Service manual

Installation
___________________________________________________________________________________
___________________________________________________________________________________
- 258 -
Min. inserting depth and clearance between connectors. Unit: mm
Out .Diameter. (D) Min. Inserting depth (B) Clearance (A~D)
5D8
6
8D12
7
0.050~0.21
11D16
8
16D25
10
0.050~0.27
25D35
12
A
D
35D45
14
0.050~0.35
4.6.3 Flare Connection
1) Before flaring, the auxiliary pipe must be annealed.
2) Use incision machine.
3) Dimension:
Shape Diameter O.D. A
3/8" 9.53
1/2" 12.7
0.050.21
5/8" 15.88
3/4" 19.05
0.050.27
4) Smear oil at flaring part.
Be careful to get rid of burr.
Use two torques.
Use proper torque to fasten nut.
Torque
Dimension
(kgf ·m) (N·cm)
1/4"(Φ6.4) 144176 14401720
3/8"(Φ9.5) 133407 32703990
1/2"(Φ12.7) 504616 49506030
5/8"(Φ15.9) 630770 61807540
3/4"(Φ19.0) 9901210 927011860
4.6.4 Laying
1) Laying the refrigerant pipes
Mark the system clearly in every distance to prevent wrong connection.
The plane where the two branches locate should be parallel to the horizontal plane, or the