718446-YTG-A-0811 ® TECHNICAL GUIDE R-410A AFFINITY™ SERIES DNX MODELS 2 - 4 TON 60 Hertz Description These York® Affinity™ packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation. The single or two stage gas-fired heaters have aluminized steel tubular heat exchangers and spark to pilot ignition. They are available in natural gas with field conversion to propane.
718446-YTG-A-0811 Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
718446-YTG-A-0811 Nomenclature Cooling/Gas Unit D 1 NX 036 N 036 06 Product Category Voltage Code D = Single Package Air Conditioner 06 = 208/230-1-60 25 = 208/230-3-60 46 = 460-3-60 Product Generation 1 = 1st Generation 2 = 2nd Generation Product Identifier NX = R-410A 15 SEER Gas Heat/Electric Factory Installed Gas Heat N = Single Stage D = Two Stage Nominal Cooling Capacity (MBH) 024 = 24,000 BTUH 036 = 36,000 BTUH Features and Benefits Standard Features • Operating Efficiency - All gas unit
718446-YTG-A-0811 • Top Discharge - The top discharge condenser fan does not disrupt neighboring areas or dry-out vegetation surrounding the unit. The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications. • Condenser Coil Grille - All models utilize a stamped “Louvered” design which provides superior impact protection against smaller objects during transit and after installation.
718446-YTG-A-0811 control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy are also available. A built-in barometric relief of 25% is provided. • Single Enthalpy Sensor - Sensor replaces dry bulb sensor standard in economizer kit. Provides improved economizer operation by sensing the dry bulb temperature from outdoors plus the enthalpy content of the outdoor air.
718446-YTG-A-0811 Indoor (Evaporator) Fan Assembly Fan shall be direct drive design. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance. Fan assembly shall be “Slip Track” (slide-out) design for easy removal and cleaning.
18446-YTG-A-0811 Physical Data DNX024-048 Single Stage Gas Heat Component Nominal Tonnage ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) ARI net capacity (Btu) EER SEER Nominal CFM System power (KW) Refrigerant type Refrigerant charge (lb-oz) ARI HEATING PERFORMANCE Heating model Heat input (K Btu) Heat output (K Btu) AFUE % Steady state efficiency (%) No. burners No. stages Temperature Rise Range (ºF) Gas Limit Setting (ºF) Gas piping connection (in.
718446-YTG-A-0811 DNX024-048 Two Stage Gas Heat Component Nominal Tonnage ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) ARI net capacity (Btu) EER SEER Nominal CFM System power (KW) Refrigerant type Refrigerant charge (lb-oz) ARI HEATING PERFORMANCE Heating model Heat input (K Btu) Heat output (K Btu) AFUE % Steady state efficiency (%) No. burners No. stages Temperature Rise Range (ºF) Gas Limit Setting (ºF) Gas piping connection (in.) DIMENSIONS (inches) Length Width Height OPERATING WT.
718446-YTG-A-0811 DNX Unit Limitations Size (Tons) Model Unit Voltage Unit Limitations Applied Voltage Min Max 024 (2.0) DNX 208/230-1-60 187 252 115 036 (3.0) DNX 048 (4.
718446-YTG-A-0811 Capacity Performance DNX024-048 Cooling Capacities DNX024 (2.0 Ton) Air on Evaporator Coil CFM 600 800 600 800 600 800 WB (°F) Net Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 24.9 22.8 20.8 18.3 19.5 32.1 29.8 27.4 25.0 25.6 1.2 1.1 1.1 1.1 1.0 1.8 1.8 1.7 1.7 1.7 11.4 16.1 20.8 18.3 19.5 15.1 21.1 27.1 25.0 25.6 77 72 67 62 57 77 72 67 62 57 22.3 19.9 17.6 16.1 16.1 29.2 26.6 24.0 22.2 22.2 1.5 1.5 1.4 1.4 1.4 2.1 2.1 2.1 2.0 2.0 12.5 15.1 17.
718446-YTG-A-0811 DNX036 (3.0 Ton) Air on Evaporator Coil CFM 925 1275 925 1275 925 1275 WB (°F) Net Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 35.2 32.3 29.5 26.8 28.2 48.7 45.7 42.8 38.0 38.4 1.5 1.5 1.5 1.5 1.6 2.8 2.6 2.5 2.3 2.5 20.9 25.2 29.5 26.8 28.2 23.8 33.3 42.8 38.0 38.4 77 72 67 62 57 77 72 67 62 57 31.5 28.5 25.6 23.4 23.6 44.4 40.7 37.0 35.4 35.0 1.9 1.9 1.9 1.9 1.9 3.2 3.1 3.1 2.9 3.0 21.5 23.6 25.6 23.4 23.6 27.2 32.1 37.0 35.4 35.
718446-YTG-A-0811 DNX048 (4.0 Ton) Air on Evaporator Coil CFM 1000 1550 1000 1550 1000 1550 WB (°F) Net Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 45.3 42.0 38.8 34.4 33.6 64.7 59.6 54.5 50.3 48.8 2.2 2.2 2.2 2.2 2.2 3.9 3.8 3.7 3.5 3.5 23.2 29.7 36.3 34.4 33.6 31.1 42.0 52.9 50.3 48.8 77 72 67 62 57 77 72 67 62 57 40.4 37.2 34.0 30.5 29.8 56.8 52.4 48.0 44.8 44.3 2.8 2.8 2.8 2.7 2.7 4.5 4.4 4.3 4.1 4.0 22.2 28.1 34.0 30.5 29.8 30.9 39.4 48.0 44.8 44.
718446-YTG-A-0811 Airflow Performance Side Duct Application DNX024-060 Size (Tons) Model Mode Low Cool High N036 024 (2.0) DNX N056 Heat D056 Low Cool High N065 036 (3.
718446-YTG-A-0811 DNX024-060 (Continued) Size (Tons) Model Mode Low Cool High N065 N090 048 (4.
718446-YTG-A-0811 Bottom Duct Application DNX024-060 Size (Tons) Model Mode Low Cool High N036 024 (2.0) DNX N056 Heat D056 Low Cool High N065 036 (3.
718446-YTG-A-0811 DNX024-060 (Continued) Size (Tons) Model Mode Low Cool High N065 N090 048 (4.
718446-YTG-A-0811 Gas Heat Minimum Supply Air Supply Air (CFM) Size (Tons) Model 024 (2.0) DNX 036 (3.0) DNX 048 (4.0) DNX Heat Size Cooling Min 450 450 450 685 685 685 930 930 930 930 930 N036 N056 D056 N065 N090 D090 N065 N090 D090 N110 D110 Heating Max 900 900 900 1350 1350 1350 1700 1700 1700 1700 1700 Min 610 860 860 1080 1070 1070 1080 1230 1230 1330 1330 Max 1330 1730 1730 2370 1780 1780 2370 2290 2290 2220 2220 Indoor Blower Specifications Size (Tons) HP RPM Motor Eff.
718446-YTG-A-0811 Typical DNX024-048 Wiring Diagrams Typical DNX024 Cooling Unit with Single Stage Gas Heat 208/230-1-60 volt Wiring Diagram 18 Johnson Controls Unitary Products
718446-YTG-A-0811 Typical DNX024 Cooling Unit with Two Stage Gas Heat 208/230-1-60 volt Wiring Diagram Johnson Controls Unitary Products 19
718446-YTG-A-0811 Typical DNX036-048 Cooling Unit with Single Stage Gas Heat 208/230-1-60 volt Wiring Diagram 20 Johnson Controls Unitary Products
718446-YTG-A-0811 Typical DNX036-048 Cooling Unit with Two Stage Gas Heat 208/230-1-60 volt Wiring Diagram Johnson Controls Unitary Products 21
718446-YTG-A-0811 Typical DNX036-048 Cooling Unit with Single Stage Gas Heat 208/230-3-60 volt Wiring Diagram 22 Johnson Controls Unitary Products
718446-YTG-A-0811 Typical DNX036-048 Cooling Unit with Two Stage Gas Heat 208/230-3-60 volt Wiring Diagram Johnson Controls Unitary Products 23
718446-YTG-A-0811 Typical DNX036-048 Cooling Unit with Single Stage Gas Heat 460-3-60 volt Wiring Diagram 24 Johnson Controls Unitary Products
718446-YTG-A-0811 Typical DNX036-048 Cooling Unit with Two Stage Gas Heat 460-3-60 volt Wiring Diagram Johnson Controls Unitary Products 25
718446-YTG-A-0811 Weights and Dimensions DNX Unit Weights Unit 4 Point Load Weight "D" CENTER OF GRAVITY FRONT OF UNIT "C" "A" 49-1/8 X "B" Weight (lbs.) Center of Gravity Size Model (Tons) Shipping Operating X Y 024 DNX 445 440 20 24.5 (2.0) 036 DNX 485 480 20 24 (3.0) 048 DNX 505 500 20 24 (4.0) 26 47-1/4 Y 4 Point Load Location (lbs.
718446-YTG-A-0811 Gas Unit Dimensions VENT AIR OUTLET HOOD GAS SUPPLY 1-1/4" DIAMETER HOLE (1/2" NPTF CONNECTION) BLOWER SERVICE ACCESS COMPARTMENT PANEL CONDENSER COIL UNIT CONDENSATE CONNECTION 3/4" NPTF (TRAP RECOMMENDED) A 2-3/8 HIGH VOLTAGE CONN. 1-3/8" DIA. KNOCKOUT B 3-3/4 REFRIGERANT CONNECTIONS 2-1/2 COMBUSTION AIR INLET LOUVERS GAS SUPPLY 1-1/4" DIA. KNOCKOUT (1/2" NPTF CONNECTION) LOW VOLTAGE CONN.1-3/8" DIA.
718446-YTG-A-0811 Unit Dimensions Front and Bottom HIGH VOLTAGE CONN. 1-3/32" DIA. KNOCKOUT 8-7/8 11-7/8 19-1/4 FRONT GAS SUPPLY 1-5/8" DIA. KNOCKOUT (1/2" NPTF CONNECTION) LOW VOLTAGE CONN. 7/8" DIA. KNOCKOUT LOW VOLTAGE CONN. 7/8" DIA. KNOCKOUT HIGH VOLTAGE CONN.
718446-YTG-A-0811 Unit Typical Duct Applications ROOF CURB INSTALLATION REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION Unit Typical Slab on Ground Installation (Gas Model Shown) TO POWER SUPPLY FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REAR OF UNIT CONTROL WIRING TO INDOOR THERMOSTAT RETURN AIR DUCT SUPPLY AIR DUCT TO GAS SUPPLY LINE MANUAL GAS SHUT-OFF VALVE Johnson Controls Unitary Products 29
718446-YTG-A-0811 Unit Typical Roof Curb Installation (Gas Model Shown) MANUAL GAS SHUT-OFF VALVE FIELD SUPPLIED DISCONNECT SWITCH MOUNTED ON UNIT TO POWER SUPPLY TO GAS SUPPLY LINE CONTROL WIRING TO INDOOR THERMOSTAT RETURN AIR DUCT SUPPLY AIR DUCT Unit Accessory Dimensions Roof Curb1 RECOMMENDED DUCT SIZE 17-1/2" x 16-3/4" 42-2/3 40-3/4 3-1/2 45-1/8 17-5/8 17-1/4 43-1/4 OPENING FOR RETURN AIR DUCT 22 OPENING FOR SUPPLY AIR DUCT 14 1 RECOMMENDED DUCT SIZE 17-1/8" x 21-1/2" 1.
718446-YTG-A-0811 Roof Curb Cross Section 2 1" 3/4" x 1" WIDE GASKETING FOR CURB FRAME AND ALL DUCT SUPPORT SURFACES UNIT BASE UNIT BASE RAIL WOOD NAILER COUNTERFLASHING 8" MIN.