Technical Guide

718444-YTG-A-0811
26 Johnson Controls Unitary Products
Electrical Data
DNZ024-060 Gas Heat
Size
(Tons)
DNZ
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max
Fuse
2
/
Breaker
3
Size
(Amps)
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
RLA LRA MCC FLA FLA
024
(2.0)
208/230-1-60 9.3 43 15 1.4 4.1 17.1 25
030
(2.5)
208/230-1-60 13.1 74 21 1.3 6.0 23.7 30
208/230-3-60 8.6 68 14 1.3 6.0 18.1 25
460-3-60 4.5 34 7 0.75 3.0 8.6 15
036
(3.0)
208/230-1-60 14.7 74 23 1.3 6.0 25.7 35
208/230-3-60 9.1 68 14 1.3 6.0 18.7 25
460-3-60 4.5 34 7 0.8 3.0 9.4 15
042
(3.5)
208/230-1-60 15.7 88 25 1.7 6.0 27.3 35
208/230-3-60 9.3 68 15 1.7 6.0 19.3 25
460-3-60 5.1 34 8 1.0 3.0 10.4 15
048
(4.0)
208/230-1-60 20.5 115 32 1.7 7.6 34.9 45
208/230-3-60 16.0 120 25 1.7 7.6 29.3 40
460-3-60 7.7 50 12 1.0 3.8 14.4 20
060
(5.0)
208/230-1-60 26.2 150 41 2.3 7.6 42.7 60
208/230-3-60 17.9 120 28 2.3 7.6 32.3 40
460-3-60 9.6 70 15 1.3 3.8 17.1 25