ERJC 36, 42 R by johnson controls Ref: GB Heat pump Multisplit Inverter Condensing units Installation Instructions Johnson Controls Manufacturing España, S.L. is participating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products, in the program AC1, AC2, AC3, LCP and FC.
User Notice The total capacity of the indoor units which runs at the same time can not exceed 150% of that of the outdoor units; otherwise, the cooling (heating) effect of each indoor unit would be poor. Switch the main power on 8 hours before start the unit, helpful for a successful startup. It is a normal phenomenon that the indoor unit fan will still run for 20~70 seconds after the indoor unit receives the “stop” signal so as to make full use of after-heat for the next operation.
by johnson controls Contents Safety Precautions....................................................................................... 4 Installation Instructions............................................................................... 5 1 Installation Location and Matters Needing Attention.......................................... 5 2 Installation of the Outdoor Unit........................................................................... 7 3 Connection between Indoor and Outdoor Units ...........
by johnson controls Safety Precautions Ⅰ Safety Precautions Please read this manual carefully before use and operate correctly as instructed in this manual. Please especially take notice of the following two symbols: Warning! It indicates improper operation which will lead to human casualty or sever injury. Cuation! It indicates improper operation which will lead to injury or property damage.
by johnson controls Installation Instructions Installation Instructions 1 Installation Location and Matters Needing Attention The installation of the unit must comply with the national and local safety regulations. The installation quality directly affects the normal use, so the user should not carry out the installation personally. Instead, the installation and debugging should be done by the professional personnel. Only after that, can the unit be energized. a.
by johnson controls Installation Instructions the dedicated one. 6) The earthing should be reliable and the earth wire should be connected to the dedicated device of the building by the professional personnel. Besides, the air switch coupled with the leakage current protection switch must be equipped, which is of enough capacity and of both magnetic and thermal tripping functions in case of the short circuit and overload.
by johnson controls Installation Instructions ERJC(36)R POWER INDOOR UNIT A INDOOR UNIT B INDOOR UNIT C INDOOR UNIT D XT5X T4 XT3X T2 N L XT1 OUTDOOR UNIT Fig.2 e. Noise Precautions 1) The air conditioning unit should be installed where ventilation is in good condition, otherwise the working capability of the unit would be reduced or working noise would be increased.
by johnson controls Installation Instructions ERJC(36)R ERJC(42)R 1087 1015 572 362 121 76 412 110 76 340 378 440 401 99 96 450 350 840 1103 1022 950 631 192 191 Fig.3 Fig. 4 2) During the transportation of the outdoor unit, two lifting ropes long enough must be used in four directions and the separation angle must be less than 40°prevent the center of unit deviating. he support leg and base frame of the unit.
by johnson controls Installation Instructions b. Capacity Level and Capacity Code of the Indoor and Outdoor Units Table 2 Indoor Unit Outdoor Unit Capacity Level Capacity Code 09 25 12 35 18 50 21 60 24 71 36 100 42 120 1) The outdoor unit with capacity level 36 can drive up to four sets of indoor units, while the outdoor unit 42 can drive up to five. 2) The sum of the capacity codes of the indoor units should be among 50%-150% of that of the outdoor unit. c.
by johnson controls Installation Instructions Flare Nut Pipe Pipe Torque Wrench Ordinary Fig. 6 Table 5:Moments of Torque for Tightening Screws Diameter Wall Thickness(mm) Moment of Torque φ6.35mm ≥ 0.5 15-30(N·m) φ9.52mm ≥ 0.71 30-40(N·m) φ12.7mm ≥1 45-50(N·m) φ15.9mm ≥1 60-65(N·m) CUATION ! ① .
by johnson controls Installation Instructions 1) Bundle the refrigerant pipe and electric wire together with tape, and separate them from the drain pipe 2) Wrap the pipe from the bottom of the outdoor unit to the top of the pipe where it enters the wall. During the wrapping, the later circle should cover half of the former one. 3) Fix the wrapped pipe on the wall with clamps. CAUTION ! ① . Do not wrap the pipe too tightly; otherwise the insulation effect would be weakened.
by johnson controls Installation Instructions refrigerant will be charged. Table 7 Model Total Liquid Pipe Lenght (a+b+c+d+e) ERJC(36)R ≤ 40m ERJC(42)R ≤ 50m Additional Refrigerant Charge2=∑Extra Liquid Pipe Length×22g/m( liquid pipe 1/4’’). Note: if the total refrigerant pipe length is larger than that listed in the table above, the additional refrigerant for the extra length of the pipe needs to be charged as per 22g/m. 3) Example : ERJC (42) R e d c b a Fig.9 Table 8 Indoor Unit Serial No.
by johnson controls Installation Instructions Table 11 Refrigerant Pipe Diameter Total Length(m) Additional Refrigerant Charge(kg) Φ15.9 Φ12.7 Φ9.52 Φ6.35 Total c. Items to be checked after the Installation Table 12 Items to be Checked Possible Errors Has each part and component the of unit installed securely? Is the thermal insulation sufficient? The unit may fall off, vibrate or generate noise. The cooling (heating) capacity may be poor. Dews and water drops may be generated.
by johnson controls Working Principles of the Unit Ⅲ Working Principles of the Unit Schematic Diagram of Free Match Series Inverter Heat Pump Multi VRF System M Fig. 10 Schematic Diagram of Free Match Series Inverter Heat Pump Multi VRF System The outdoor and indoor units start to work once the power is switched on.
