Operating instructions

14
Data and measurements are subject to change without prior notice.
Standard electric connections,
thermostat DPC-1 (for thermostat
with communication)
Once the base is fastened to the wall, wire
the thermostat as shown in the following il-
lustration:
Caution
A shielded 10 x 0.22 mm² cable,
with a maximum length of 100 m.,
should be used between the ther-
mostat and the control board.
Connections to be carried out are R, B and
X1. (The other 7 wires are necessary to
connect G, Y, Y2, O/B and W if you wish to
use a thermostat with relays)
To connect the remote sensor use shielded
2 x 0.5 mm
2
cable with a maximum length
of 100 m. between the thermostat and the
sensor. The connections to be carried out
are RS1 and RS2.
For correct operation of the thermostat, it is
indispensable to have made electric wiring
properly, and have inserted the two AAA 1.5
V alkaline batteries at the rear of the front
panel, as shown below:
GB
X1
X2
RS1
RS2
RS3
AL
R
B
G
Y
Y2
O/B
W
REAR OF
FRONT PANEL
BASE OF
THERMOSTAT
AAA 1.5 V ALKALINE
BATTERIES
X1
X2
RS1
RS2
RS3
AL
R
B
G
Y
Y2
O/B
W
BASE OF
THERMOSTAT
REMOTE PROBE
(OPTIONAL)
YELLOW
RED
WHITE
SHIELDED 10x 0.22mm2 CABLE
(MAXIMUM LENGTH 100 m)
SHIELDED CABLE 2x 0,5 mm2 cable
(MAXIMUM LENGTH 100 m)