8.7 8.6 8.6 8.9 8.8 8.7 8.6 8.6 8.8 8.8 8.6 8.6 8.8 8.8 8.7 8.6 69.7 71.4 73.1 69.9 69.5 82.4 78.9 75.5 72.
505428-YTG-M-0512 PC120/NC120 Air on Evaporator Coil CFM 3000 3500 4000 4500 5000 3000 3500 4000 4500 5000 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 140.5 133.6 126.6 120.2 121.8 147.3 140.0 132.8 126.0 127.7 154.1 146.5 138.9 131.8 133.6 148.2 140.5 133.4 135.2 150.0 142.2 134.9 136.7 7.5 7.5 7.4 7.4 7.3 7.7 7.6 7.6 7.6 7.5 7.8 7.8 7.8 7.8 7.6 7.7 7.7 7.7 7.5 7.6 7.5 7.5 7.4 70.2 87.5 104.8 120.2 121.8 74.8 93.
505428-YTG-M-0512 PC120/NC120 (Continued) Air on Evaporator Coil CFM 3000 3500 4000 4500 5000 1 2 52 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 113.3 105.2 97.2 95.9 97.1 118.7 110.2 101.8 100.4 101.8 124.1 115.3 106.4 105.0 106.4 116.3 107.3 105.9 107.3 117.2 108.3 106.8 108.2 12.1 12.0 11.9 11.8 11.8 12.2 12.1 12.0 11.9 12.0 12.3 12.2 12.1 12.1 12.1 12.1 12.0 12.0 12.0 12.1 12.0 11.9 11.9 58.5 77.8 97.2 95.9 97.
505428-YTG-M-0512 PC180/NC180 Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 223.0 209.3 195.7 176.7 179.6 229.0 215.0 200.9 181.4 184.5 235.0 220.6 206.2 186.2 189.3 223.2 208.6 188.4 191.6 225.9 211.1 190.6 193.8 12.5 12.3 12.1 11.8 11.8 12.6 12.4 12.2 11.8 11.9 12.6 12.4 12.2 11.9 11.9 12.5 12.3 11.9 12.0 12.6 12.4 12.0 12.1 104.1 134.
505428-YTG-M-0512 PC180/NC180 (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 1 2 54 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 175.1 162.0 148.8 138.1 143.6 179.2 165.7 152.3 141.3 146.9 183.2 169.5 155.8 144.5 150.2 171.9 158.0 146.6 152.4 174.3 160.2 148.6 154.5 18.3 18.1 18.0 17.8 17.8 18.3 18.1 18.0 17.8 17.8 18.3 18.1 18.0 17.8 17.9 18.2 18.0 17.8 17.9 18.2 18.1 17.9 18.0 92.4 120.0 147.6 138.
505428-YTG-M-0512 PD180/ND180 Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 231.4 215.6 199.7 183.7 184.6 233.6 217.6 201.6 185.5 186.3 235.8 219.7 203.5 187.2 188.0 222.5 206.2 189.7 190.5 225.4 208.9 192.1 193.0 12.4 12.0 11.7 11.4 11.4 12.4 12.1 11.7 11.4 11.4 12.4 12.1 11.7 11.4 11.4 12.1 11.8 11.5 11.5 12.2 11.8 11.5 11.5 111.6 142.
505428-YTG-M-0512 PD180/ND180 (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 1 2 56 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 175.7 162.2 148.6 141.5 144.4 177.4 163.7 150.0 142.9 145.8 179.0 165.2 151.4 144.2 147.1 167.3 153.3 146.0 149.0 169.4 155.3 147.9 150.9 18.9 18.6 18.2 18.1 18.1 18.9 18.6 18.3 18.1 18.1 18.9 18.6 18.3 18.1 18.2 18.7 18.3 18.1 18.2 18.7 18.4 18.2 18.3 91.5 123.9 148.6 141.
505428-YTG-M-0512 PD240/ND240 Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 6000 7000 8000 9000 10000 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 314.8 285.9 257.1 239.1 239.5 321.1 291.7 262.3 243.9 244.3 327.5 297.5 267.5 248.8 249.2 303.3 272.7 253.6 254.0 309.0 277.8 258.4 258.8 15.1 14.8 14.5 14.2 14.3 15.2 14.9 14.6 14.3 14.5 15.3 15.0 14.8 14.4 14.6 15.2 14.9 14.6 14.7 15.4 15.1 14.7 14.9 142.6 177.
