INSTALLATION MANUAL Mini-Split Air Conditioner HTCA / HTHA 36 Read this manual before installation and operation Make sure that it is well kept for later reference Read this manual before installation and operation Make sure that it is well kept for later reference
CONTENTS P le a s e r e a d th is in s ta lla tio n manual carefully before starting the installation. It will tell you necessary information. Safety precautions ..................................................................... 3 Part names..................................................................................... 4 Manual operation ....................................................................... 5 How the air conditioner works .............................................
EXTENDED PARTS REQUIRED TOOLS 1. 2. 3. 4. 5. 6. 7. 8. Screw driver Hexagonal wrench Torque wrench Spanner Reamer Hole core drill Tape measure Thermometer 9. 10. 11. 12. 13. 14. 15. Manifold guage Gas leak detector Vaccum pump Pipe clamp Pipe cutter Flare tool set Electrical circuit tester 1. Refrigerant Pipe Models 12-21 24-36 Liquid size 1/4 inch 3/8 inch Gas size 1/2 inch 5/8 inch 2. Pipe Insulation Material (Polyethylene foam 9 mm thick) 3. Vinyl tape 4.
PART NAMES INDOOR UNIT 3 INDOOR UNIT 2 Air inlet 1 2 3 4 5 6 7 1 - 4 5 Air outlet 6 Front panel frame 8 Infrared signal receiver Front panel 9 Remote controller Air filter 10 Drain hose, refrigerant Horizontal air flow grille connecting pipe Vertical air flow louver 11 Connective cable Room temperature sensor 12 Stop valve Display panel Active Carbon Electrostatic Fiber Filter (Standard) DISPLAY PANEL 7 8 OUTDOOR UNIT 10 9 Air inlet 11 12 Air outlet OPERATION Indicator: The indicator flashe
0$18$/ 23(5$7,21 0DQXDO RSHUDWLRQ FDQ EH XVHG WHPSRUDULO\ LQ FDVH \RX FDQ QRW ÀQG WKH UHPRWH FRQWUROOHU RU LWV EDWWHULHV DUH H[KDXVWHG 2SHQ DQG OLIW WKH IURQW SDQHO XS WR DQ DQJOH XQWLO LW UHPDLQV À[HG ZLWK D FOLFNLQJ VRXQG 3XVK WKH EXWWRQ XQWLO WKH $872 LQGLFDWRU LV OLW WKH XQLW ZLOO ZRUN LQ IRUFHG $872 PRGH &ORVH WKH SDQHO ÀUPO\ WR LWV RULJLQDO SRVLWLRQ 0DQXDO FRQWURO EXWWRQ &$87,216 2QFH \RX SXVK WKH PDQXDO EXWWRQ WKH RSHUDWLRQ PRGH LV VKLIWHG LQ DQ RUGHU DV $872 &22/ 2)) 3XVK
OPTIMAL OPERATION To achieve optimal performance, Please note the following: • Adjust the air flow direction correctly so that it is not directed on people. • Adjust the temperature to achieve the highest comfort level. Do not adjust the unit to excessive temperature levels. • Close doors and windows on COOL or HEAT modes, or performance may be reduced. • Use TIMER ON button on the remote controller to select a time you want to start your air conditioner.
OUTDOOR UNIT PICTURES 1. Dimension 3.1 Indoor unit Dimension W H D 12K 750 250 188 18K 906 286 235 24K-30K 1080 330 222 36K 1250 325 230 Mode EN 3.2 Outdoor unit Dimension Mode W H D L1 L2 12K 760 590 285 540 335 18K-30K 845 695 335 560 360 36K 895 860 330 590 333 ENGLISH J435.
PARTS INSTALLATION Name of part Installation plate Mounting screw ST3.9x25-C-H Clip anchor Part No. 1 2 3 Liquid side 4 Refrigerant pipe Q’ty 1 8 8 rm ore 1 2 3 Parts you must purchase ø 9.53 (24000-36000 Btu/h) 12c mo rm ore ø 16 (24000-36000 Btu/h) 1 1 1 1 Remote controller Remote controller holder Seal 5 6 7 8 15cm or more mo ø 6.35 (12000-21000 Btu/h) ø 12.7 (12000-21000 Btu/h) Gas side 12c Drain elbow Air filte r Mounting screw B ST2.
