Service manual

146
a. Under AUTO mode, if T
amb
.T
preset
is detected, the unit will select to run under cooling mode, in which case implicit
preset temperature is 25ć; if T
amb
.T
preset
-2ć, the compressor will stop, the outdoor fan will stop with a time lag of 1
minute, and the indoor fan will run at preset speed; and if T
preset
–(-2ć)< T
amb
.< T
preset
, the unit will remain at its original
state.
b. Under AUTO mode, if T
amb
. T
preset
+2ć
is detected, the unit will select to run under heating mode, in which case
implicit preset temperature is 18ć; if T
amb
.T
preset
+5ć, the compressor will stop, the outdoor fan will stop with a time lag
of 1 minute, and the indoor fan will run under the mode of residue heat blowing; and if T
preset
+2ć< T
amb
.< T
preset
+5ć, the
unit will remain at its original state. The cooling-only unit will run under fan mode.
c. Under AUTO mode, if 20ć< T
amb
.< 25ć, the unit will remain at its original state.
2.Protection
a. In cooling operation, protection is the same as that under the cooling mode;
b. In heating operation, protection is the same as that under the heating mode;
c. When ambient temperature changes, operation mode will be converted preferentially. Once started, the compressor will
remain unchanged for at least 6 minutes.
(6) Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes
ķ
Overload protection
T
tube
: measured temperature of outdoor heat exchanger under cooling mode; and measured temperature of indoor heat
exchanger under heating mode.
1) Cooling overload
a. If T
tube
52ć, the unit will return to its original operation state.
b. If T
tube
55ć, frequency rise is not allowed.
c. If T
tube
58ć, the compressor will run at reduced frequency.
d. If T
tube
62ć, the compressor will stop and the indoor fan will run at preset speed.
2) Heating overload
a. If T
tube
52ć, the unit will return to its original operation state.
b. If T
tube
55ć, frequency rise is not allowed.
c. If T
tube
58ć, the compressor will run at reduced frequency.
d. If T
tube
62ć, the compressor will stop and the indoor fan will blow residue heat and then stop.
ĸ
Exhaust temperature protection of compressor
If exhaust temperature 98ć, frequency is not allowed to rise.
If exhaust temperature 103ć, the compressor will run at reduced frequency.
If exhaust temperature 110ć, the compressor will stop.
If exhaust temperature 90ć and the compressor has stayed at stop for at least 3 minutes, the compressor will resume its
operation.
Ĺ
Communication fault
If the unit fails to receive correct signals for durative 3 minutes, communication fault can be justified and the whole system
will stop.
ĺ
Module protection
Under module protection mode, the compressor will stop. When the compressor remains at stop for at least 3 minutes, the
compressor will resume its operation. If module protection occurs six times in succession, the compressor will not be started
again.
Ļ
Overload protection
If temperature sensed by the overload sensor is over 115ć, the compressor will stop and the outdoor fan will stop with a
time lag of 30 seconds. If temperature is below 95ć, the overload protection will be relieved.
ļ
If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a time
lag of 30 seconds. When voltage on the DC bus returns to its normal value and the compressor has stayed at stop for at least
3 minutes, the compressor will resume its operation.
Ľ
Faults of temperature sensors
Operation