505428-YTG-M-0512 PD240/ND240 (Continued) Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 1 2 58 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 244.4 222.6 200.8 190.4 198.8 248.3 226.1 204.0 193.4 201.9 252.1 229.6 207.1 196.4 205.1 233.2 210.3 199.4 208.3 236.7 213.5 202.5 211.4 23.6 23.2 22.8 22.5 22.8 23.6 23.2 22.9 22.6 22.8 23.7 23.3 22.9 22.6 22.9 23.5 23.2 22.8 23.1 23.8 23.4 23.1 23.4 120.7 155.5 190.
505428-YTG-M-0512 Heat Pump And Air Handler Heating Capacities PC090 / NC090 Air Over Evaporator Coil CFM DB (°F) 55 2250 70 80 55 3000 70 80 55 3750 70 80 1 Capacity1 & kW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW Outdoor Temperature (°F @ 72% RH) -10 34.0 4.9 31.0 5.8 28.7 6.4 35.3 4.7 32.4 5.6 30.1 6.2 36.6 5.2 33.7 6.1 31.4 6.7 0 39.6 5.3 36.6 6.1 34.3 6.8 40.9 5.1 38.0 5.9 35.7 6.5 42.2 5.6 39.3 6.4 37.0 7.0 10 46.2 5.6 43.2 6.5 40.9 7.1 47.5 5.4 44.5 6.3 42.3 6.9 48.
505428-YTG-M-0512 PC180 / NC180 Air Over Evaporator Coil CFM DB (°F) 55 4500 70 80 55 6000 70 80 55 7500 70 80 1 Capacity1 & kW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW Outdoor Temperature (°F @ 72% RH) -10 68.2 11.8 61.5 13.5 57.6 15.0 74.0 11.2 67.3 12.9 63.4 14.5 72.4 12.0 65.6 13.7 61.7 15.3 0 80.0 12.2 73.2 14.0 69.3 15.5 85.8 11.7 79.0 13.4 75.1 14.9 84.1 12.5 77.3 14.2 73.4 15.7 10 93.8 12.7 87.0 14.4 83.1 16.0 99.6 12.2 92.8 13.9 88.9 15.4 97.9 13.0 91.1 14.7 87.
505428-YTG-M-0512 PD240 / ND240 Air Over Evaporator Coil CFM DB (°F) 55 6000 70 80 55 8000 70 80 55 10000 70 80 1 Capacity1 & kW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW Outdoor Temperature (°F @ 72% RH) -10 64.6 15.7 69.5 15.4 63.3 17.2 71.6 15.1 76.5 14.8 70.4 16.6 73.3 15.3 78.2 15.0 72.1 16.8 0 79.5 16.5 84.4 16.2 78.3 18.0 86.6 15.9 91.5 15.6 85.3 17.4 88.3 16.1 93.2 15.8 87.0 17.6 10 97.4 17.3 102.3 17.0 96.2 18.8 104.5 16.8 109.4 16.5 103.2 18.3 106.1 17.0 111.0 16.
505428-YTG-M-0512 Air Handling and Hot Water Coil Accessory Heating Capacity NC300 / 1HW04061 CAPACITY (MBH) UNIT MODEL HOT WATER COIL MODEL NC300 GPM 1HW0406 CFM ENTERING WATER TEMPERATURE MINUS ENTRY AIR TEMPERATURE °F. 70 90 110 130 150 6,000 204 263 325 384 443 8,000 236 304 372 440 508 10,000 265 341 416 492 568 12,000 291 374 457 540 623 50 1 These capacities do not include any blower motor heat. NOTE: Temperature Water Drop (ºF) = (2 X MBH) / GPM.