MODEL 24-30 CAUTIONS Above 150 from the ceiling Hooked Part Hooked Part Hooked Part 1080 432 108 22 432 Above 120mm from the wall 50 58 95 95 50 58 330 Above 120mm from the wall 115 115 465 Pipe hole 465 Pipe hole • Nevermodifytheunitbyremovinganyofthesafetyguards or by passing any of the safety interlock swithces. • Connect the interconnecting cable correctly and connect the connecting cable to terminal as identified with their respective marking.
Indoor Unit Fixing • • • • Thread the indoor unit piping and cable through the hole. Hang the top of the unit onto the upper ridge of them in mounting plate. Make sure that the unit is correctly hung in place by sliding it to the left, then to the right. Press the bottom left and bottom right hand corners of the unit against the mounting plate until the fixing prongs click into place in the retainers provided to that effect.
To this effect, when the piping has been evacuated, close the pressure gauge tap, note the value on the gauge, then wait for 15 minutes. If the needle moves, there is a leak in the system. Make the necessary adjustments or repairs and repeat this procedure until the needle no longer moves. - Open the service valves and top up the refrigerant charge if necessary.
Wiring Prepare the power source for exclusive with the air conditioner. The supply voltage must comply with the rated voltage of the air conditioner: The plug socket shall be accessible after installation. Remark: All the wiring must be based on the wiring nameplate which shown on the model. CAUTIONS • Perform the wiring with sufficient capacity. Installation places legally require a short circuit isolator to be attached to prevent electrical shock. • Do not extend the power cable code by cutting.
Outdoor Unit : HTCA18OSAAAR Indoor Unit : HTCA18OSAAAR COMPRESSOR RELAY TRANSFORMER INDOOR UNIT OUTDOOR UNIT BLUE WHITE BROWN SWITCH BOARD CN9 CN4 Y&G CN12 DISPLAY BOARD Y/G CURRENT DETECTOR RED BLACK BLACK LOUVER MOTOR 2 LOUVER MOTOR 1 CN6 WHITE CN10 HEAT EXCHANGER SENSOR AMB IENT SENSOR CN8 CN7 BLACK OVERLOAD RELAY CN5 BLACK Y/G COMPRESSOR BLUE JX1 RED INDOOR UNIT TO OUTDOOR UNIT WHITE Y&G INDOOR MOTOR FAN MOTOR BLUE COMPRESSOR CAPACITOR FAN CAPACITOR Indoor Unit : HTCA2
Indoor Unit : HTHA18OSAAAR Outdoor Unit : HTHA18OSAAAR Indoor Unit : HTHA24-30OSAAAR Outdoor Unit : HTHA24-30OSAAAR Indoor Unit : HTCA12OSAADR Outdoor Unit : HTCA12OSAADR POWER SUPPLY INDOOR MOTOR WHITE EN TO INDOOR UNIT OUTDOOR UNIT STEP MOTOR 1 BLACK 2(N) GREEN BLACK PIPE TEMPERATURE SENSOR BK COMPRESSOR RELAY ROOM TEMPERATURE SENSOR BK DISPLAY BOARD C CURRENT DETECTOR OVERLOAD RELAY (INTERNAL/ EXTERNAL DEPENDING ON MODELS) RD RED FAN MOTOR COMP R(M) S BL CAPACITOR RD BK RD
Indoor Unit : HTCA18RSAAAR Outdoor Unit : HTCA18RSAAAR OUTDOOR FAN C RED R BLUE COMPRESSOR BLACK BLUE S WHITE RED ACITOR 1 2 F ACITOR 1 2 BLACK BLACK BLACK 1 TERMINAL BLACK ARTER N T Indoor Unit : HTCA36RSAADR Outdoor Unit : HTCA36RSAADR Outdoor HTCA36RSAADR Indoor Unit : HTHA36RSAADR EN Outdoor Unit : HTHA36RSAADR Outdoor HTHA36RSAADR Indoor Unit :HTCA18OSAADR-I Outdoor Unit : HTCA18OSAADR-I WIRING DIAGRAM (OUTDOOR UNIT) EN ENGLISH J435.
