Technical Guide

333491-YTG-G-0211
Johnson Controls Unitary Products 53
Gas Heat Minimum Supply Air
Size
(Tons)
Model Heat Size
Supply Air (CFM)
Cooling Heating
Min Max Min Max
024
(2.0)
DNZ
N036 600 1000 610 1330
D056 600 1000 860 1730
DNQ
N036 450 900 610 1330
N056 450 900 860 1730
D056 450 900 860 1730
DNX
N036 450 900 610 1330
N056 450 900 860 1730
D056 450 900 860 1730
030
(2.5)
DNZ
DNQ
N036 750 1250 610 1330
N056 750 1250 860 1730
D056 750 1250 860 1730
036
(3.0)
DNZ
N036 1200 1500 610 1330
N056 1200 1500 940 2070
D056 1200 1500 940 2070
N072 1200 1500 1110 2220
D072 1200 1500 1110 2220
DNQ
N036 700 1350 610 1330
N056 700 1350 940 2070
D056 700 1350 940 2070
N072 700 1350 1110 2220
D072 700 1350 1110 2220
DNX
N065 685 1350 1080 2370
N090 685 1350 1070 1780
D090 685 1350 1070 1780
042
(3.5)
DNZ
DNQ
N065 1050 1750 1080 2370
N090 1050 1750 1070 1780
D090 1050 1750 1070 1780
048
(4.0)
DNZ
N065 1200 2000 1080 2370
N090 1200 2000 1230 2290
D090 1200 2000 1230 2290
N110 1200 2000 1330 2220
D110 1200 2000 1330 2220
DNQ
N065 930 1700 1080 2370
N090 930 1700 1230 2290
D090 930 1700 1230 2290
N110 930 1700 1330 2220
D110 930 1700 1330 2220
DNX
N065 930 1700 1080 2370
N090 930 1700 1230 2290
D090 930 1700 1230 2290
N110 930 1700 1330 2220
D110 930 1700 1330 2220
060
(5.0)
DNZ
N065 1500 2100 1080 2370
N090 1500 2100 1230 2290
D090 1500 2100 1230 2290
N110 1500 2100 1330 2220
D110 1500 2100 1330 2220
DNQ
N065 1060 1800 1080 2370
N090 1060 1800 1230 2290
D090 1060 1800 1230 2290
N110 1060 1800 1330 2220
D110 1060 1800 1330 2220