505428-YTG-M-0512 Airflow Performance NC090 Upflow and Horizontal Airflow Performance NC090 Upflow (CFM) Available External Static Pressure - IWG 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Std. 1.5 HP & Field Supplied Drive 2250 2500 2750 3000 3250 3500 3750 705 741 780 823 1.0 1.1 1.4 1.6 707 735 767 802 842 884 Standard 1.5 HP & Drive 0.8 0.9 1.1 1.3 1.5 1.7 754 777 805 837 872 912 954 0.8 0.9 1.1 1.2 1.4 1.6 1.
505428-YTG-M-0512 NC/ND120 Upflow and Horizontal Airflow Performance NC/ND120 Upflow (CFM) Available External Static Pressure - IWG 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Std. 2 HP & Field Supplied Drive 2500 2750 3000 3250 3500 3750 4000 4250 4500 4750 5000 653 679 707 737 768 801 1.1 1.3 1.5 1.7 1.9 2.1 664 685 709 735 762 792 824 856 Standard 2 HP & Drive 1.0 1.1 1.3 1.5 1.6 1.9 2.1 2.
505428-YTG-M-0512 NC/ND180 Upflow and Horizontal Airflow Performance NC/ND180 Upflow (CFM) 4500 4750 5000 5250 5500 5750 6000 6250 6500 6750 7000 7250 7500 0.2 RPM BHP 0.4 RPM BHP 0.6 RPM BHP Std. 3 HP & Field Supplied Drive 583 592 602 613 577 1.1 625 590 1.2 638 603 1.3 651 617 1.5 664 587 1.4 631 1.6 679 601 1.6 645 1.8 693 616 1.8 660 2.0 710 632 2.1 675 2.3 725 647 2.3 691 2.5 740 1.1 1.2 1.2 1.3 1.4 1.4 1.6 1.7 1.8 2.0 2.9 3.2 3.5 Available External Static Pressure - IWG 0.8 1.0 1.
505428-YTG-M-0512 NC/ND240 Upflow and Horizontal Airflow Performance NC/ND240 Upflow (CFM) Available External Static Pressure - IWG 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Std. 5 HP & Field Supplied Drive 6000 6250 6500 6750 7000 7250 7500 7750 8000 8250 8500 8750 9000 9250 9500 9750 10000 700 712 726 740 754 768 783 799 815 831 2.6 2.8 3.0 3.2 3.4 3.6 3.9 4.1 4.4 4.
505428-YTG-M-0512 NC300 Airflow Performance1 Avaiable External Static Pressure - IWG CFM 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Motor & Drive 7500 7.5 HP Motor & Drive 600 2.04 648 2.50 694 3.00 738 3.54 781 4.08 823 4.63 863 5.16 903 5.66 942 6.10 981 6.49 603 2.17 652 2.63 698 3.13 742 3.67 785 4.22 827 4.76 867 5.29 907 5.79 946 6.24 984 6.62 608 2.
505428-YTG-M-0512 NC300 Drive Kit Data Unit Model Drive Kit Model Number NC300 1LD0440 1LD0407 1LD0442 Sheave Model Number 2VP56 2VP60 2VP71 Adjustable Motor Sheave Blower Pitch RPM Diameter Range (in.) 575 - 719 4.0 - 5.0 659 - 815 4.2 - 5.2 762 - 906 5.3 - 6.3 Bore (in.) 1 1/8 1 3/8 1 3/8 Fixed Blower Sheave Sheave Pitch Bore Model Diameter (in.) Number (in.) 2AK124 12.0 1 3/16 2AK114 11.0 1 3/16 2AK124 12.0 1 3/16 Qty. 2 2 2 Belts Pitch Length (in.) 63.3 63.3 63.
505428-YTG-M-0512 Additional Static Resistance CFM Wet Indoor1 Coil 2” Filters Bottom Return 2250 2500 2750 3000 3250 3500 3750 3000 3250 3500 3750 4000 4250 4500 4750 5000 4500 4750 5000 5250 5500 5750 6000 6250 6500 6750 7000 7250 7500 0.03 0.03 0.02 0.02 0.01 0.00 0.00 0.08 0.07 0.07 0.06 0.05 0.04 0.03 0.02 0.00 0.07 0.06 0.06 0.06 0.05 0.05 0.05 0.04 0.03 0.03 0.02 0.01 0.00 0.10 0.11 0.11 0.12 0.13 0.14 0.15 0.12 0.13 0.14 0.15 0.16 0.18 0.19 0.21 0.23 0.11 0.11 0.11 0.12 0.12 0.12 0.13 0.14 0.