Outdoor Unit : HTHA18OSAADR-I Indoor Unit : HTHA18OSAADR-I POWER SUPPLY GREEN Indoor Unit : HTCA24OSAADR-I Outdoor Unit : HTCA24OSAADR-I POWER SUPPLY GREEN EN Outdoor Unit : HTCA30OSAADR Indoor Unit : HTCA30OSAADR WIRING DIAGRAM (INDOOR UNIT) MAIN BOARD Indoor Unit :HTHA24OSAADR-I Outdoor Unit : HTHA24OSAADR-I EN 16 J435.
Indoor Unit : HTHA30OSAADR Outdoor Unit : HTHA30OSAADR Indoor Unit : HTCA24RSAAAR Outdoor Unit : HTCA24RSAAAR Indoor Unit : HTCA30RSAAAR Outdoor Unit : HTCA30RSAAAR EN EN ENGLISH J435.
Electrical Work Model Power Switch and Fuse rating Power Source 220-240V ~ 50Hz 220-240V ~ 60Hz 115V ~ 60Hz (UL) 220-240V ~ 50Hz 220-240V ~ 60Hz 115V ~ 60Hz (UL) 220-240V ~ 50Hz 220-240V ~ 60Hz 220-230V ~ 60Hz (UL) 220-240V ~ 50Hz 220-240V ~ 60Hz 220-230V ~ 60Hz (UL) 220-240V ~ 50Hz 220-240V ~ 60Hz 380-420V 3N ~ 60Hz 220-240V ~ 50Hz 380-420V 3N ~ 60Hz 7000-9000 Btu/h 12000 Btu/h 18000-21000 Btu/h 24000 Btu/h 28000-30000 Btu/h 36000 Btu/h Wiring size 10A f 1.0 mm 2 15A f 1.5 mm 2 40/30A 2.
MAINTENANCE WARNING Household Drain Cleaner No It is necessary to stop the air conditioner and disconnect the power supply before cleaning. Cleaning the indoor unit and remote controller CAUTION Thinner • Use a dry cloth to wipe the indoor unit and remote controller. • A cloth dampened with cold water may be used on the indoor unit if it is very dirty. • The front panel of the indoor unit can be removed and cleaned with water. Then wipe it with a dry cloth.
OPERATION TIPS The following events may occur during normal operation. 1. Protection of the air conditioner. Compressor protection • The compressor cannot restart for 3 minutes after it stops. Anti-cold air (Cooling and heating models only) • The unit is designed not to blow cold air on HEAT mode, when the indoor heat exchanger is in one of the following three situations and the set temperature has not been reached. A) When heating has just starting. B) Defrosting. C) Low temperature heating.
TROUBLESHOOTING GUIDE Problem A. The air conditioner does not run. Probable cause 1. Power Failure. 2. Fuse blown or circuit breaker open. 3. Voltage is too low. 4. Faulty contactor or relay. 5. Electrical connections loose. 6. Thermostat adjustment too low (in heating mode) or too high (in cooling mode) 7. Faulty Capacitor 8. Incorrect wiring, terminal loose 9. Pressure switch tripped B. The outdoor fan runs but the compressor will not start. 1. Motor winding cut or grounded. 2. Faulty Capacitor. C.
INSTALLATION, REMOVAL AND DISPOSAL This product contains refrigerant under pressure, rotating parts, and electrical connections which may be a danger and cause injury! All work must only be carried out by competent persons using suitable protective clothing and safety precautions. Read the Manual Risk of electric shock Unit is remotely controlled and may start without warning 1. Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit.