Technical Guide

333491-YTG-G-0211
34 Johnson Controls Unitary Products
115°F 125°F
1350
77
43.8 4.0 33.4 22.1 16.0 - - - 42.4 4.6 36.0 24.5 16.2 - - -
72
39.9 4.0 34.7 28.8 23.0 17.1 - - 37.0 4.4 33.8 28.0 22.1 16.3 - -
67
36.0 3.9 36.0 35.6 29.9 24.1 18.2 - 31.7 4.3 31.7 31.7 28.1 22.3 16.4 -
62
34.2 3.9 34.2 34.2 33.7 27.9 22.0 16.1 32.3 4.4 32.3 32.3 31.7 25.8 20.0 14.1
57
34.0 3.9 34.0 34.0 33.4 27.6 21.7 15.8 31.9 4.4 31.9 31.9 31.2 25.3 19.5 13.6
1400
77
44.6 4.0 34.9 22.8 16.5 - - - 42.9 4.5 37.6 25.5 16.6 - - -
72
40.6 4.0 35.8 29.7 23.6 17.6 - - 37.5 4.4 34.8 28.8 22.7 16.7 - -
67
36.6 3.9 36.6 36.6 30.8 24.7 18.7 - 32.0 4.2 32.0 32.0 28.8 22.8 16.8 -
62
34.8 3.9 34.8 34.8 34.7 28.6 22.6 16.5 32.7 4.3 32.7 32.7 32.5 26.4 20.4 14.3
57
34.6 3.9 34.6 34.6 34.4 28.3 22.3 16.2 32.2 4.3 32.2 32.2 32.0 25.9 19.9 13.8
1500
72
40.1 4.0 37.5 31.2 24.9 18.6 - - 37.7 4.4 36.7 30.5 24.2 18.0 - -
67
36.2 3.9 36.2 36.2 32.4 26.1 19.8 - 32.3 4.3 32.3 32.3 30.8 24.5 18.3 -
62
34.4 3.9 34.4 34.4 34.4 28.1 21.8 15.5 32.9 4.4 32.9 32.9 32.7 26.5 20.2 14.0
57
34.1 3.9 34.1 34.1 34.1 27.8 21.5 15.2 32.4 4.4 32.4 32.4 32.3 26.0 19.8 13.5
1600
72
39.6 4.0 39.2 32.7 26.1 19.6 - - 37.9 4.5 37.9 32.2 25.7 19.3 - -
67
35.7 3.9 35.7 35.7 34.0 27.5 21.0 - 32.6 4.3 32.6 32.6 32.6 26.2 19.8 -
62
34.0 3.9 34.0 34.0 34.0 27.5 21.0 14.5 33.0 4.4 33.0 33.0 33.0 26.6 20.1 13.7
57
33.7 3.9 33.7 33.7 33.7 27.2 20.7 14.2 32.6 4.4 32.6 32.6 32.6 26.1 19.7 13.2
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DNQ042 (3.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65