505428-YTG-M-0512 Additional Static Resistance (Continued) Model NC300 CFM 8000 9000 10000 11000 12000 Hot Water Coil 0.06 0.07 0.08 0.09 0.10 Steam Coil 0.11 0.14 0.17 0.20 0.23 CFM Static Pressure and Power-Altitude and Temperature Corrections order to use the indoor blower tables for high altitude applications, certain corrections are necessary. The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level.
505428-YTG-M-0512 Altitude/Temperature Correction Factors Table Air Temp. 40 50 60 70 80 90 100 0 1.060 1.039 1.019 1.000 0.982 0.964 0.946 1000 1.022 1.002 0.982 0.964 0.947 0.929 0.912 2000 0.986 0.966 0.948 0.930 0.913 0.897 0.880 3000 0.950 0.931 0.913 0.896 0.880 0.864 0.848 4000 0.916 0.898 0.880 0.864 0.848 0.833 0.817 Altitude (Ft.) 5000 0.882 0.864 0.848 0.832 0.817 0.802 0.787 6000 0.849 0.832 0.816 0.801 0.787 0.772 0.758 7000 0.818 0.802 0.787 0.772 0.758 0.744 0.730 8000 0.788 0.
505428-YTG-M-0512 Drive Selection 1. Determine Upflow or Horizontal supply duct Application. 2. Determine desired airflow. 3. Calculate or measure the amount of external static pressure. 4. Using the operating point, determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table. (Linear interpolation may be necessary.) 5. Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table. 6.
505428-YTG-M-0512 Sound Performance Outdoor Sound Power Levels (dB), 60 Hz Size (Tons) 090 (7.5) 120 (10.0) 150 (12.5) 180 (15.0) 240 (20.0) 300 (25.
505428-YTG-M-0512 Electrical Data Electrical Data For Outdoor Models Electrical Data - Outdoor Unit - AC Without Powered Convenience Outlet Compressors Model YC090 YC120 YD120 YC150 YD150 YC180 YD180 YC240 YD240 YC300 1 2 74 Outdoor Fan Motor Pwr Conv Outlet Qty FLA (each) FLA Minimum Circuit Ampacity1 Maximum Fuse Size (A)2 1/3 2 2.1 - 35.5 45 1/3 2 1.2 - 17.6 25 575-1-60 1/3 2 0.9 - 13.1 20 137 208/230-1-60 3/4 2 3.0 - 46.8 60 14.0 62 460-1-60 3/4 2 1.
505428-YTG-M-0512 Electrical Data - Outdoor Unit - AC With Powered Convenience Outlet Compressors Model YC090 YC120 YD120 YC150 YD150 YC180 YD180 YC240 YD240 YC300 1 2 Outdoor Fan Motor Pwr Conv Outlet Qty FLA (each) FLA Minimum Circuit Ampacity1 Maximum Fuse Size (A)2 1/3 2 2.1 10.0 45.5 60 1/3 2 1.2 5.0 22.6 30 575-1-60 1/3 2 0.9 4.0 17.1 25 137 208/230-1-60 3/4 2 3.0 10.0 56.8 70 14.0 62 460-1-60 3/4 2 1.6 5.0 28.5 35 10.6 50 575-1-60 3/4 2 1.
505428-YTG-M-0512 Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet Compressors Model PC090 PC120 PC180 PD180 PD240 1 2 Outdoor Fan Motor Pwr Conv Outlet Qty FLA (each) FLA Minimum Circuit Ampacity1 Maximum Fuse Size (A)2 1/3 2 2.1 - 35.5 45 1/3 2 1.2 - 17.6 25 575-1-60 1/3 2 0.9 - 13.1 20 137 208/230-1-60 3/4 2 3.0 - 46.8 60 14.0 62 460-1-60 3/4 2 1.6 - 23.5 30 10.6 50 575-1-60 3/4 2 1.4 - 18.0 20 25.