by johnson controls Parts and Components of the Unit Ⅳ Parts and Components of the Unit System Structure Outdoor Unit Cassette Type Indoor Unit Duct Type Indoor Unit(Round air outlet) Wall Mounted Indoor Unit Fig. 11 Duct Type Indoor Unit(Rectangular air outlet) For the free match series DC inverter GMV multi VRF air conditioning system, one outdoor unit is able to drive up to five indoor units which can be cassette type, duct type, wall-mounted or floor ceiling type.
by johnson controls Maintenance Maintenance WARNING ! ① . The unit can only be cleaned after the unit is turned off and the main power is cut off; otherwise it would cause an electric shock hazard. ② . Do not dampen the air conditioner, as it would cause a electric shock hazard and never rinse the unit with water in any event. CUATION ! ① . Volatile liquid, like thinner, gasoline etc would damage the appearance of the air conditioning unit.
by johnson controls Troubleshooting Troubleshooting WARNING ! ① . In the event of abnormal conditions (like, stinky smell), please shut off the main power supply immediately and then contact the YORK appointed service center; otherwise the continuous abnormal running would damage the air conditioning unit and also would cause ele ② .
by johnson controls Troubleshooting 2 The conditions listed below are not classified into errors Table 14 Conditions The unit does not run The unit blows out mist The unit generates noise The unit blows out dust. The unit emits odors. Causes When restart the unit soon after it is stopped. The overload protection switch of the unit let the startup delayed for three minutes. As soon as power is on. The unit will stand by for approximate one minute. When the cooling operation starts.
by johnson controls Troubleshooting Refrigerant insufficiency or blockage protection (available for the residential outdoor unit) Short/open circuit of the indoor ambient temperature sensor Short/open circuit of the indoor evaporator Short/open circuit of the of the outdoor ambient temperature sensor Short/open circuit of the temperature sensor at the midway of the condenser coil ( for the commercial unit) Short/open circuit of the outdoor discharge temperature sensor Oil returning in cooling System high p
by johnson controls Troubleshooting Mode conflict Mode conflict Overload protection Overload protection Anti cold blow protection / / Indoor unit water overflow error Trial run/trial operation Refrigerant recovery mode Drive module resetting(for the commercial unit) Min. cooling/ heating (capability test code) Mid.
by johnson controls Troubleshooting Drive board ambient temperature sensor error (for the commercial unit) Drive board ambient temperature sensor error PF Flash 3 times Flash 3 times Flash 3 times oE oE DC link high voltage protection DC link low voltage protection PL Flash 3 times Flash 3 times Flash 3 times oE oE DC link low voltage protection DC link high voltage protection PH Flash 3 times Flash 3 times Flash 3 times oE oE / Abnormal AC input voltage PP Flash 3 times Flash 3
by johnson controls Troubleshooting Short/open circuit of the temperature sensor at the inlet of the condenser coil ( for the commercial unit) Short/open circuit of the temperature sensor at the outlet of the condenser coil ( for the commercial unit) Memory card error Frequency limitation/ degradation for module circuit protection (for phase circuit) 22 Frequency limitation/ degradation for module temperature protection Frequency limitation/ degradation for overload Frequency limitation / degradation for
by johnson controls Troubleshooting Compressor phase circuit detection error DC link voltage drop error Zero detection circuit error Nominal cooling/heating (capability test code) Max. cooling/ heating (capability test code) / U1 / / Flash 12 times / / / U3 / / Flash 20 times / / / U8 Flash 17 times / / / / / P1 / / / / / / P2 / / / / / The words in gray means the corresponding function is unavailable.
by johnson controls Troubleshooting Table 17 Error description of outdoor refrigerant pipe detection function Wiring error or component error Unit which is detecting Unit which isn’t detecting 5E 5E 01 ** 5E 02 ** 03 ** 04 ** 05 ** Unit which is detecting -- 01 -- 02 -- 5P 03 -- 04 -- 5P 05 -- 5E 5E Indoor unit gas pipe connection error or component error 5P 5P 5P Fig.
by johnson controls Function Description Ⅶ Function Description Refrigerant Recovery The refrigerant can be recovered from either the indoor unit or the outdoor unit. From the outdoor unit: it is available to recover the refrigerant from the outdoor unit by pressing “SW3”for a long time period.
by johnson controls Performance Parameters Ⅷ Performance Parameters Rated Working Conditions of the Air Conditioning Unit Table 18 Working Temperature Range Indoor side state Outdoor side stae Dry bulb temp. ℃ Wet bulb temp. ℃ Dry bulb temp. ℃ Wet bulb temp. ℃ Rated Cooling 27 19 35 24 Max. cooling 32 23 48 26 Min. cooling 21 15 18 — Rated Heating 20 15 7 6 Max. heating 27 — 24 18 Min. heating 20 15 - 15 - 16 Notes: ① .
DECLARACION CE DE CONFORMIDAD SOBRE MAQUINAS FABRICANTE: JOHNSON CONTROLS MANUFACTURING ESPAÑA, S.L. DIRECCIÓN: Paseo Espronceda, 278, 08204 SABADELL Certificamos que el equipo descrito, ha sido diseñado, fabricado y probado de conformidad con los requisitos básicos de la Directiva de Equipos a presión 97/23/CEE y sus correspondientes módulos de aplicación.