505428-YTG-M-0512 Electrical Data For Indoor Models Electrical Data - Indoor Units Motor HP Power Supply Supply Blower Motor FLA 208-3-60 5.0 230-3-60 5.2 460-3-60 2.5 575-3-60 2.0 1.5 208-3-60 6.6 230-3-60 6.8 460-3-60 3.4 575-3-60 2.4 2.0 Johnson Controls Unitary Products MCA1 (Amps) Max Fuse2/ Breaker3 Size (Amps) --20.8 33.4 54.2 75.1 --24.1 38.5 62.5 86.6 --12.0 19.2 31.3 43.3 --9.6 15.4 25.0 34.6 6.3 32.3 47.9 74.0 100.1 6.5 36.6 54.6 84.7 114.8 3.1 18.2 27.2 42.2 57.3 2.
505428-YTG-M-0512 Electrical Data - Indoor Units (Continued) Motor HP Power Supply 208-3-60 230-3-60 3.0 460-3-60 575-3-60 208-3-60 230-3-60 5.0 460-3-60 575-3-60 78 Supply Blower Motor FLA MCA1 (Amps) Max Fuse2/ Breaker3 Size (Amps) --20.8 33.4 54.2 75.1 104.2 --24.1 38.5 62.5 86.6 120.3 --12.0 19.2 31.3 43.3 60.1 --9.6 15.4 25.0 34.6 48.1 12.0 38.1 53.7 79.8 105.8 116.2 11.8 41.8 59.9 89.9 120.0 132.0 5.9 20.9 29.9 45.0 60.0 66.0 4.5 16.5 23.7 35.8 47.8 52.
505428-YTG-M-0512 Electrical Data - Indoor Units (Continued) Motor HP Power Supply Supply Blower Motor FLA 208-3-60 14.0 230-3-60 13.2 460-3-60 6.6 575-3-60 5.2 208-3-60 230-3-60 460-3-60 575-3-60 16.7 15.2 7.6 6.1 5.0 5.0 208-3-60 20.4 230-3-60 19.4 460-3-60 9.7 575-3-60 7.8 208-3-60 230-3-60 460-3-60 575-3-60 24.2 22.0 11.0 9.0 7.5 7.5 1 2 3 4 5 Electric Heat Option Model KW (NC/ND)240C00E None --20 KW 15 32 KW 24 52 KW 39.
505428-YTG-M-0512 Typical Wiring Diagrams Air Conditioning Condensing Units Typical YC090 Wiring Diagram 80 Johnson Controls Unitary Products
505428-YTG-M-0512 Typical YC120 - 150 Wiring Diagram Johnson Controls Unitary Products 81
505428-YTG-M-0512 Typical YD120 - 150 Wiring Diagram 82 Johnson Controls Unitary Products
505428-YTG-M-0512 Typical YC180 Wiring Diagram Johnson Controls Unitary Products 83
505428-YTG-M-0512 Typical YC240 Wiring Diagram 84 Johnson Controls Unitary Products
505428-YTG-M-0512 Typical YC300 Wiring Diagram Johnson Controls Unitary Products 85
505428-YTG-M-0512 Typical YD180 - 240 Wiring Diagram 86 Johnson Controls Unitary Products
505428-YTG-M-0512 Heat Pump Units Typical PC090 Wiring Diagram Johnson Controls Unitary Products 87
505428-YTG-M-0512 Typical PC120 Wiring Diagram 88 Johnson Controls Unitary Products
505428-YTG-M-0512 Typical PC180 - 240 Wiring Diagram Johnson Controls Unitary Products 89
505428-YTG-M-0512 Typical PD180 - 240 Wiring Diagram 90 Johnson Controls Unitary Products
505428-YTG-M-0512 Air Handling Units Typical NC090 Wiring Diagram Johnson Controls Unitary Products 91
505428-YTG-M-0512 Typical NC120 thru 240, 1.
505428-YTG-M-0512 Typical NC 240, 7.
505428-YTG-M-0512 Typical NC 240, 7.
505428-YTG-M-0512 Typical NC300 Indoor Unit Wiring Diagram Johnson Controls Unitary Products 95
505428-YTG-M-0512 Typical ND120 thru 240, 1.
505428-YTG-M-0512 Typical ND 240, 7.
505428-YTG-M-0512 Typical ND 240, 7.
505428-YTG-M-0512 Weights And Dimensions Corner Weights & Center of Gravity AC/HP Units Weight (lbs.) Shipping Operating 421 430 543 574 947 968 921 942 1090 1126 390 387 499 497 493 490 499 497 493 490 914 909 899 894 945 942 930 927 945 942 Model PC090 PC120 PC180 PD180 PD240 YC090 YC120 YD120 YC150 YD150 YC180 YD180 YC240 YD240 YC300 Center of Gravity (in.) X Y 17.3 33 16.4 32.3 32.5 33 34 32.5 31.2 31.8 17 32.3 17.3 32.3 17.4 32.5 17 32.3 17.4 32.5 32.5 31.5 32.5 31.5 30.3 31.0 32.7 31.8 30.3 31.
505428-YTG-M-0512 RIGHT REAR FRONT LEFT CONVENIENCE OUTLET A 30.994 2X (Ø 1.375) KNOCKOUT 2X (Ø 0.875) KNOCKOUT 12.126 9.876 4.751 10.000 7.000 3.883 7.000 3.664 24.000 2.933 31.758 1.664 7.000 23.000 7.000 37.000 58.500 FRONT RIGHT SYSTEM 2 2X (Ø 0.875) KNOCKOUT 2X (Ø 1.375) KNOCKOUT 15.53 12.70 10.000 SYSTEM 1 12.000 4.875 6.26 7.52 8.98 REAR 10.60 4.132 2.382 LEFT 1.
505428-YTG-M-0512 REAR RIGHT LEFT FRONT A SYSTEM 2 SYSTEM 1 2X (Ø 1.375) KNOCKOUT 30.994 11.375 2X (Ø 0.875) KNOCKOUT 9.125 4.750 23.000 7.000 4.132 3.913 3.181 1.913 7.000 37.000 64.000 FRONT 7.000 23.000 37.000 7.000 59.000 RIGHT SYSTEM 2 SYSTEM 1 16.133 13.133 17.367 18.867 20.617 22.
505428-YTG-M-0512 Unit Height Dimensions MODEL PC180 PD180 PC240 PD240 YC180 YD180 YC240 YD240 YC300 A 44.5 44.5 50.0 50.0 44.5 44.5 50.0 50.0 50.0 PIPING AND ELECTRICAL CONNECTIONS Piping connections are made from the rear of 7.5 thru 12.5 Ton units and the front of 15 thru 20 Ton units. Connections can be made directly to the suction and liquid line service valves. and Piping and Electrical Connection Sizes tables for piping sizes and electrical knockout details.
505428-YTG-M-0512 Corner Weights & Center of Gravity NC/ND 090 Thru 240 Units Model Center of Gravity 4 Point Load Location (lbs.) (in.) Shipping Operating X Y A B C D Weight (lbs.) Drive Options 6 Point Load Location (lbs.) A B C D E F Vertical Airflow NC090 NC120 ND120 NC180 ND180 NC240 ND240 Std. Mtr. and Drv. High Static Mtr. and Drv. Std. Mtr. and Drv. High Static Mtr. and Drv. Std. Mtr. and Drv. High Static Mtr. and Drv. Std. Mtr. and Drv. High Static Mtr. and Drv. Std. Mtr. and Drv.
505428-YTG-M-0512 Corner Weights & Center of Gravity NC300 Unit Model Evaporator Section Drive HP Cabinet Wt (lb) Blower Drive Weight Center of Section Section (lbs.) Gravity Cabinet Cabinet Ship Opera CG X CG Y Wt (lb) Wt (lb) ping ting 4 Point Load Location (lbs.) A B C D 6 Point Load Location (lbs.) A B C D E F Vertical Airflow NC300 5 7.5 539 539 463 463 111 138 1067 1130 1067 1157 19.0 19.3 45.5 45.
505428-YTG-M-0512 TOP VIEW Ø 1.72 KNOCKOUT ELECTRIC HEAT Ø 1.718 KNOCKOUT FOR ELECTRIC HEAT 20.31 20.313 8.84 8.837 9.25 9.246 13.44 15.920 8.22 5.135 17.59 15.63 14.590 18.628 TOP VIEW - BLOWER OUTLET NC/ND120 INDOOR TOP VIEW - BLOWER OUTLET NC090 INDOOR FRONT AND SIDE VIEW Ø 1.718 KNOCKOUT POWER ACCESS 3.66 4.56 7.06 Ø 0.875 KNOCKOUT POWER ACCESS 65.000 6.38 FIELD PIPING CONNECTIONS 35.000 SYSTEM 2 20.531 17.85 15.50 SYSTEM 1 13.13 10.73 2.000 52.000 56.
505428-YTG-M-0512 BOTTOM VIEW 56.00 50.75 2.72 2.72 2.66 AIR IN 11.43 30.00 HORIZONTAL CONFIGURATION 30.00 35.00 30.00 60.
505428-YTG-M-0512 TOP VIEW Ø 1.718 KNOCKOUT FOR ELECTRIC HEAT 23.85 10.00 10.50 18.84 3.79 26.34 21.82 TOP VIEW - BLOWER OUTLET FRONT AND SIDE VIEW 3.66 4.56 7.06 1-1/4” CONDUIT KNOCKOUT Ø 1.718 POWER ACCESS 1/2” CONDUIT KNOCKOUT Ø 0.875 CONTROLS ACCESS 75.00 6.44 FIELD PIPING CONNECTIONS 42.00 27.53 SYSTEM 2 17.85 15.50 13.13 SYSTEM 1 10.73 2.00 70.50 74.50 FRONT VIEW - RETURN AIR NC/ND180 INDOOR 2.00 DRAIN 3/4” ABS PIPE CONNECTION 7.12 1.88 33.
505428-YTG-M-0512 BOTTOM VIEW 74.50 2.72 69.25 2.72 2.66 AIR IN 14.43 33.00 HORIZONTAL CONFIGURATION 33.000 42.000 33.000 66.
505428-YTG-M-0512 TOP VIEW 1-1/4” CONDUIT KNOCKOUT (Ø 1.718) ELECTRIC HEAT CONTROL WIRE CONNECTION 1-1/4” CONDUIT KNOCKOUT (Ø 1.718) ELECTRIC HEAT POWER CONNECTION 22.86 8.83 9.25 15.90 BLOWER OPENING 9.25 5.14 4.14 1-1/4” CONDUIT KNOCKOUT (Ø 1.718) ELECTRIC HEAT CONTROL WIRE CONNECTION 25.30 1-1/4” CONDUIT KNOCKOUT (Ø 1.718) ELECTRIC HEAT POWER CONNECTION 18.63 BLOWER OPENING 18.63 BLOWER OPENING 54.57 75.64 TOP VIEW BLOWER OUTLET NC/ND240 INDOOR FRONT AND SIDE VIEW 3.66 4.56 7.
505428-YTG-M-0512 BOTTOM VIEW 98.50 2.72 45.38 50.59 45.38 2.72 2.66 AIR IN AIR IN 11.43 30.00 HORIZONTAL CONFIGURATION 30.00 35.00 30.00 60.
505428-YTG-M-0512 BLOWER POSITION 1 EVAPORATOR COIL POSITION 5 POSITION 2 POSITION 6 POSITION 3 POSITION 7 POSITION 4 POSITION 8 Vertical Airflow Arrangements NC090-240 and ND120-240 Johnson Controls Unitary Products 111
505428-YTG-M-0512 POSITION 1 POSITION 2 POSITION 3 POSITION 4 POSITION 5 POSITION 6 POSITION 7 POSITION 8 Horizontal Airflow Arrangements NC090-240 and ND120-240 112 Johnson Controls Unitary Products
505428-YTG-M-0512 TOP VIEW 22.03 62.37 22.49 5.31 22.02 5.31 2.58 9.05 3.00 19.03 4X Ø.88 K0 CONTROLS CONNECTION 15.92 Ø 0.88 K0 ELECTRIC HEAT CONNECTION 57.69 FRONT AND SIDE VIEW 36.69 74.59 Ø 1.38 KO Ø 0.88 LIQUID CONNECTION 37.28 33.22 Ø 2.13 SUCTION CONNECTION Ø 1.38 KO 24.98 Ø 0.88 DRAIN CONNECTION 7.64 3.53 2.36 46.97 3.37 4.08 4.22 0.63 95.59 100.13 FRONT (RETURN AIR) VIEW 38.
505428-YTG-M-0512 HORIZONTAL CONFIGURATION RETURN AIR SUPPLY AIR 73.3 74.
7 AIR 505428-YTG-M-0512 8 9 AIR AIR AIR AIR 11 AIR AIR 10 12 AIR AIR AIR AIR AIR Horizontal Airflow Arrangements NC300 PIPING, ELECTRICAL AND DUCT OPENING CONNECTION SIZES MODEL NC090 NC120 ND120 NC180 ND180 NC240 ND240 NC300 SYSTEM DATA No. Refrigeration Circuits Suction Line OD (in.) Liquid Line OD (in.
505428-YTG-M-0512 Unit Mounting - NC/ND 090 Thru 240 The split air handling units can be applied in various horizontal positions. The Typical Suspension of AHU’s From Ceiling Figure shows recommended suspension rigging using properly sized all-thread and metal c-channel. All components to suspend an AHU must be field supplied. Please refer to the units total weight, center of gravity and corner weights. (Horizontal position) shown in the appropriate table for proper support sizing.
505428-YTG-M-0512 Unit Mounting - NC300 channels and hardware. The channels extend across the evaporator coil section, the heating coil section (if included) and the blower section. Each channel is to be bolted to each section as shown. The NC300 evaporator blower may be suspended from the joists with isolation type hangers or hooks. Suspension accessories 1HH0403 (NC300) may be ordered separately.
505428-YTG-M-0512 NOTE: Do not use a heat pump thermostat. R C Y1 G W1 W2 THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is not included or required on 7.5 Ton Single Stage Units.
505428-YTG-M-0512 NOTE: Do not use a heat pump thermostat. R C Y1 G Y2 W1 W2 THERMOSTAT TWO STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is only activated during second stage cooling operation.
505428-YTG-M-0512 R C Y1 G Y2 W1 W2 NOTE: Do not use a heat pump thermostat. THERMOSTAT TWO STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is not included or required on any 4 pipe units.
505428-YTG-M-0512 W1 W2 G C Y1 X R THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is not included or required on 7.5 Ton Single Stage Units. Typical Field Wiring Diagram - NC090 Evaporator Unit with YC090 Condenser Unit NOTE: On non NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
505428-YTG-M-0512 W1 W2 G C Y1 Y2 X R THERMOSTAT TWO STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is only activated during second stage cooling operation. Typical Field Wiring Diagram - NC120 thru 240 Evaporator Unit with YC120 thru 240 Condenser Unit NOTE: On non NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
505428-YTG-M-0512 Typical Field Wiring Diagram - NC300 Evaporator Unit with YC300 Condenser Unit NOTE: On non NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
505428-YTG-M-0512 W1 W2 G C X Y1 Y2 R THERMOSTAT TWO STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is not included or required on any 4 pipe units. Typical Field Wiring Diagram - ND120 thru 240 Evaporator Unit with YD120 thru 240 Condenser Unit NOTE: On non NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
505428-YTG-M-0512 Y1 R C G X W1 W2 THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING Y1 R C G X W1 W2 THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING Typical Field Wiring Diagram - Twin NC120 thru 240 Evaporator Units with 4-Pipe Condenser Unit NOTE: On non NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
505428-YTG-M-0512 Y1 Y2 G X C R W1 THERMOSTAT TWO STAGE COOLING SINGLE STAGE HEATING THERMOSTAT TWO STAGE COOLING SINGLE STAGE HEATING Y1 Y2 G X C R W1 Typical Field Wiring Diagram - Single 4-Pipe Evaporator Unit with Twin Condenser Units NOTE: On non NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
505428-YTG-M-0512 Y1 R C G X W1 W2 THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING Y1 R C G X W1 W2 THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING Typical Field Wiring Diagram - Twin NC090 Evaporator Units with 4-Pipe Condenser Unit NOTE: On non NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
Subject to change without notice. Printed in U.S.A. Copyright © 2012 by Johnson Controls, Inc. All rights reserved.